• As an alternative, the VariMax50 NG can have an external rotation monitor (magnet 

mounted on the rotor with an associated rotation monitor). This is connected at terminal 

connections 9 and 10, and the DIP switch for the “External rotation monitor” should be 

in the ON position.

• 

If both types of rotation monitor are to be deactivated, an 820 ohm resistor (1% ¼ W) is 

installed between terminal connections 9 and 10.

• 

The VariMax50 NG has a built-in cleaning function. 

The function can be disconnected via DIP switches.

• 

VariMax50 NG only needs a shielded cable and EMC gland to the motor. Other 

cables do not need to be shielded or EMC glands.

• The VariMax50 NG starts automatically following a power failure,  

and resets all alarms upon restarting.

• The VariMax50 NG is a stepper motor with high torque throughout its speed range.

• The VariMax50 NG motor has no built-in thermal contact. The control unit  

regulates power and makes sure the motor will not overheat.

• A holding torque is activated when the motors is stopped, which makes sure the rotor 

remain static. The holding torque is lost if power to the control unit is cut.

• The motor is mounted with a 3 m cable as standard. 

-----------------------------------------------------------------------------------------

We use FreeRTOS v6.1.0 (http://www.freertos.org) 

 

in this product; we are 

able to provide the source code.

5

4

Continued from previous page

Summary of Contents for VariMax50

Page 1: ...IBCcontrol NG MANUAL CONTROL UNIT FOR ROTARY HEAT EXCHANGER VariMax50 M ade in S w ed en Since 1983 Since 1983 Ska vara 25 mm i diameter p h jden Article no F21050305...

Page 2: ......

Page 3: ...chnical data control unit 6 Technical data motor 6 Functions 6 DIP switch 7 Operational indications 7 Alarms 8 9 Settings via potentiometer 9 Reset 9 Connection diagram 10 Connections 10 11 Input sign...

Page 4: ...cycling When replacing components or when the control unit must be replaced in its entirety please follow the advice below The aim should always be maximum possible recycling of raw materials with min...

Page 5: ...afety during operation 3 MANUFACTURER S DECLARATION Manufacturer IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Product Control unit for rotary heat exchanger Type designation VariMax50 NG...

Page 6: ...ated when the DIP switch for the External rotation monitor is in the OFF position The internal rotation monitor performs measurements at different times depending on whether the speed of the motor is...

Page 7: ...ble and EMC gland to the motor Other cables do not need to be shielded or EMC glands The VariMax50 NG starts automatically following a power failure and resets all alarms upon restarting The VariMax50...

Page 8: ...A Exact value cannot be obtained with a digital measuring instrument TECHNICAL DATA CONTROL UNIT Max moment 4 Nm Min rpm 1 rpm Max speed rpm 375 rpm Motor temperature mantle max 110 O C Shaft diamete...

Page 9: ...N Low speed The rotor rotates at the pre set min speed 1 rpm when the DIP switch is set to ON Modbus termination If the control unit is last in the Modbus loop the DIP switch must be in the ON positio...

Page 10: ...if two consecutive measurements indicate that the rotor is not rotating For more information see Description of functions on page 4 Broken belt Belt slipping Stuck wheel Generates an alarm and trips i...

Page 11: ...resetting the control unit The control unit is also reset in the event of voltage drop out and closure between terminal 11 and 12 Motor temperature The control unit regulates power and makes sure the...

Page 12: ...rrent circuit breaker may be connected Motor U V W A VariMax50 NG motor must be used Direction of rotation is changed by switching two of the phases Manual speed A1 A2 Produces set rotation speed on c...

Page 13: ...nt of alarm The control unit is reset automatically in the event of voltage drop out Alarm relay 13 14 15 Closes between 14 15 in the event of an alarm or voltage drop out Max 0 5 A resistive load 30...

Page 14: ...make sure the DIP switch is set to OFF Checking the cleaning function Switch off the voltage Make sure the Cleaning function DIP switch is set to ON and the input signal is disconnected After switchi...

Page 15: ...ielded Motor NCY HAR UL CSA 4G0 75 Shielded Input signal 2 0 34 0 5 Does not need shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EM...

Page 16: ...IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Tel 46 42 33 00 10 www ibccontrol se info ibccontrol se IBCcontrol F21050905GB VERSION 1 0 2020 10 01...

Reviews: