IPM3400 Compact Power Meter 

 

 

 

User guide 

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

IA Networks Technology Co., Ltd. 
5F-1, No.44, Sec. 2, Roosevelt Rd., Taipei, Taiwan

 

TEL

886-2-2395-3153 FAX

886-2-2395-3152 

http://

 

www.iantech.com.tw

    E-mail

[email protected]

 

 

Summary of Contents for IPM3400

Page 1: ...0 Compact Power Meter User guide IA Networks Technology Co Ltd 5F 1 No 44 Sec 2 Roosevelt Rd Taipei Taiwan TEL 886 2 2395 3153 FAX 886 2 2395 3152 http www iantech com tw E mail market_infor iantech c...

Page 2: ...1 2 3 Limitation of Warranty Chapter 2 Specification Chapter 3 Installation 3 1 Inspection 3 2 safety 3 3 Size and Latch 3 4 Mounting and Dismounting 3 4 1 Mounting 3 4 2 Dismounting Chapter 4 Wiring...

Page 3: ...other metering equipment can present a danger of electrical shock It is strongly recommended that all work should be performed only by qualified industrial electricians and metering specialist IA Net...

Page 4: ...rameters Measures V1 V1 V2 V2 I 1 I 2 I 3 I 4 kW1 kW2 kW3 kW4 kVA1 kVA2 kVA3 kVA4 kvar1 kvar2 kvar3 kvar4 PF1 PF2 PF3 PF4 kWh1 kWh2 kWh3 kWh4 kVAh1 kVAh2 kVAh3 kVAh4 kvarh1 kvarh2 kvarh3 kvarh4 Freque...

Page 5: ...no longer safe when a shows clear signs of damage b does not work c long storage under extreme conditions d damage during shipment 3 2 Safety Please use the soft dry clothes to clean the instrument P...

Page 6: ...it rail mounting width can up to the length of 35 mm Meter auxiliary power for IPM3400 is DC 10V 30V 3 4 Mounting and Dismounting 3 4 1 Mounting Pull down the latch of meter and mount the meter on to...

Page 7: ...damage the instrument due to its large current around 5A When more than one instrument will be installed please do not disconnect the CT with its instrument Each instrument is calibrated with matching...

Page 8: ...wired order 1S 1L 2S 2L 3S 3L 4S 4L After connection the CT s clip on CT s Make sure the arrow sign on CT s follow current flow direction K L Note it must in same direction Connect the voltage input t...

Page 9: ...FF 2 ON OFF OFF OFF OFF OFF 3 OFF ON OFF OFF OFF OFF 4 ON ON OFF OFF OFF OFF 5 OFF OFF ON OFF OFF OFF 6 ON OFF ON OFF OFF OFF 7 OFF ON ON OFF OFF OFF 8 ON ON ON OFF OFF OFF 9 OFF OFF OFF ON OFF OFF 10...

Page 10: ...38 ON OFF ON OFF OFF ON 39 OFF ON ON OFF OFF ON 40 ON ON ON OFF OFF ON 41 OFF OFF OFF ON OFF ON 42 ON OFF OFF ON OFF ON 43 OFF ON OFF ON OFF ON 44 ON ON OFF ON OFF ON 45 OFF OFF ON ON OFF ON 46 ON OF...

Page 11: ...PM3400 User Guide 12 SW7 8 are used to select Wh pulse output IPM3400 to the LED for each of four channels IPM3400 Select Wh pulse output to LED Wh pulse output 7 8 Wh1 ch1 OFF OFF Wh2 ch2 ON OFF Wh3...

Page 12: ...ax data reading of Function 03 and Function04 is 125 registers Format of data Integer 16 bits with sign Unsigned Integer 16 bits without sign Float IEEE 754 Format each with 2 registers Low Word is fi...

Page 13: ...5 DWord Float kW Primary kvar_a 34359 34360 0x1106 0x1107 DWord Float kvar Primary kVA_a 34361 34362 0x1108 0x1109 DWord Float kVA Primary PF_a 34363 34364 0x110A 0x110B DWord Float Primary kWh_a 3436...

Page 14: ...t for IPM3400 Parameter name Modbus Register Len Data Type Range Units Comment Modicom Format Hex V_a 34609 34610 0x1200 0x1201 DWord UInt32 0 1 Volt Primary I_a 34611 34612 0x1202 0x1203 DWord UInt32...

Page 15: ...38 DWord Int32 0 1kW Primary kvar_tot kvar_d 34666 34667 0x1239 0x123A DWord Int32 0 1kvar Primary kVA_tot kVA_d 34668 34669 0x123B 0x123C DWord Int32 0 1kVA Primary PF_tot PF_d 34670 0x123D Word Int...

Page 16: ...t is 1 2 confirm the Band Rate default is 9600 3 confirm the stop bit default is 2 4 confirm the RS485 connect line terminal is it connect correct Q5 Regarding to the combine shipment of the meter wit...