Manual
ibaBM-DDCS
20
Issue 1.11
Important note
When acquiring data sets in a star topology, ensure that the connected drives are set to
“Star” topology.
In DriveWindow, the parameter “CH0 HW CONNECTION” in the parameter set “DDCS
Control” of each drive has to be checked and set to “STAR”.
In some drives, e.g. ACC800, there are several user sets. The topology setting must be
set in all used user sets. The user sets can be loaded and saved in the parameter
“APPLICATION MACRO” of the set “START-UP DATA“ (z.B. Par. 99.03).
Settings at the branching unit NDBU-95
Address settings (S1):
Address range 76 … 124
Default setting (01111100) = 0x7C.
S1
ON DIP
OFF
1 2 3 4 5 6 7 8
Operating mode selection (X13):
adjust to REGEN mode
Select transfer rate (X12):
Default value for CH0: 4 Mbit/s
1
The parameter set is in the protected area (set 105) in some drives, e.g. ACC800. In this case, a 4-digit
code has to be entered in the parameter „PASS CODE“ of the set „SYST CTR INPUTS“ (e.g. Par 16.03) in
order to have access to the protected area. Please contact ABB, when the code is unknown.