IBC control MicroMax750 Manual Download Page 7

• 

The MicroMax750 is part of a range of control units adapted, with the necessary  

additional functions, for optimum control of rotating heat exchangers.  

The series consists of four sizes, MicroMax, MicroMax180, MicroMax370 and  

MicroMax750.  

All of the control units drive three-phase induction motors with associated gearing;  

the control unit designation denotes motor output.  

All control units have an input signal of 0-10 V.

• 

MicroMax750 is designed for wheels up to 5000 mm mm with a wheel speed of max  

12 rpm. If a faster wheel speed is necessary, rotor diameter should be reduced.

• 

Heat exchanger rpm and thus thermal efficiency are governed by the control unit so that 

wheel speed is proportional to the input signal from the control centre.

• 

MicroMax750 has a preset threshold value of 0.1 V (hysteresis 0.13–0.07 V).

 

If the input signal falls below this value, the wheel will stop. 

• 

MicroMax750 has a rotation monitor (magnet mounted on the wheel with associated  

magnetic sensor) and built-in cleaning function. 

The functions can be disconnected via DIP switches.

• 

MicroMax750 starts automatically following voltage drop-out, and resets all alarms on 

restart.

• 

The motor should not be disconnected from the control unit while under load.

DESCRIPTION OF FUNCTIONS

4

5

Summary of Contents for MicroMax750

Page 1: ...IBCcontrol Made in Sweden MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER MicroMax750 Article no F21075401...

Page 2: ......

Page 3: ...5 Technical data 6 Functions 6 DIP switch 7 Operational indications 7 Alarms 8 9 Settings via potentiometer 9 Push button 9 Connection diagram 10 Connections 10 Checks before powering up the control u...

Page 4: ...t Disposal and recycling When replacing components or when the control unit in its entirety need replacing please follow the advice below The aim should always be maximum possible recycling of raw mat...

Page 5: ...in power before removing the cover Never touch electrical components or contacts while main current is switched on Risk of electric shock resulting in serious injury or death Residual voltage remains...

Page 6: ...EMC Directive 2004 108 EC All control units are approved according to the requirements of the EMC Directive 2004 108 EC and are tested according to standard EN 61800 3 2004 emission category C1 and im...

Page 7: ...peed is necessary rotor diameter should be reduced Heat exchanger rpm and thus thermal efficiency are governed by the control unit so that wheel speed is proportional to the input signal from the cont...

Page 8: ...ower input max 1100 W Input current max 5 0 A External fuse max 10 A Output voltage 3x0 230 V Min frequency Fixed 4 Hz Max frequency 40 100 150 Hz Motor output max 750 W Motor current 3 6 A Exact valu...

Page 9: ...l rotates at the set maximum rpm when the switch is set to ON After a test run make sure the DIP switch is set to OFF Low speed The wheel rotates at the fixed minimum rpm when the switch is set to ON...

Page 10: ...o normal mode when the temperature drops See Overcurrent on page 9 Overvoltage Alarms and trips if the connection voltage exceeds 276 V for more than 4 5 seconds Undervoltage Alarms and trips if the p...

Page 11: ...after 4 5 seconds The motor is too small in relation to rotor diameter Wheel rotation sluggish Damaged motor e g bearing fault Measure amperage NOTE Precise voltages and amperages can only be obtaine...

Page 12: ...Must be jumped if the temperature switch is not connected Alarm relay 13 14 15 Closes between 14 15 in the event of an alarm or voltage drop out Max 8 A resistive load 250 V AC Input signal 2 3 0 10...

Page 13: ...hases to the motor Adjustment of max speed Set the High Speed DIP switch to the ON position Adjust Max speed so that the wheel rotates at 10 12 rpm or as per directions from wheel manufacturer After a...

Page 14: ...LAND Motor cable lflex Classic 110 CY 7G0 75 Shielded Incoming EKK 3G1 5 Not shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EMC Dir...

Page 15: ...YOUR NOTES 13...

Page 16: ...IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Tel 46 0 42 33 00 10 Fax 46 0 42 33 03 75 www ibccontrol se info ibccontrol se IBCcontrol F21075901 Version 2 0 2015 07 01...