background image

HHC9025/I-20180731-A1

Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button     Shift at first. 

2. Select the buttons in    “Detection range”,    /    “Daylight threshold”,    
   “Hold time”,     “Stand-by time”,    “Stand-by dimming level” to set all 
    parameters.    

Daylight threshold [ zone           ]          

Troubleshooting

MALFUNCTION CAUSE REMEDY

CAUSE

REMEDY

The fixture does not light up

The fixture is always on

Check detection area setting

The fixture is on when it should not

Incorrect daylight threshold setting

Continous movement in the detection zone 

Sudden change in temperature due to weather (wind, rain, 
snow) or air expelled from fans, or open windows

Detection zone not targeted

Faulty fixture

No power supply

Adjust daylight threshold setting

Replace fixture

Check power to sensor

Check detection area setting

Adjust zone, change installation site

3. Press button “Memory” to save all the settings programmed in the 
    remote control.

4. Press button “Apply” to set the settings to each sensor unit(s).     
    For example, to pre-set detection range 100%, daylight threshold Disable, 
    hold time 5min, stand-by time +∞, stand-by dimming level 30%, steps 
    should be: Press button     Start, button     100%,     Disable,      Shift,      
    5min,      Shift,    +∞,     30%,     Memory. By pointing to the sensor unit(s) 
    and pressing      Apply, all settings are passed on the sensor(s).      

8

8

8

3

3

9

9

10 11

11

12

14

12

13

14

Dual tech & RF mode [ zone     ]

All buttons in zone      are disabled. 

15

15

Stand-by dimming level [ zone      ]

Press buttons in zone     to set the stand-by dimming level at 10% / 20% / 30% 
/ 50%.
Note: the function of “Auto-config” is disabled.

14

14

Stand-by time [ zone     ]

Press buttons in zone     to set the stand-by period at 0s / 10s / 1min / 5min / 
10min / 30min / 1h / +∞. 
Note: “0s” means on/off control; “+∞” means the stand-by period is infinite and 
the light is effectively controlled by the daylight sensor, 

off when natural light is 

sufficient and automatically on at dimming level when insufficient.

13

13

         2. 2s is for test purpose only, stand-by period and daylight sensor settings
         are disabled in this mode. 

*To exit from Test mode, press button     or any button in zone     .    

3

2

12

Ambient daylight threshold [ button      ]

1. Press button     Shift, the red LED flashes for indication. 
2. Press button     , the ambient lux level is sampled and set as the new
    daylight threshold. 

3

11

11

Detection range [ zone     ] 

Press buttons in zone      to set detection range at 100% / 75% / 50% / 10%.

9

9

11

Press buttons in zone           to set the daylight sensor at 2Lux / 10Lux
/50Lux / 100Lux / 300Lux / 500Lux or Disable. 
Note: To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button   
Shift at first.  

10

11

10

3

13

Hold time [ zone     ]

Press buttons in zone     to set the hold time at 2s / 30s / 1min / 5min /10min /
15min / 20min / 30min. 

12

12

Scene prog. [ zone      ] (One-key-commissioning)

1. Press button “Start” to program.

8

Brig/- [ button 

 ]

Press the buttons under below modes:
AUTO mode: to adjust hold-time light brightness.
Sensor off mode: to adjust light brightness.
Twilight mode: to adjust light brightness and reset the output lux value in line 
with natural light for daylight harvest function. The higher natural lux level, the 
lower output brightness, and vice-versa.

Reviews: