Specifications
AHU 800
Max. water temperature (°F/C°)
195 / 90
Coil performance at 180°F (Btu/hr)
66,800
Water pipe connections (inches)
¾
External static pressure (" wc)
.7
Max. operating water pressure (PSI)
150
Width (inches)
17.6
Depth (inches)
26
Height (inches)
32
Supply air opening width (inches)
16
Supply air opening depth (inches)
19.5
Left and right return air opening height (inches)
7
Left and right return air opening width (inches)
23
Bottom return air opening width (inches)
13
Bottom return air opening depth (inches)
23
Max. internal current power rating 120Volts (Amp)
2.4
External pump supply 120V (Amp)
5
Voltage (V)
120
Max. air flow @ rated static pressure (CFM)
1000
Maximum return air temperature (°F/C°)
122 / 50
Filter size (MERV 8) (inches)
16 x 25 x 1
7
Specifications
Summary of Contents for AHU Series
Page 1: ...Installation and Operating Manual AHU SERIES Air Handling Unit AHU 800...
Page 2: ......
Page 5: ...Air handling unit parts diagram 58 3...
Page 6: ...This page is intentionally left blank...
Page 14: ...This page is intentionally left blank...
Page 59: ...This page is intentionally left blank...
Page 60: ...Air handling unit parts diagram 58 Section Service and maintenance...