Chemical dosing

System Filter– 6 720 803 839 (2014/03)

▶ Using a suitable spanner open the isolation valves (If the 

filter is used on a sealed system, recharge the system to 
correct working pressure).

Fig. 15

5

Chemical dosing

▶ Remove the "quick dose" air vent with a standard radiator 

key.
The built-in, one-way valve will prevent water from 
escaping.

Fig. 16

▶ Attach the chemical adaptor and feed in the chemical.
▶ Wait five seconds before removing the adaptor.

Fig. 17

▶ Replace the quick dose air vent [1].
▶ Allow the system to circulate for 30 seconds.

Fig. 18

The adaptor on market leading chemical 
additives, either liquid or concentrate form, 
will fit onto the "quick dose" air vent.

6720803839

-14.2W

o

6720803839

-15.2W

o

1

6720803839

-16.2W

o

6720803839

-17.2W

o

1

Summary of Contents for CB-L1936LCD/DVD

Page 1: ...UK IE Installation Servicing Instructions Greenstar System Filter 6720803839 00 1Wo For sealed open vent central heating systems with 22mm central heating pipes 6 720 803 839 2014 03...

Page 2: ...s possible personal injury WARNING indicates possible severe personal injury DANGER indicates possible risk to life Important information Additional symbols Safety instructions in this document are fr...

Page 3: ...ealth and safety The appliance contains no substances that contravene the COSHH Regulations Control of Substances Hazardous to Health regulations 1988 Spare Parts CAUTION The system filter contains a...

Page 4: ...boiler Worcester Bosch recommend that the filter is fitted between the last radiator and the boiler on a vertical run of pipework In determining a suitable location for installation itisimportanttoen...

Page 5: ...s for the pipework to allow for multiple installation situations See figure 4 for our advised installation position when installing under a boiler Fig 4 Pipework orientation 2 1 2 Dimensions Fig 5 Dim...

Page 6: ...filter onto the pipework and hand tighten following the flow direction indicated on the isolation valves Fig 8 System filter installation Tighten the compression fittings firmly but do not over tight...

Page 7: ...ter ensuring that any water or debris is caught within the container Slide the magnetic cap sheath off the base 2 Wipe clean the magnetic cap sheath 2 and base 1 Reassemblethemagneticcapsheathontotheb...

Page 8: ...adiator key The built in one way valve will prevent water from escaping Fig 16 Attach the chemical adaptor and feed in the chemical Wait five seconds before removing the adaptor Fig 17 Replace the qui...

Page 9: ...gnature Service 2 Date Engineer Name Company Name Telephone No Comments Signature Service 3 Date Engineer Name Company Name Telephone No Comments Signature Service 4 Date Engineer Name Company Name Te...

Page 10: ...10 System Filter 6 720 803 839 2014 03 Notes...

Page 11: ...11 System Filter 6 720 803 839 2014 03 Notes...

Page 12: ...SPARES 0330 123 9779 LITERATURE 0330 123 9119 TRAINING 0330 123 0166 SALES 0330 123 9669 Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Tel 0330 123 9559 Worcester Bosch Group is a bran...

Reviews: