Contact Characteristics
The operational characteristics for the relay’s main contacts (95-96, 97-98) and auxiliary contact (07-08) can be various based on the
Cont settings and the Au-c settings. The inverse of normal mode is applied during test mode
Technical Data
Operational Characteristics
Model
Status
Menu Setting
Trip Cause
Contact Output
Notes
Cont
Au-c
95-96
97-98
07-08
HGMP A60
Advanced Type/
HGMP N60 I
Instantaneous
Type
Normal
1a1b
Sc-c, gF-c, AL-c
-
●
-
-
2a
-
-
-
2b
●
●
-
Test
1a1b
Sc-c, gF-c, AL-c
-
-
●
●
2a
●
●
●
2b
-
-
●
Trip
1a1b
Sc-c
Instantaneous
●
-
●
gF-c
Ground fault
●
-
●
AL-c
Overcurrent
-
●
●
Sc-c, gF-c, AL-c
Others
1)
-
●
-
2a
Sc-c
Instantaneous
-
-
●
gF-c
Ground fault
-
-
●
AL-c
Overcurrent
●
●
●
Sc-c, gF-c, AL-c
Others
1)
●
●
-
2b
Sc-c
Instantaneous
●
●
●
gF-c
Ground fault
●
●
●
AL-c
Overcurrent
-
-
●
Sc-c, gF-c, AL-c
Others
1)
-
-
-
HGMP N60 Z
Leakage Type
Normal
1a1b
-
-
●
-
-
2a
-
-
-
2b
●
●
-
Test
1a1b
-
-
-
●
-
2a
●
●
-
2b
-
-
-
Trip
1a1b
-
All
-
●
-
2a
●
●
-
2b
-
-
-
※
1)
Indicates trip causes except earth leakage and ground fault.
14
Electronic Motor Protection Relays