HIR28-20190326-A1

Wire Preparation

Pluggable screw terminal.  It is recommended to make
connections to the terminal before fitting to the sensor.

3. Functions

On/ off  Control

This sensor is a motion switch, which turns on the light upon detection of motion, 
and turns off after a pre-selected hold-time when there is no movement. A daylight sensor is
also built in to prevent the light from switching on when there is sufficient natural light.

Manual Override

With the help of push-switch, this sensor can be over-ridden by the end-user to manually switch 
on/off the light, which makes the product more user-friendly and offers more options to fit some 
extra-ordinary demands:

It is easy to forget to switch off the light, in office, corridor, even at home. And in many other cases, 
people do not want to have a sensor to switch on the light automatically, for example, when people 
just quickly pass-by, there is no need to have the light on. The solution is to apply this “absence 
detector”:  motion sensor is employed, but only activated on the manual press of the push-switch, the 
light keeps being ON in the presence, and switches off in the long absence.

Note: end-user can choose either function 3.3 or function 3.4 for application. 
Default function is manual override.

 

Semi-auto Mode (Absence Detection)

3.4

3.3

3.1

The built-in daylight sensor can measure ambient natural light and switch off the fixture 
automatically whenever artificial light is not required (natural light lux level exceeds daylight 
threshold).

Lux Off Function

3.2

* Short Push (<1s): on/off function;   
   On 

 Off: the light turns off immediately and cannot be triggered ON by motion until the expiration  

                    of pre-set hold-time. After this period, the sensor goes back to normal sensor mode.
   Off 

 On: the light turns on and goes to sensor mode, no matter if ambient Lux level exceeds the 

                    daylight threshold or not.

Note: if end-user do not want this manual override function, just leave the “push” terminal 
unconnected to any wire.   

zero-cross point

Alternating current

Zero-cross Relay Operation

Designed in the software, sensor 
switches on/off the load right at the 
zero-cross point, to ensure that the 
in-rush current is minimised, enabling 
the maximum lifetime of the relay.

3.5

0.75 - 2.5mm

8mm

(min 6mm, max 11mm)

2. Installation 

1. Technical Specifications

Stand-by power

Resistive

800W

220~240VAC  50/60Hz 

Mains voltage

Load ratings:

<1W

400VA

Capacitive

20s

PIR detection

Sensor principle 

Warming-up

Operation temperature

Ta: -20°C ~ +50°C

IP20  

IP rating

360°

Detection angle

EMC standard (EMC)

Safety standard (LVD)

Certification

EN55015, EN61000

Semko, CB, CE , EMC, LVD, RCM

EN60669-1, EN60669-2-1

Detection range (Max.)*

 

Detection range (Max.)*

 HIR28/H

Installation height

15m (forklift)

                               12m (person)

Detection range (Ø)

24m 

Installation Height : 6m

Detection Range (Ø) :9m

Installation height

15m (forklift)

                          12m (person)

Detection range (Ø)

40m 

Detection range (Max.)*

HIR28/R

Installation Height : 6m

Detection Range(Ø) :10m

Detection range (Max.)*

 HIR28/RH

Installation and Instruction Manual

 

 

 HIR28  HIR28/R 
HIR28/H  HIR28/RH

FLUSH MOUNT PIR MOTION SENSOR

On/off relay control

78

75.2

70.5

62

4

2

3

1

65mm

* Install lens as required

7

2

1

5

* Install blind as required

A

B

6

1.  Ceiling (drill hole 65mm)
2.  Carefully prise off the cable clamps.
3.  Make connections to the pluggable
     terminal blocks.
4.  Insert plug connectors and secure using
     the provided cable clamps, then clip
     terminal covers to the base.
5.  Fit detection blind (if required) and 
     desired lens.
6.  Clip fascia to body.
7.  Bend back springs and insert into ceiling.

3

2

1

Summary of Contents for HIR28

Page 1: ...pre set hold time After this period the sensor goes back to normal sensor mode Off On the light turns on and goes to sensor mode no matter if ambient Lux level exceeds the daylight threshold or not Note if end user do not want this manual override function just leave the push terminal unconnected to any wire zero cross point Alternating current Zero cross Relay Operation Designed in the software s...

Page 2: ...rmanent ON or permanent OFF mode Press button to to quit this mode The mode will change to AUTO Mode after power failure button 1 1 2 4 Daylight threshold zone Press buttons in zone to set daylight sensor at 2Lux 10Lux 50Lux 100Lux 300Lux 500Lux Disable Note To set daylight sensor at 100Lux 300Lux 500Lux press Shift button first 9 9 3 Hold time zone Press buttons in zone to set the hold time at 2s...

Page 3: ...etection pattern for single person Ta 20ºC Recommended ceiling mount installation height 2 5m 6m max 64m2 Ø 9m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m max 50m2 Ø 8m max 38m2 Ø 7m max 38m2 Ø 7m max 38m2 Ø 7m Optional Accessory Ceiling Surface Mount Box HA03 1 HIR28 Low bay Valid Range Blind Option 1 Aisle Detection Optional Accessory Blind Insert for Blocking Certain D...

Page 4: ...Ø 8m max 20m2 Ø 5m max 20m2 Ø 5m max 20m2 Ø 5m max 20m2 Ø 5m max 20m2 Ø 5m 2 HIR28 R Reinforced Low bay A Tangential movement Tangential max 10m h max 6m A B Radial movement Radial max 5m h max 6m B Optional Accessory Ceiling Surface Mount Box HA03 Optional Accessory Blind Insert for Blocking Certain Detection Angles 75 Ø 94 Valid Range Blind Option 1 Aisle Detection Blind Option 2 180º Detection ...

Page 5: ...ction pattern for forklift Ta 20ºC Recommended ceiling mount installation height 10m 15m Optional Accessory Ceiling Surface Mount Box HA03 Optional Accessory Blind Insert for Blocking Certain Detection Angles Valid Range Valid Range Radial B Tangential A 2 5m Mount height 11m 12m 10m 8m 6m max 104m2 Ø 11 5m max 50m2 Ø 8m max 154m2 Ø 14m max 227m2 Ø 17m max 269m2 Ø 18 5m max 314m2 Ø 20m max 7m2 Ø 3...

Page 6: ...tial max 40m h max 15m A B Radial movement HIR28 RH Reinforced high bay lens detection pattern for forklift Ta 20ºC Recommended ceiling mount installation height 10m 15m Radial max 15m h max 15m B Optional Accessory Ceiling Surface Mount Box HA03 4 HIR28 RH Reinforced High bay with 3 Pyro Tangential max 30m h max 12m A Radial max 4m h max 12m B Radial B Tangential A 2 5m Mount height 11m 12m 10m 8...

Reviews: