Hytronik HCD418-DH Installation And Instruction Manual Download Page 3

HCD418-DH-20170427-A1

Terminations and wiring diagrams

Basic

Point-by-point basic end user installation

Synchronised - ‘Master’

Sync terminal to other sensor luminaires 

Description of the Button Functions 
(remote control HRC-11)

HRC-11

6

8

10

11

12

13

14

2

4

1

3

7

9

5

Permanent ON/OFF [               ]

Press button      to select permanent ON or permanent OFF mode.
* Press button     /     to resume automatic operation.
The mode will change to AUTO Mode after power failure. 

Semi-auto Mode [ button     &     ]

Power output [ button     ]

Press button     , the light output shifts between 80% and 100%.
Note: the function of “Sensor off” and “Twilight” are disabled.          

button 

Auto Mode [ button     ]

Shift [ button      ]

RESET [ button     ]

Press button     , all settings go back to the DIP switch settings.

Press button     to initiate automatic mode. The sensor starts 
working and all settings remain as before the light was switched 
ON/OFF.

Press button     , the LED on the top left corner flashes to indicate 
mode selection.    
All values / settings in RED are in valid for 20 seconds. 

1. Press button     Shift (the red LED is on for indication), 
2. press button     to initiate semi-auto mode. The fixture is  
    manually on by push-switch and will automatically turn off    
    after stand-by period.

1

2

2

3

3

3

3

4

4

4

5

Brig/- [ button     ]

Press button     to adjust the light output brightness and set as a 
new target lux level. The built-in daylight sensor can measures 
ambient daylight level from behind the diffuser and calculates how 
much artificial light is needed to maintain the target lux level. 

6

6

5

4

1

2

4

Ambient daylight threshold [ button      ]

Detection range [ zone     ] 

Press buttons in zone      to set detection range at 100% / 
75% / 50% / 10%.

Stand-by time [ zone     ]

Press buttons in zone     to set the stand-by period at 0s / 10s / 
1min / 5min / 10min / 30min / 1h / +∞. 
Note: “0s” means on/off control; “+∞” means the stand-by 
time is infinite and the light is effectively controlled by the 
daylight sensor, off when natural light is sufficient and 
automatically on at dimming level when insufficient.

Daylight threshold [ zone      ]          

Press buttons in zone     to set the daylight sensor at 2Lux / 
10Lux / 50Lux / 100Lux / 300Lux / 500Lux or Disable.
Note: To set daylight sensor at 100Lux / 300 Lux / 500Lux, 
        press button     Shift at first.

1. Press button     Shift, the red LED flashes for indication. 
2. Press button     , the ambient lux level is sampled and set as 
    the new daylight threshold.

Hold time [ zone     ]

Press buttons in zone     to set the hold time at 2s / 30s / 1min / 
5min / 10min / 15min / 20min / 30min.
Note: 1.To set hold-time at 30s / 5min / 15min / 30min, 
            press button     Shift at first.
         2. 2s is for test purpose only, stand-by period and daylight     
             sensor settings are disabled in this mode.
*To exit from Test mode, press button     or any button in zone     .    

Stand-by dimming level [ zone      ]

Press buttons in zone     to set the stand-by dimming level at 
10% / 20% / 30% / 50%.

8

3

3

2

9

10

11

12

13

Daylight harvest auto-configuration

1.Press button      ,the red LED starts to flash.
2.Select a time period and the sensor will do light level 
measurement and determine/save the lowest light level
(commission line) with 100% light on,so as to set the target 
lux level automatically.
Note:1.Make sure the light level measurement covers the 
night time.
        2.The fixture will go into sensor mode after the 
measurement, all sensor setting remain unchanged. 

Dual tech & RF mode [ zone     ]

All buttons in zone      are disabled. 

14

14

13

 3

12

11

11

10

9

8

Scene prog. [ zone      ] (One-key-commissioning)

1. Press button “Start” to program.
2. Select the buttons in    “Detection range”,    /    “Daylight 
   threshold”,    “Hold time”,    “Stand-by time”,    “Stand-by 
   dimming level” to set all parameters.
3. Press button “Memory” to save all the settings programmed 
    in the remote control.
4. Press button “Apply” to set the settings to each sensor unit(s).     
    For example, to pre-set detection range 100%, daylight 
    threshold Disable, hold time 5min, stand-by time +∞, 
    stand-by dimming level 30%, steps should be:
    Press button     Start, button     100%,     Disable,     Shift,      
       5min,    Shift,     +∞ ,    30%,    Memory. By pointing to 
    the sensor unit(s) and pressing    Apply, all settings are 
    passed on the sensor(s).

7

7

7

7

3

3

8

8

9 10

10

11

13

12

11

12

13

3

Hytronik Industrial Ltd.  |  www.hytronik.com

3rd Floor, block C, complex building, 155#, 

Bai'gang road south, Bai'gang village, 

Xiao Jin Kou town, Huicheng district, Huizhou 516023

Tel: 86-752-2772020  Fax: 86-752-2777877

Push Sync

HCD418-DH

-

+

Dali

HCD418-DH

Push

Sync

- +

Dali

HCD418-DH

- +

Dali

Push

Sync

- +

Dali

-

+

LED

N L

LED Driver

- +

Dali

-

+

LED

N L

LED Driver

- +

Dali

-

+

LED

N L

LED Driver

Reviews: