External Dimensions 

 
 
 
 
 
 
 
 
 

 
 
 
 
 

Installation Environment 

This product is capable for use in the environment of pollution degree 2*1 or equivalent. 
*1 Pollution Degree 2 :  Environment that may cause non-conductive pollution or transient conductive 

pollution by frost. (IEC60664-1) 

1. Installation Environment 

Do not use this product in the following environment. 

  Location where the surrounding air temperature exceeds the range of 0 to 40

°

C

 

•  Location where condensation occurs due to abrupt temperature changes 
•  Location where relative humidity exceeds 85%RH 
•  Location exposed to corrosive gases or combustible gases 
•  Location exposed to significant amount of dust, salt or iron powder 
•  Location subject to direct vibration or impact 
•  Location exposed to direct sunlight 
•  Location where the product may come in contact with water, oil or chemical droplets 
•  Environment that blocks the air vent [Refer to Installation and Noise Elimination Section] 

When using the product in any of the locations specified below, provide a sufficient shield. 

•  Location subject to electrostatic noise 
•  Location where high electrical or magnetic field is present 
•  Location with the mains or power lines passing nearby 

2.  Storage and Preservation Environment 

The storage and preservation environment should comply with the same standards as those for the installation 
environment. In particular, when the machine is to be stored for a long time, pay close attention to environmental conditions 
so that no condensation forms. Unless specially specified, moisture absorbency protection is not included in the package 
when the machine is delivered. In the case that the machine is to be stored and preserved in an environment where 
condensation is anticipated, take the condensation preventive measures from outside of the entire package, or directly after 
opening the package. 

 

Installation and Noise Elimination 

1.  Noise Elimination Grounding (Frame Ground) 
 

 
 
 
 
 
 
 

 

2.  Precautions regarding wiring method 

(1) Twist the wires for the 24V DC power unit. 
(2) Separate the communication line from the power line. 

3.  Noise Sources and Elimination 

Carry out noise elimination measures for power devices on the same 
power path and in the same equipment. 
The following are examples of measures to eliminate noise sources. 

(1) AC solenoid valves, magnet switches and relays 

[Measure]  Install a Surge absorber parallel with the coil. 

(2) DC solenoid valves, magnet switches and relays 

[Measure]  Install a diode parallel with the coil. Use a DC relay with 

a built-in diode. 

4.  Heat Radiation and Installation 

Design and Build the system considering the size of the controller box, location of the controller and cooling factors to keep 
the ambient temperature around the controller below 40

°

C. 

 

 
 
 
 
 
 
 
 
 
 
 
 

System Configuration (Example) 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note : Have the 0V line in common for the 24V power supply for each controller (except for SCON). 

 

Power Supply and Emergency Stop Circuit (Example) 

There is no emergency stop function for Gateway Unit. Perform the emergency stop using the control on the 
system side. CR is an emergency stop relay for the entire system. While the connector port for the teaching 
pendant and PC is on, the contact signal of the emergency stop switch can be output externally, thus the 
emergency stop circuit of the system can be constructed. Also, Switching on/off of the port can be performed 
not only on the port switch on the main unit of Gateway Unit, but also by the external signal. Shown below is 
the relation between switching on/off of the port and the emergency stop signal output. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

External Port 

Switchover Input 

Port Switch 

Emergency Stop Signal Output

(Push Button Switch) 

Teaching pendant/ 

Connector Port for PC 

OFF OFF  Disable 

(ON) Disable 

ON OFF 

OFF ON 

ON ON 

Enable 

(Always ON 

=

 b contact) 

Enable 

 

 

SIO Communication Line Wiring Layout 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

There should be no problem to have a terminal block connection 
instead of a 4-way junction. 
Use a terminal block connection or direct-joint connection if 
there is a concern that a faulty connection may occur as a result 
of using the E-Con connector. 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

17.5 17.5

φ

5 Hole

178.5

170.5

161

68.1

RCM-GW-DV

RCM-GW-CC

RCM-GW-PR

(Note) Dimensions are the same for all the models.

5

Surge Absorber

Relay 
Coil

Relay Coil

R

C

+24V

0V

+24V

0V

+

-

Earth Terminal

Attach the ground screw 
terminal to the earth ground.

Annealed copper wire: 
Connect a ground wire with a 
diameter of 1.6 mm or larger.

Controller

Class D grounding

(Grounding resistance at 100

Ω

 or less)

Controller

Controller

Other 
equipment

Other 
equipment

Other 
equipment

Do not share the ground wire with or connect to 
other equipment. Ground each controller.

100

50

30

30

30

100

(                        )

(          )

Emergency 
stop switch

Teaching 
pendant

Emergency Stop Circuit on System Side

Emergency 
stop reset

CR

CR

Teaching pendant

Emergency 
stop

Gateway Unit

Teaching pendant/
Connector for PC software

ON

24V

Port Switch

RY

S1

S2

N

24V

PORT

IN

PORT

N

OFF

ON

Teaching pendant

Emergency Stop Signal Output

Allowable Load Voltage : 30V DC
Allowable Load Current : 1A

Gateway Power Supply

24V DC

±

10%

MAX. 300mA

External Port Switchover Input

(Please prepare separately)

OFF

ON

(Load 24V DC 7mA)

Port Switch

E-Con Connector

Press Welding

Locking 
Claw

Shrink Tube

Double Shield Cable

(AWG22)

Pin No. of E-Con Connector

Locking 
Claw

4 3 2 1

• Make sure to select the right 
  cable size.
• Do not peel off the sheath.

