ibaMS16xDO-2A
Manual
Issue 1.3
15
Pin assignment
X5 Pin
Connection
LED X6 Pin
Connection
LED
1
Digital output 00 +
L10
1
Digital output 08 +
L18
2
Digital output 00
−
2
Digital output 08
−
3
Digital output 01 +
L11
3
Digital output 09 +
L19
4
Digital output 01
−
4
Digital output 09
−
5
Digital output 02 +
L12
5
Digital output 10 +
L20
6
Digital output 02
−
6
Digital output 10
−
7
Digital output 03 +
L13
7
Digital output 11 +
L21
8
Digital output 03
−
8
Digital output 11
−
9
Digital output 04 +
L14
9
Digital output 12 +
L22
10
Digital output 04
−
10
Digital output 12
−
11
Digital output 05 +
L15
11
Digital output 13 +
L23
12
Digital output 05
−
12
Digital output 13
−
13
Digital output 06 +
L16
13
Digital output 14 +
L24
14
Digital output 06
−
14
Digital output 14
−
15
Digital output 07 +
L17
15
Digital output 15 +
L25
16
Digital output 07
−
16
Digital output 15
−
7.3.2
Circuit design
Important note
Please consider for all applications, that the load switch can only work with the correct
polarity. If polarity is wrong, the load switch is permanent conductive and all the self-
protective functions that can only be effective when the load switch is switched off, be-
come ineffective.
Note
Please do not connect 2 channels in series in contrary direction for having a non-polar-
ized (AC-) switch.
Each individual channel can be used as kind of a relay. For each channel there are only
the output chchannel and –channel (2-conductor technology), they can have
any potential difference to each other channel, to the grounding or to the current supply.
The channels can be operated as equivalent of an N-switch or between 2 load re-
sistances (in any combination). You can also connect several channels in series or in
parallel, e.g. for switching high load currents or realizing logical circuits.