SL 20-115 MODULATING GAS BOILER
5.3.5 Miscellaneous
SYMPTOM
DIAGNOSIS
REMEDY
FUMES AND HIGH HUMIDITY
Improperly installed
condensate trap
refer to installation/operation instructions
Leak in vent piping
inspect using soap solution
Flue gas leak within
boiler
Visually inspect all mechanical connections
SYMPTOM
DIAGNOSIS
REMEDY
TEMPERATURE ExCEEDS
THERMOSTAT SETTING
Incorrect anticipator
setting.
Check with ammeter.
Thermostat not level.
Check level.
ONE OR MORE ZONES DO
NOT HEAT PROPERLY
Air trapped within
zone(s) piping
Vent system/zone as required.
Insufficient radiation/
excessive heat loss.
Check actual length of pipe using radiation / heat
loss calculation.
Insufficient flow rate
to zone(s).
Check temperature drop across zone.
Defective zone valve/
zone circulator.
Check operation per manufacturer’s instructions.