Connection Diagram 

 

 

 
 

  NOTE: 

  A 24V DC power supply is required as the source for the controller and PIO. 

  Turn off the power to the controller before inserting or removing the connector for connection 

between the teaching pendant and controller. 
Inserting or removing the connector while the power is turned ON causes a controller failure.

 

 

Power Supply and Emergency Stop Circuit 

 

The following is a circuit example where the emergency stop switch on the teaching pendant is 
incorporated into the emergency stop circuit constructed by the customer: 

 
● Internal drive-power cutoff relay type : ACON-C, PCON-C/CF 

• In the case of the use of a single controller: 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

• In the case of the use of two or more controllers:

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

*1  To cut off the motor drive power supply in conformance with safety category 2, connect 24V to the 

EMG terminal and a contactor or other contact device to the MPI/MPO terminals. 

*2  When the teaching pendant is connected to the controller, the controller automatically recognizes it. 
*3  For the CR contact, the rated voltage and rated current are “24VDC” and “0.1A”. 

● Driving Source Interruption Relay: External Type

 

• In the case of the use of a single controller: 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

• In the case of the use of two or more controllers:

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

*1  To cut off the motor drive power supply in conformance with safety category 2, connect 24V to the 

EMG terminal and a contactor or other contact device to the MPI/MPO terminals. 

*2  When the teaching pendant is connected to the controller, the controller automatically recognizes it. 
*3  For the CR contact, the rated voltage and rated current are “24VDC” and “0.1A”. 

Teaching pendant 

<CON-T> 

PIO connector 

Status indicator LEDs 

Host system <PLC> 

Supplied flat cable 

Axis number setting switch 

Mode selector switch 

Brake release switch 

Actuator 

PC Software <Optional> 

RS232C type <RCM-101-MW> 

USB type <RCM-101-USB> 

PC 

+24V 

0V 

ACON-C, PCON-C/CF 

EMG Switch for the  
Teaching Pendant 

MAX 0.1A

(30VDC)

Motor Power Breaker Relay 

(Coil current 10mA or less) 

S1 

S2 

EMG- 

MPI 

MPO 

24V 

0V 

GND 

CR 

CR

*3 

CR 

Coil current 0.1A or less

(30VDC)

External EMG  
reset switch 

External EMG  
switch 

Motor power supply 

Control power supply

+24V 

0V 

ACON-C, PCON-C/CF 

EMG Switch for the  
Teaching Pendant 

MAX 0.1A

(30VDC)

Motor Power Breaker Relay 

(Coil current 10mA or less) 

S1 

S2 

EMG- 

MPI 

MPO 

24V 

0V 

S1 
S2 

EMG- 

MPI 

MPO 

24V 

0V 

S1 
S2 

EMG- 

MPI 

MPO 

24V 

0V 

GND 

CR

*3 

CR

*3 

CR

*3 

CR 

External EMG  
reset switch 

External EMG  
switch 

Motor power supply 

Control power supply 

 

 
 

 

 

CR 

Second Unit 

nth Unit

+24V 

0V 

ACON-CG,  
PCON-CG 

EMG Switch 

S1 

S2 

EMG- 

MPI 

MPO 

24V 

0V 

CR

*3 

CR 

External EMG  
reset switch 

External EMG  
switch 

Motor power supply 

Control power supply 

 
 

 

 

Teaching Pendant 

CR 

Coil current 0.1A or less

(30VDC)

MAX 0.1A

(30VDC)

+24V

0V

ACON-CG, 
PCON-CG

EMG Switch

S1

S2

EMG-

MPI

MPO

24V

0V

S1
S2

EMG-

MPI

MPO

24V

0V

S1
S2

EMG-

MPI

MPO

24V

0V

CR

*3

CR

*3

CR

*3

CR

External EMG 
reset switch

External EMG 
switch

Motor power supply

Control power supply

Second Unit

nth Unit

 

 
 

 

 

CR

Teaching Pendant

MAX 0.1A

(30VDC)

Summary of Contents for ACON-C Series

Page 1: ...A 2 10W 1 3 4 4 1 3 2 5 20W Model No 20 1 3 4 4 1 3 2 5 30W 1 3 4 0 1 3 2 2 RCA RCA2 20W Model No 20S Dedicated to HA3 HA4 and TA5 Types 1 7 5 1 1 7 3 4 2W 0 8 4 6 5W 1 0 6 4 Motor Power Capacity 1 RCL 10W 1 3 6 4 Heating value 8 4W RCA All types 800 Pulse rev RCA2 N 1048 Pulse rev RCA2 Excluding RCA2 N 800 Pulse rev RA1L ꞏ SA1L ꞏ SA4L ꞏ SM4L 715 Pulse rev RA2L ꞏ SA2L ꞏ SA5L ꞏ SM5L 855 Pulse rev E...

Page 2: ...2 Environment that may cause non conductive pollution or transient conductive pollution by frost IEC60664 1 1 Installation Environment Do not use this product in the following environment Location where the surrounding air temperature exceeds the range of 0 to 40 C Location where condensation occurs due to abrupt temperature changes Location where relative humidity exceeds 85 RH Location exposed t...

Page 3: ...he MPI MPO terminals 2 When the teaching pendant is connected to the controller the controller automatically recognizes it 3 For the CR contact the rated voltage and rated current are 24VDC and 0 1A Teaching pendant CON T PIO connector Status indicator LEDs Host system PLC Supplied flat cable Axis number setting switch Mode selector switch Brake release switch Actuator PC Software Optional RS232C ...

Page 4: ... OFF PE0 to PE6 Current position number signal In the electromagnetic valve mode this signal will turn ON when the actuator completes moving to the target position LS0 to LS2 Limit switch output signal This signal will turn ON when the current actuator position enters the positioning band of the target position It will be output even before the movement command if home return has been completed LO...

Page 5: ...turn operation first Determine the target positions while fine adjusting the transferred work and robot hand NOTE To ensure safety it is recommended that safety speed be enabled during initial movements 9 Trial Run Adjustment 1 Disable the safety speed with the PC software or teaching pendant and perform operation check for each position 2 Set the mode selector switch to the AUTO side 3 Output a m...

Reviews: