Loadcell (Dedicated Option for SCON-CA) 

This is the pressing force measurement unit that is used for the force control. 
This is used by connecting to the actuator corresponding to the force control. 
[Specification]

 

Item Specification 

Loadcell System 

Strain Gauge 

Rated Capacity 

20000N 

Allowable Overload 

200%R.C

*1

 

Loadcell Accuracy 

±

1%R.C

*1

 

Zero 

±

0.2%R.C/10

°

C

 

Temperature Drift 

Output 

±

0.1%R.C/10

°

Applicable Temperature Range 

0 to 40

°

*1  R.C.: Rated Capacity 

[Refer to RCS2-RA13R Instruction Manual for details of how to attach and the dimensions.]

 

Installation Environment, Storage Environment 

This product is capable for use in the environment of pollution degree 2

*1

 or equivalent. 

*1  Pollution Degree 2: Environment that may cause non-conductive pollution or transient conductive 

pollution by frost (IEC60664-1) 

1. Installation Environment 

Do not use this product in the following environment 

  Location where the surrounding air temperature exceeds the range of 0 to 40

°

  Location where condensation occurs due to abrupt temperature changes 

  Location where relative humidity exceeds 85%RH 

  Location exposed to corrosive gases or combustible gases 

  Location exposed to significant amount of dust, salt or iron powder 

  Location subject to direct vibration or impact 

  Location exposed to direct sunlight 

  Location where the product may come in contact with water, oil or chemical droplets 

  Environment that blocks the air vent [Refer to Installation and Noise Elimination] 

When using the product in any of the locations specified below, provide a sufficient shield. 

  Location subject to electrostatic noise 

  Location where high electrical or magnetic field is present 

  Location with the mains or power lines passing nearby 

2.  Storage and Preservation Environment 

The storage and preservation environment should comply with the same standards as those for the 
installation environment. In particular, when the machine is to be stored for a long time, pay close 
attention to environmental conditions so that no condensation forms. Unless specially specified, 
moisture absorbency protection is not included in the package when the machine is delivered. In 
the case that the machine is to be stored and preserved in an environment where condensation is 
anticipated, take the condensation preventive measures from outside of the entire package, or 
directly after opening the package. 

Installation and Noise Elimination 

1.  Noise Elimination Grounding (Frame Ground) 

 
 

 
 
 
 
 
 
 
 
 

2.  Precautions regarding wiring method 

1)  Wire is to be twisted for the 24V DC power supply. 
2)  Separate the signal and encoder lines from the power 

supply and power lines. 

3.  Noise Sources and Elimination 

Carry out noise elimination measures for power devices on 
the same power path and in the same equipment. 
The following are examples of measures to eliminate noise 
sources. 
1)  AC solenoid valves, magnet switches and relays 

[Measure] Install a Surge absorber parallel with the coil. 

2)  DC solenoid valves, magnet switches and relays 

[Measure] Mount the windings and diodes in parallel. 

Select a diode built-in type for the DC relay 

4.  Heat Radiation and Installation 

Design and Build the system considering the size of the controller box, location of the controller and 
cooling factors to keep the ambient temperature around the controller below 40

°

 
 
 
 
 
 
 
 
 
 
 

 

Connection Diagram 

 Standard 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  For Models Equipped with brake Except for RCS2-RA13R and NS Actuators 

 
 
 
 
 
 
 
 
 
 
 

  RSC2-RA13R Equipped with Brake, with no Loadcell, or NS Actuators with Brake 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  RCS2-RA13R Equipped with no Brake, with Loadcell in SCON-CA 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  RCS2-RA13R Equipped with Brake and Loadcell in SCON-CA 

 
 
 
 
 

 

Power Supply and Emergency Stop Circuit 

  Wiring for Power Supply (to be prepared by customer) 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Power consumption of SCON varies depending on the connected actuator, etc. Select the circuit breaker that suits to the 
specification. 
[Refer to Basic Specifications] 
A ground fault circuit interrupter needs to be selected carefully considering the purposes of prevention of fire and protection 
of human. 
Have a measurement of the leak current where a ground fault circuit interrupter is to be installed. 
Use the “harmonic type” for the ground fault circuit interrupter. 