Link Cable
(with a E-Con connector)

E-Con Connector
(with the terminal 
resistance)

Junction

E-Con Connector

■ Controller Link Cable
(enclosed with E-Con connector, junction and terminal resistance)
Model CB-RCB-CTL002

4-1473562-4 
(Manufactured by AMP)

5-1473574-4 
(Manufactured by AMP)

Note

If Gateway Unit is used as a terminal, 
refer to “Field Network Wirings and 
Settings” for how to mount or set the 
terminal resistance.

Note

PLC

DeviceNet/CC-Link/PROFIBUS

Gateway Unit
DeviceNet Type
<Model RCM-GW-DV>

CC-Link Type
<Model RCM-GW-CC>

PROFIBUS Type
<Model RCM-GW-PR>

Teaching Pendant

Switching ON/OFF of the teaching 
port can be performed not only 
on the front panel, but also by 
the external signal.
Be careful when handling the 
external signals.
[Refer to “Power Supply and 
 Emergency Stop Circuit 
 (Example)” for the details.]

SIO Communication Line

Port Switch

24V DC 
power supply

Recommended Cable (Taiyo Cabletec Corporation)
HK-SB/20276 

×

 L [m]

2P 

×

 AWG22

to be prepared by customer. 

e-Con connector

Junction

Power I/O Cable for SIO Type
CB-ERC2-PWBIO***

Terminal Resistance R 

=

 220

Ω

Network Connection Cable
CB-ERC2-CTL001

0.2m

0.2m

0.2m

Controller Link Cable
Model : CB-RCB-CTL002

1st unit

2nd unit

15th unit

16th unit

Connectable Controller     ERC2/PCON/ACON/SCON

ERC2 (SIO type)

Gateway Unit

PORT IN

PORT N

SDA

SDB

GND

FG

Double Shield Cable
Recommended :
Taiyo Electric Wire & Cable
HK-SB/20276 

×

 L

2P 

×

 AWG22

4-way junction (Manufactured by AMP : 5-1473574-4)

E-Con connector
(Manufactured by AMP : 4-1473562-4)
Housing color : GN

E-Con connector
(Manufactured by AMP : 3-1473562-4)
Housing color : OR

1st unit

Controller Link Cable
CB-RCB-CTL002

1

2

3

4

1

2

3

4

1

2

3

1

2

7

4

1

2

3

4

SGA

SGB

GND

2nd unit

1

2

7

SGA

SGB

GND

YW

OR

BL

YW

OR

BL

1

2

3

4

1A

1B

5B

1

2

1

2

SGA

SGB

GND

OR (RD1)

OR (BK1)

OR (RD1)

OR (BK1)

OR (BK1)

0V

Connect to Junction

(Connect to 0V on ERC2 
 24V power supply)

ERC2-NP/PN

• Power I/O Cable for PIO Type
  Accessory Cable for CB-ERC-PWBIO***

E-Con Connector

Terminal Block

J.S.T. Mfg. V0.5-3

Prepare the outlined cable section separately.
(Recommended cable: HK-SB/20276 

×

 L [m] 2P 

×

 AWG22 supplied by 

 Taiyo Cabletec Corporation)

For ERC2 (PIO type)
For SIO Type, connection to a 4-way junction is available with the network connection cable (CB-ERC2-CTL001). 
For PIO Type, perform the wiring as shown below with using a device such as a terminal block.

Summary of Contents for RCM-GW

Page 1: ...ication Communication Protocol RS485 conformance Communication System Start Stop Synchronization System Half Duplex Communication Baud Rate 230 4kbps Error Control System Non parity bit CRC 1 Communication Cable Length Total Cable Length 100m or less Communications Cable Twisted pair shielded cable Recommended Taiyo Cabletec Corporation K SB 20276 Length m 2P AWG22 Environment Surrounding air temp...

Page 2: ...Enable Always ON b contact Enable SIO Communication Line Wiring Layout There should be no problem to have a terminal block connection instead of a 4 way junction Use a terminal block connection or direct joint connection if there is a concern that a faulty connection may occur as a result of using the E Con connector 17 5 17 5 φ5 Hole 178 5 170 5 161 68 1 RCM GW DV RCM GW CC RCM GW PR Note Dimensi...

Page 3: ...and the extended cyclic settings cannot be used for other purposes Refer to Instruction Manual DVD for the details of the address assignment No Mode Remote I O Data Register GW PLC RX PLC RY GW GW PLC RWr PLC RWw GW 1 Position number specification mode 7 words 7 words 9 words 9 words 2 Direct numeric specification mode Position Data Limit Mode 7 words 7 words 16 words 16 words 3 Normal Positioning...

Page 4: ...d ON Illuminating CPU error Please contact us G ER RD OFF CPU is operating in normal condition Illuminating Either an error is occurred on CC Link module or the connection with CC Link is not established Check the communication status LEDs for the connection to CC Link and check the settings and wirings Even if this LED is ON the connection to the teaching tool is available as long as RUN is turne...

Page 5: ...ating Status is off line OFF The machine is not off line ERR RD 1Hz Flashing There is a configuration error Exnample The number of input and output set with the mode setting switch does not match with the number of input and output set with the configuration tool 4Hz Flashing It is a communication board ASIC initializing error Please contact us if the condition does not recover even with a reboot ...

Reviews: