Activate 

The activate button in the interface box performs a standard flush indicated with a blue LED blink. 

Activation Count Reset 

The activation count is reset by holding the Activation Count Reset button for 5 seconds. The red LEDs on the device will 

 

rapidly blink when the reset has occurred.

DIGITAL DISPLAY

An IR Plate is equipped with a digital display to read the current activation count, alerts, and make changes to parameters. 

When the valve enters maintenance mode a round-robin display will begin. If an adjustment is made, the displayed setting 

 

and respective LED will blink, and the round-robin will restart.

ROUND-ROBIN DISPLAY

An IR Plate continuously runs the Round-Robin Display when in Maintenance Mode. 

When the Round-Robin Display begins, it will cycle through the Alert Codes, Activation Count, and current values of adjustable 

parameters.

ALERT CODES DISPLAY

Alert codes can be seen on the digital display. Additionally, the plate will flash a red LED every 10 seconds when an alert is present. 

Indicated by AL and then the code number on the COBALT Round-Robin Display. 

Code 2 Activation Count Threshold Reached 

250,000 activations have been reached since the last reset, indicating that the valve should be rebuilt. 

Code 4 Obstruction 

An object has remained locked on for 30 minutes. Auto Activation is disabled. To exit obstruction nothing must be detected 

 

for 5 seconds. 

Code 6 Disconnected or faulty Pressure/Temperature Sensor 

The Pressure/Temperature sensor must be plugged in or replaced.

ACTIVATION COUNT

The current number of activations since the last activation count reset. 

Indicated by AC and then the number of activations scrolling from right to left on the digital display. 

The activation count is saved to memory on certain intervals depending on the total number of activations. For the first 100 

activations it saves every activation. From 100 to 1000 activations, it saves every 10 activations. For 1000+ activations it saves every 

100 activations. For example, if the device is powered off at 215 activations, when powered back on it will report 210 activations.

ADJUSTABLE PARAMETERS

Range 

Adjusts the maximum range used to detect a user. The range can be adjusted from 6-54 inches. 