1. Technical Specifications
Product type High bay microwave DALI sensor (Tri-level control)
Operating voltage 120~277VAC 50/60Hz
Rated load Maximum 20pcs devices, maximum 40mA
Power consumption < 1W
Detection angle 360
o
Detection area (DxH) 12 x 12m (Maximum)
Mounting height 15M(Maximum)
Detection range 10% / 50% / 75% / 100%
Hold time 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +
Stand-by dimming level 10% / 20% / 30% / 50%
Daylight threshold 2~ 500Lux, Disable
Warmming up time 20s
Operating temperature -20
o
C ~ +50
o
C
IP rating IP42
3. Rotary Switch Settings
A rotary switch is built inside the sensor for
scene selection / fast programming. Total
16 channels available:
Note: settings can also be changed by remote control HRC-11. The last action controls.
8
SURFACE MOUNT HIGH BAY DALI SENSOR HMW15
Installation and Instruction Manual
Rotary switch preset (Please
see the location in 2. Installation)
Detection
range
Channel
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
75%
50%
100%
100%
100%
5s
1min
5min
5min
5min
5min
5min
10min
10min
10min
10min
10min
10min
30min
30min
5s
10s
5min
10min
30min
0s
+∞
+∞
10min
30min
+∞
+∞
+∞
+∞
+∞
+∞
10s
10%
10%
10%
10%
Disable
10%
30%
10%
10%
10%
30%
10%
10%
10%
30%
10%
Disable
2Lux
10Lux
30Lux
10Lux
30Lux
Disable
2Lux
10Lux
30Lux
Disable
30Lux
10Lux
50Lux
Disable
2Lux
Hold
time
Stand-by
time
Stand-by
dimming level
Daylight
threshold
4. Functions
The built-in daylight sensor can read ambient natural light and switch off the fixture automatically
whenever artificial light is not required (natural light lux level exceeds daylight threshold).
Note: if the stand-by time is preset at "+∞", the fixture never switches off even when natural
light is sufficient.
The motion sensor is employed, but only activated on the manual press of the push switch,
The light remains on during presence and dims down in absence, eventually switching off
automatically after the stand-by time has expired.
Note: in this mode, the push terminal used for the ‘manual on’ switch input.
End-user can choose either function 4.4 or 4.5 for application. Default function is 4.4.
4.2 Lux Off Function
4.5 Semi-auto Function (Absence Detection)
4.4 Manual Override
With the help of push-switch, this sensor maybe over-ridden by the end-users to switch on/off
the lights manually, or adjust the light brightness during motion hold-time. This makes the
product more user-friendly and offers more options to fit for extra-ordinary demands.
* Short push (<1s): on/off function;
ON
→
OFF: the light turns off immediately and cannot be lighten for a certain time (equals to
hold time preset) even there is movement is detected. After this period, the sensor goes back
to auto sensor mode.
OFF
→
ON: the light turns on 100% and goes to auto sensor mode, even when ambient
Lux level exceeds the daylight threshold.
* Long push (>1s): adjust the maximum brightness (between 10% and 100%) during
hold-time. Both the settings on remote control and push switch can
overwrite each other, the last adjustment remains in memory.
HMW15-20170308-A1
2. Installation
Warnings:
1. Installation must be carried out by a
qualified engineer in accordance with
local regulations.
2. Disconnect supply before installing.
3. Install to a solid surface - vibrations may
cause mis-triggering.
4. Ensure environmental conditions are
suitable for electronic equipment
29
50.2
Direct junction “J” box mounting
a. Separate control board (A) from facia (B)
& Surface box (C). C is not required.
b. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
c. Secure control board (A) to junction box.
d. Set-up sensor modes as per sections 3 & 4
of this manual.
e. Clip facial plate (B) to control board (A).
Surface mount assembly
a. Separate control board (A) from facia (B) &
Surface box (C).
b. Securely mount surface box (C) to a flat and
solid surface.
c. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
d. Set-up sensor modes as per sections 3 & 4 of
this manual.
e. Secure control board (A) to surface box (C).
f. Clip facial plate (B) to control board (A).
32.5
53.7
C - Surface box
B - Facia Cover
A - Control Board
Rotary switch preset
Photocell
Infrared receiver
HF Sensor module
LED indicator
By connecting the “SYNC” terminals in parallel (see wiring diagram), no matter which sensor detects
motion, all HMW15 in the group will turn on the lights when surrounding natural light is below the daylight
threshold. The sensor module is shared and the detection area could be widely enlarged in this way.
4.3 Synchronization Function
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas require
a light change notice before switch-off.
It offers 3 levels of light: 100%-->dimmed light-->off; and 2 periods of selectable waiting time: motion
hold-time and stand-by time; Selectable daylight threshold and detection area.
4.1 Tri-level Control (Corridor Function)
All manuals and user guides at all-guides.com
all-guides.com