*1  CLF : Clamp Filter  …  It is recommended to attach it to improve noise immunity. 
*2  SK  : Surge Killer  …  It is recommended to attach it to improve noise immunity. 
*3  NF  : Noise Filter  …  Make sure to install it. It is recommended to have it installed within 0.3m of the cable length from 

SCON. 

Parts Name 

Supplier 

Model 

CLF Clamp 

Filter 

TDK 

ZCAT3035-1330 

SK 

Surge Protector 

Okaya ELECTRIC CO.,LTD

R·A·V-781BWZ-2A 

SOSHIN ELECTRIC CO.,LTD

NF2010A-UP 

NF Noise 

Filter 

DENSEI-LAMBDA MC1210 

  Wiring for Emergency Stop Input 

The following diagram shows an example of how the emergency stop switch for the teaching pendant may be 
included in the emergency stop circuit you may construct. 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Note 1  When the teaching pendant is not connected, S1 and S2 become short-circuited inside the controller. 
Note 2  Connect a contactor to L1 and L2 terminals for external power cutoff by the emergency stop if the motor power is 

required to be cut off externally to comply with the Safety Categories. 

Note 3  The rating for the emergency stop signal to turn ON/OFF at contact CR1 is 24V DC and 10mA. 
Note 4  For CR1, select the one with coil current 0.1A or less. 

Attached to RCS2-RA13R 

Loadcell

Regenerative Resistor Unit
(REU-2 : option)
 Required depending 
 on usage condition

LED Indication

Axis Number 
Setting Switch

Pulse Train Mode 
Changeover Switch

System 
I/O Connector

CB-SC-REU010

CB-ST-REU010

Regenerative Resistor Unit
(REU-1 [for secondary unit] : option)

Power Supply 
Connector

FG Connection 
Terminal

Absolute Battery

(for Absolute Type)

Mode Changeover Switch

Brake Release Switch
Brake Power Supply Connector

AK-04 (option)
Converts PLC open 
collector output into 
differential pulse output

JM-08 (option)
Converts SCON differential 
pulse output into open 
collector output

Flat Cable
(Accessories)

PLC 
(Please prepare separately)

Touch panel teaching (option),
or Teaching pendant (option)

PC Software (option)

Detail View of Pulse Train Mode Changeover Switch

Pulse Train Mode Changeover Switch No. 1
ON: to select Pulse Train Control Mode
OFF: to select Positioner Mode

Actuator
The following models are excluded:

 RCS2-RA13R with brake or loadcell equipped

 NS Actuators with brake equipped

AK-04

JM-08

Wiring for Pulse 
Train Control Mode

SW

ADRS

1 2

ON

CB-RCS2-PLLA

RCS2-RA13R
(with Loadcel)

Absolute Battery

(for Absolute Type)

24V DC

Power Supply for Brake

Absolute Battery

(for Absolute Type)

Actuator
The following models are excluded:

 RCS2-RA13R with brake or loadcell equipped

 NS Actuators with brake equipped

24V DC

Power Supply for Brake

For LS (option)

Brake Box

CB-RCS2-PLA010
(enclosed to Brake Box)

For LS (option)

• 

NS Actuators  (with Brake

• 

RCS2-RA13R (with Brake

Connect to back side

Absolute Battery

(for Absolute Type)

CB-LDC-LTL

CB-RCS2-PLLA

RCS2-RA13R
(with Loadcell and Brake)

CB-RCS2-PLA (enclosed to Brake Box)

24V DC

Brake Box
RCB-110-RA13-0

Connect to back side

Absolute Battery

(for Absolute Type)

Power Supply for Brake

100V AC
or
200V AC
(Refer to Controller 
 Power Voltage Specifications)

Circuit 
Breaker

Ground Fault 
Circuit 
Interrupter

*3

NF

*2

SK

CLF

Class D grounding

(Formerly Class-III grounding)

+24V

0V

24V DC
Power 
Supply

SCON

AC Power Supply 
Input Connector

B. Motor Power Unit

A. Control power supply

L1

L2

L1C

L2C

NC

PE

BK+

PWR-

Brake Power Supply 
Input Connector

PIO 
Connector

Brake 
Release Box

*1

10mm or more

50mm
or more

50mm
or more

50mm
or more

50mm
or more

50mm
or more

50mm
or more

100mm
or more

30mm
or more

10mm
or more

100mm
or more

150mm 
or more

Air Flow

Air Flow

Fan

Brake Box

Regenerative 
Resistor Unit

Place a fan to make the 
ambient temperature even

Earth Terminal

Connect using FG connection
terminal on the main unit.

Copper Wire : 
Connect to an ground cable with
diameter 1.6mm or more.

Controller

Class D grounding
(Formerly Class-III grounding :
Grounding resistance at 100

Ω

 or less)

Do not share the ground wire with or connect 
to other equipment. Ground each controller.

Controller

Other 

equipment

Controller

Other 

equipment

Other 

equipment

Surge absorber

Relay 
coil

Relay coil

R

C

+24V

0V

+24V

0V

+

-

24V

Emergency stop 
reset switch

Emergency stop 
switch

Emergency stop switch 
for the teaching pendant

(Note 1)

SCON-CA

First unit

SCON

-CA

Second 

unit

SCON

-CA

Nth unit

S1

S2

S1

S2 S1

S2

CR1

(Note 1)

0V

MC1

CR1

CR1

CR1

(Note 1)

MC1

(Note 2)

AC100V
AC200V

SCON-CA

EMG+

EMG-

L1

L2

L1C

L2C

24V

Motor power cutoff relay

Motor 
power supply

Control 
power supply

CR1

(Note 1)

MC1

(Note 2)

AC100V
AC200V

EMG+

EMG-

L1

L2

L1C

L2C

SCON-CA

Second unit

CR1

(Note 1)

MC1

(Note 2)

AC100V
AC200V

EMG+

EMG-

L1

L2

L1C

L2C

SCON-CA

Nth Unit

Summary of Contents for scon

Page 1: ...er the power is turned on at 40 C Note that the value of in rush current differs depending on the impedance of the power supply line 2 Leak current varies depending on the capacity of connected motor cable length and the surrounding environment Measure the leak current at the point where a ground fault circuit interrupter is to be installed when leakage protection is conducted A ground fault circu...

Page 2: ... 2 SK Surge Killer It is recommended to attach it to improve noise immunity 3 NF Noise Filter Make sure to install it It is recommended to have it installed within 0 3m of the cable length from SCON Parts Name Supplier Model CLF Clamp Filter TDK ZCAT3035 1330 SK Surge Protector Okaya ELECTRIC CO LTD R A V 781BWZ 2A SOSHIN ELECTRIC CO LTD NF2010A UP NF Noise Filter DENSEI LAMBDA MC1210 Wiring for E...

Page 3: ...y alarm overload alarm or message level alarm is occurred Signal Assignment for Each Mode The signal assignment of I O flat cable by the PIO pattern is as shown below Follow the following table to connect the external equipment such as PLC Corresponding Type All Types Selection in Parameter No 25 PIO Pattern 0 1 2 3 Category PIO Functions Positioning mode Teaching mode 256 point mode 512 point mod...

Page 4: ... the alarm to have the right treatment CAUTION Please perform this process with the actuator away from the mechanical end or interfering subjects as much as possible Put the actuator away if it interferes with surroundings It may generate an alarm if the actuator hit the mechanical end or interfering subjects when the servo is turned on The slider may get slightly dropped by self weight if servo o...

Reviews: