COBALT Pro
™
Wall Sensor
Standard Operations
101822 / 101675 / 101929 / 101674
I-CON Systems, Inc., for product support call 1-866-730-7192 or visit us online at support.i-con.com
One or more products contained herein are protected by U.S. Patent with other undergoing the patent process www.i-con.com/patents
page 3
Activate
The activate button in the interface box performs a standard flush indicated with a blue LED blink.
Activation Count Reset
The activation count is reset by holding the Activation Count Reset button for 5 seconds. The red LEDs on the device will
rapidly blink when the reset has occurred.
DIGITAL DISPLAY
An IR Plate is equipped with a digital display to read the current activation count, alerts, and make changes to parameters.
When the valve enters maintenance mode a round-robin display will begin. If an adjustment is made, the displayed setting
and respective LED will blink, and the round-robin will restart.
ROUND-ROBIN DISPLAY
An IR Plate continuously runs the Round-Robin Display when in Maintenance Mode.
When the Round-Robin Display begins, it will cycle through the Alert Codes, Activation Count, and current values of adjustable
parameters.
ALERT CODES DISPLAY
Alert codes can be seen on the digital display. Additionally, the plate will flash a red LED every 10 seconds when an alert is present.
Indicated by AL and then the code number on the COBALT Round-Robin Display.
Code 2 Activation Count Threshold Reached
250,000 activations have been reached since the last reset, indicating that the valve should be rebuilt.
Code 4 Obstruction
An object has remained locked on for 30 minutes. Auto Activation is disabled. To exit obstruction nothing must be detected
for 5 seconds.
Code 6 Disconnected or faulty Pressure/Temperature Sensor
The Pressure/Temperature sensor must be plugged in or replaced.
ACTIVATION COUNT
The current number of activations since the last activation count reset.
Indicated by AC and then the number of activations scrolling from right to left on the digital display.
The activation count is saved to memory on certain intervals depending on the total number of activations. For the first 100
activations it saves every activation. From 100 to 1000 activations, it saves every 10 activations. For 1000+ activations it saves every
100 activations. For example, if the device is powered off at 215 activations, when powered back on it will report 210 activations.
ADJUSTABLE PARAMETERS
Range
Adjusts the maximum range used to detect a user. The range can be adjusted from 6-54 inches.
Rev 081123