3
OIM AI-7X82D V2.0 Page 3 of 10
POWER UP:
At power on, following sequence will be prompted on the display till it reaches to Home display mode.
In home display mode, by pressing DOWN key, User can
view the set value of SP1 & SP2 (if OP2 = AUXILIARY or
ALARM mode) or timer value(if OP2 = soak mode)
sequentially.
Here, Lower display will show SP1-value, SP2-value,
Alarm SP-Value & Timer-value by pressing DOWN key and
it’s respective parameter code (SP1/SP2/AL.SP/SOAK
TIME) by pressing UP key.
UPPER
DISPLAY
LOWER
DISPLAY
MODEL
VERSION
HOME
PV
SV
PROGRAMMING
USER LIST : To access the user list press SET key once.
This parameter is prompted only if output 2 is configured as soak timer.
Controller starts the execution of soak time as per the mode selected.
Soak timer can be programmed using four different time base in Config.
List.
This parameter is prompted if SP2 is Enable & output 2 is configured as
(1)
Either absolute auxiliary control or as an alarm (High/Low) mode.
(2)
Either deviation auxiliary control or as a deviation alarm mode.
(3)
As a band alarm(For all above SP2 has to be enable).
SOAK
TIME
SET
POINT 2
CONTROL
SET POINT
----------
User can change SP1 value using UP/ DOWN keys. Holding the key,
will change the value at a faster rate. Press SET key to store the
desired value & move on to the next parameter.
This parameter will be available only if Enabled in Configuration List.
User can set ramp rate/min for SP1 (Set Point) to minimize overshoot.
RAMP
RATE
This parameter is prompted only if Control Logic for Output1 is
configured for Heat-Cool.
Output 2 will be automatically activated /de-activated w.r.t SP1 & HYS.
Output 2 will be permanently Activated (ON).
Output 2 will be permanently De-Activated (OFF).
0°C
0°C
Disable
Auto
1 min.
LSPL ~ HSPL
0.0 °C
to
25.0 °C
LSPL ~ HSPL
-99 to +99°C
2 to 99°C
1 Sec to
9999 Hrs.
OP2
MODE
PARA
METER
LOWER
DISPLAY
UPPER
DISPLAY
RANGE
DESCRIPTION
DEFAULT
CONTROL LIST :
SET & DOWN key simultaneously
To enter in this mode, press
for 3 sec. User can then set the
following control parameters.
0.0 %
to
100.0 %
This parameter will be prompted only if selected control action is PID.
This parameter will decide the maximum output power in % applied to
the load.
0.5
to
100.0 Sec.
This parameter will be prompted only if selected control action is PID.
User can set this value based on process being controlled & type of
output being selected. For Relay O/P, cycle time should be more than
12sec & for SSR O/P, cycle time should be less than 10sec.
0
to
300 Sec.
This parameter will be prompted only if selected control action is PID. It
defines how strongly the controller will react to rate of change of PV.
Value of this parameter is automatically set by auto tune function. If set
to ‘0’, this function will be disabled.
0
to
9999 Sec.
This parameter will be prompted only if selected control action is PID. It
sets the time taken by PID algorithm to remove steady state error. Value
of this parameter is automatically set by auto tune function. If set to ‘0’,
this function will be disabled.
0.5
to
99.9°C
This parameter will be prompted only if selected control action is PID. It
sets proportional band over which the output power is adjusted
depending upon the error (SV-PV). Value of this parameter is
automatically set by Auto tune function.
1 to10
This parameter will be prompted only if selected control action is PID.
With this parameter O/P will be Completely OFF after the Set Point +
Offset Value. If Disable, O/P will act Depending upon the PID Value
after Set Point achieved.
Set this parameter to 15 (Default LOCK CODE) to access Control List.
User has a choice to set different Lock Code via USER LOCK CODE in
Config. List.
1 ~ 9999
LOCK
CODE
PROPOR
TIONAL
BAND
INTEGRAL
TIME
DERIV
ATIVE
TIME
CYCLE
TIME
OUTPUT
POWER
LIMIT
OUTPUT
OFF
Disable
0
5.0°C
240
60
16.0 sec.
100 %
PARA
METER
LOWER
DISPLAY
UPPER
DISPLAY
RANGE
DESCRIPTION
DEFAULT
AI-7682D