Hytronik HCD418-DH Installation And Instruction Manual Download Page 1

HCD418-DH-20170427-A1

Wire preparation

16-18AWG

8mm

Dimensions (mm)

Fixture Built-in DALI Motion Sensor 

Installation and Instruction Manual

 

HCD418-DH

This product utilises photocell advance 
technology to realise occupancy and true 
automatic photocell functions in one product. 
The technology allows luminaire design to be 
simplified as the luminaire body no longer 
needs to be drilled to accept a photocell for 
assessing the daylight condition.  This sensor 
can tell the difference of nature light and 
artificial light (LED) from behind the diffuser, 
and measure ambient natural light then 
calculate how much artificial light is needed to 
reach the target lux level. The need is passed 
to the driver by DALI signal for delivering the 
right amount of light. 

The light will be dimmed to minimum level and 
switched off eventually if ambient daylight is 
sufficient, no matter it is during hold-time or 
stand-by time, with or without motion.

Introduction

Technical Specifications

Product type                           Built-in DALI motion sensor (daylight harvest)
Operating voltage                    120~277VAC  50/60Hz
Switched power                      max. 20 devices
                                              max.40mA
Stand-by power                       < 1W
Detection settings                    50% / 100%
Hold time                                 5s / 3min / 10min / 30min                                               
Stand-by time                          0s / 10s / 1min / 5min / 10min / 30min / 1h / + 
Stand-by dimming level           10% / 30% 
Daylight threshold                    2 ~ 50Lux , Disable
Detection area (DxH)                12 x 6 m
Microwave frequency               5.8 GHz    +/- 75Mhz
Microwave power                    <0.2 mW
Warmming-up time                 20s
Operating temperature            -20

o

C ~ +60

o

C

8

Daylight Harvest

Installation

Please read this manual carefully before 
installing the microwave sensor and siting the 
luminaire.

Both the microwave sensor (antenna) and the 
photocell elements of the product must be in 
front of any metal work and have full line of 
sight to the cover/diffusing element of the 
fixture for trouble-free operation.

After Installing the sensor, it is highly 
recommended that the luminaire is tested for 
compatibility and correct operation of all 
components.

Note: If testing under laboratory conditions, 
the unique nature of this product requires full 
bandwidth of the visible and invisible parts of 
the electromagnetic spectrum, therefore it is 
not recommended to attempt daylight 
simulation with artificail light sources.

Not suitable for use with
Incandescent or Halogen
lamps

Not suitable for use in 
installations where glass 
is treated for reflection 
of infrared radiation

Preparation of Luminaire

1. Positioning

This microwave sensor is ideal for use with LED 
luminaires with the following considerations:

For simple mounting, the sensor may be placed on 
the LED side of the LED PCB.  The microwave 
sensor will not be able to ‘see’ through any metal 
components of the fixture.  (See diagram 1 
opposite).

For shadow-free operation, it is recommended that 
the LED PCB is designed with a viewing window for 
the sensor so that it may fit flush (or slightly proud) 
of the LED PCB.  (Please refer to diagram 2)

2. Configure the luminaire

Referring to the wiring diagrams overleaf, it is best 
to consider terminations of the luminaires offered to 
the installer dependant on system or project design.  
If in any doubt, it is recommended that all 8 
terminals of the sensor are made accessible to the 
installer so that all of the features may be used if 
required. 

3.  Wiring

To assist with installation, Hytronik use push-wire 
style terminals.  It is recommended that single core 
(1/0.8mm for example) is used for making the 
connections to the sensor.
The full specification for the wiring terminal is:

Detection area

Infrared remote receiver

Hold-time

Daylight sensor

Stand-by period

Stand-by dimming level

Daylight sensor

SYNC

Push

N L

DALI 

-

DALI

 

+  

Installation hole (4.2mm)

Sensor antenna

IR sensor 

Buzzer

Diagram 2. Typical layout - behind LED PCB with cut-out

Diagram 1. Typical layout - in front of LED PCB

Base

LED PCB

Sensing direction

Sensing direction

Diffuser (Non-metal)

Glass less than 0.5cm

LED PCB

Cut-out 45mm x 31mm

22mm PCB support pillars

Photocell Advance

Reviews: