OIM AI-7X82D V2.0 Page 3 of 10

POWER UP:   

At power on, following sequence will be prompted on the display till it reaches to Home display mode.

In home display mode, by pressing DOWN key, User can 
view the set value of SP1 & SP2 (if OP2 = AUXILIARY or 
ALARM mode) or timer value(if OP2 = soak mode) 
sequentially. 
Here, Lower display will show SP1-value, SP2-value, 
Alarm SP-Value & Timer-value by pressing DOWN key and 
it’s respective parameter code (SP1/SP2/AL.SP/SOAK 
TIME) by pressing UP key.

UPPER

DISPLAY

LOWER

DISPLAY

MODEL

VERSION

HOME

PV

SV

PROGRAMMING

USER LIST : To access the user list press SET key once.

This parameter is prompted only if output 2 is configured as soak timer. 
Controller  starts  the  execution  of  soak  time  as  per  the  mode  selected. 
Soak timer can be programmed using four different time base in Config. 
List.

This parameter is prompted if SP2 is Enable & output 2 is configured as

(1)

 

Either absolute auxiliary control or as an alarm (High/Low) mode.

(2)

 

Either deviation auxiliary control or as a deviation alarm  mode.

(3)

  As a band alarm(For all above SP2 has to be enable).

SOAK

TIME

SET

POINT 2

CONTROL

SET POINT

---------- 

User  can  change  SP1  value  using  UP/  DOWN  keys.  Holding  the  key,   
will  change  the  value  at  a  faster  rate.  Press  SET  key  to  store  the 
desired value & move on to the next parameter.

This parameter will be available only if Enabled in Configuration List. 
User can set ramp rate/min for SP1 (Set Point) to minimize overshoot. 

RAMP

RATE

This parameter is prompted only if Control Logic for Output1 is 
configured for Heat-Cool.
Output 2 will be automatically activated /de-activated w.r.t SP1 & HYS.

Output 2 will be permanently Activated (ON).

Output 2 will be permanently De-Activated (OFF). 

0°C

0°C

Disable

Auto

1 min.

LSPL ~ HSPL

 0.0 °C
     to
25.0 °C

LSPL ~ HSPL
 -99 to +99°C
    2 to 99°C

 1 Sec to
9999 Hrs.

OP2

MODE

  PARA
METER

 LOWER
DISPLAY

 UPPER
DISPLAY

RANGE

DESCRIPTION

DEFAULT

CONTROL LIST : 

SET & DOWN key simultaneously 

To enter in this mode, press 

for 3 sec. User can then set the 

following control parameters.

0.0 %

to

100.0 %

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID. 
This  parameter  will  decide  the  maximum  output  power  in  %  applied  to 
the load.

0.5

 to 

100.0 Sec.

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID. 
User  can  set  this  value  based  on  process  being  controlled  &  type  of 
output  being  selected.  For  Relay  O/P,  cycle  time  should  be  more  than 
12sec & for SSR O/P, cycle time should  be less than 10sec.

to 

300 Sec.

This parameter will be prompted only if selected control action is PID. It 
defines  how  strongly  the  controller  will  react  to  rate  of  change  of  PV. 
Value of this parameter is automatically set by auto tune function. If set 
to ‘0’, this function will be disabled.

to 

9999 Sec.

This parameter will be prompted only if selected control action is PID. It 
sets the time taken by PID algorithm to remove steady state error. Value 
of this parameter is automatically set by auto tune function. If set to ‘0’, 
this function will be disabled.

0.5 

to 

99.9°C

This parameter will be prompted only if selected control action is PID. It 
sets  proportional  band  over  which  the  output  power  is  adjusted 
depending  upon  the  error  (SV-PV).  Value  of  this  parameter  is 
automatically set by Auto tune function.

1 to10 

This parameter will be prompted only if selected control action is PID. 
With this parameter  O/P will be Completely OFF after the Set Point + 
Offset Value. If Disable, O/P will act Depending upon the PID Value 
after Set Point achieved.

Set this parameter to 15 (Default LOCK CODE) to access Control List.
User has a choice to set different Lock Code via USER LOCK CODE in 
Config. List.

1 ~ 9999

LOCK
CODE

PROPOR
 TIONAL
  BAND

INTEGRAL
    TIME

DERIV
ATIVE
 TIME

CYCLE
  TIME

OUTPUT
 POWER
   LIMIT

OUTPUT
    OFF

Disable

0

5.0°C

240

60

16.0 sec.

100 %

  PARA
METER

 LOWER
DISPLAY

 UPPER
DISPLAY

RANGE

DESCRIPTION

DEFAULT

AI-7682D

Summary of Contents for AI-7482D

Page 1: ...rent power cables Where it is impractical to do this use shielded ground at both ends v The controller should not be wired to a 3 Phase supply with unearthed star connection Under fault condition such...

Page 2: ...NC OUT2 RLY 90 270VAC SSR BZR OP1 OP2 Digital Input AI 7782D OUT 1 RLY NO CM NC OUT 2 RLY NO CM NC SSR BZR OP1 OP2 90 270VAC Digital Input AI 7982D AI 7682D 7882D OUT 1 RLY SSR BZR OP1 OP2 1 2 3 4 5...

Page 3: ...LOWER DISPLAY UPPER DISPLAY RANGE DESCRIPTION DEFAULT CONTROL LIST SET DOWN key simultaneously To enter in this mode press for 3 sec User can then set the following control parameters 0 0 to 100 0 Th...

Page 4: ...for Output2 is Soak timer Depending on end of soak strategy the value of this parameter sets the activation time for OP2 when Soak timer is over Setting this parameter to 0 will make OP2 continuously...

Page 5: ...PV SP PV increases when output is ON User can select cooling logic in which OP1 will remain ON till PV SP PV decreases when output is ON This parameter will be prompted only if selected input is RTD...

Page 6: ...ated By selecting this parameter Digital Input can be used as Water Level Indicator input By selecting this parameter Digital Input can be used to detect whether the door is open or closed By selectin...

Page 7: ...logic for control Output 2 in which OP2 will remain ON till PV SP2 PV increases when output is ON User can select Cool logic for control Output 2 in which OP2 will remain ON till PV SP2 PV decreases...

Page 8: ...S Alarm condition persists it will Disable Alarm O P at power ON If this parameter is set as NO Alarm condition persists it will Enable Alarm O P at power up Once the Alarm is activated User has follo...

Page 9: ...the following conditions 1 At every Power ON 2 Completion of current soak time cycle 3 Power failure during soak time is in progress In this Mode Timer will start only after pressing START key for 3...

Page 10: ...ired P I D values It can be performed at any time after power ON but it is best to start it when the process is at Ambient temperature in order to minimize overshoot undershoot Auto tuning is applied...