Description of the Button Functions (remote control HRC-11)
5.
Ambient daylight threshold [ button
]
1. Press button Shift, the red LED starts to flash.
2. Press button
, the ambient lux level is sampled and set as
the new daylight threshold / target Lux level.
3
10
10
Detection range [ zone ]
8
RESET[ button ]
Press button , all settings go back to default values as below:
2
2
Shift [ button
]
Press button , the LED on the top left corner is on
selection.
All values / settings in RED are in valid for 20 seconds.
3
3
Auto Mode [ button ]
Press button to initiate automatic mode. The sensor starts working
and all settings remain as before the light is switched ON/OFF.
4
4
Scene prog. [ zone ] (One-key-commissioning)
1. Press button “Start” to program.
2. Select the buttons in “Detection range”, / “Daylight threshold”,
“Hold time” to set all parameters.
3. Press button “Memory” to save all the settings programmed in the
remote control.
7
7
7
7
3
8
10
11
7
8
9
10
7
11
Brig/- [ button ]
6
Power output [ button
]
5
Semi-auto Mode [ button & ]
1. Press button Shift (the red LED is on for indication).
2. Press button to initiate semi-auto mode. The fixture is manually
on by push-switch and automatically off in semi-auto mode.
3
3
4
4
Permanent ON/OFF [ ]
Press button , to select permanent ON or permanent OFF mode.
* Press button / to to quit this mode.
The mode will change to AUTO Mode after power failure.
button
1
1
2
4
Daylight threshold [ zone
]
Press buttons in zone to set daylight sensor at 2Lux/ 10Lux /
50Lux / 100Lux / 300Lux / 500Lux / Disable.
Note: To set daylight sensor at 100Lux / 300Lux / 500Lux, press
Shift button first.
9
9
3
Hold time [ zone ]
Press buttons in zone to set the hold time at 2s / 30s / 1min /
5min / 10min / 15min / 20min / 30min.
Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button
Shift at first.
2. 2s is for test purpose only, stand-by period and daylight
sensor settings are disabled in this mode.
*To exit from Test mode, press button or any button in zone .
3
11
11
11
2
HRC-11
6
8
10
11
12
13
14
2
4
1
3
7
9
5
Hold-time 5min, daylight threshold Disabled
to indicate mode
These two buttons are disabled.
These two buttons are disabled.
These two buttons are disabled.
All buttons in zone “Stand-by time ”, “Stand-by dimming
level & Auto-config“, “Dual-tech & RF mode” are disabled.
4. Press button “Apply” to set the settings to each sensor unit(s).
For example, to set detection range 100%, daylight threshold
Disable, hold time 5min, the steps should be:
Press button Start, button 100%, Disable, Shift, 5min,
Memory. By pointing to the sensor unit(s)
and pressing Apply, all settings are passed on the sensor(s).
& A
4
4 h
h
h
4. Wiring Diagram
LED Driver
Push L’
N L
Max. 400W
L
N
LED+
LED--
LED Driver
L
N
LED+
LED--
HIR28-20190326-A1