Warning
Avoid running the LED mains driver and Emergency pack without the load connected.
Failure to do so may result in damage to the LED array.
Do not short circuit or reverse connect the ba
eries.
ISOLATE BOTH MAINS SUPPLIES AND DISCONNECT THE BATTERY BEFORE INSTALLATION OR MAINTENANCE.
High voltage could be present at the output terminals if the battery is not isolated.
CAUTIONS IN EMERGENCY BATTERY USAGE
STORAGE CONDITIONS
1. Temperature range for storage (Humidity: Max. 85%)
0 ~ +35
℃
, one year storage
(Storage time will be shortened if out of this temp. range)
2. Storage duration before use: Less than 6 months from batteries received to start with charging.
Note 1: For Ni-Cd battery, we recommend batteries are charged and discharged at least once every 6 months.
Note 2: For Ni-MH battery, we recommend batteries are charged and discharged at least once every 3 months.
Note 3: Never over discharge the battery.
WARNING
1. Avoid direct soldering onto cells.
2. Use only within the specified working temperature range.
3. Do not subject batteries to mechanical shock.
DANGER!
1. Avoid throwing cells into a fire or attempting to disassemble them. As the electrolyte inside is strong alkaline and
can damage skin and clothes.
2. Avoid short circuiting. It may be leakage.
SPECIFICATION
220-240V/AC 50/60Hz
Mains voltage
Mains current
Mains power
19mA-21mA
4.5W
Output voltage (U-out max.)
68VDC
0.85
Power factor
Operation temperature
Ta: 0 ~ +50
℃
Battery charge voltage
3.0V ~ 4.5V
Battery charge current
Max.200mA
Battery pack
3 x 4.0 Ah C cell or 18670 type NiMH battery pack
24 hours
Charge period
+75
℃
Max. case temp.
Battery duration
Min. 3 hours
Mains Switch-over voltage range
120VAC - 180VAC
Output LED current
40mA (60VDC) - 320mA (8VDC)
Over-heat protection
Over-heat protection with auto-reset.
EN55015, EN61547
EMC standard
EN50172, EN61347-2-7, EN61347-2-13, IEC62034, BS5266
Safety standard
Certification
Semko, CE, EMC
Dielectric strength
Input
→
output: 3750V/AC
IP20
IP grade