Press buttons in zone “ Daylight threshold” to set daylight sensor / target lux level at 50Lux / 100Lux / 300Lux / 500Lux / Disable.
Note: 2lux / 10lux are disabled.
To set daylight sensor at 100Lux / 300Lux / 500Lux, press “Shift” button first.
Daylight threshold
1. Press button “Shift”, the red LED starts to flash.
2. Press button “Ambient”, the surrounding lux level is sampled and set as the new daylight threshold / target lux level.
Ambient daylight threshold
Hold-time
Press buttons in zone “hold-time” to set the hold-time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.
Note: 1. To set hold-time at 30s / 5min / 15min / 30min, press “Shift” button first.
2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode.
*To exit from Test mode, press button “RESET” or any button in “Hold-time”.
Dual tech & RF mode
Stand-by dimming level
Stand-by time (corridor function)
Press buttons in zone “stand-by time” to set the stand-by period at 0s /
10s / 1min / 5min / 10min / 30min / 1h / +∞.
Note: “0s” means on/off control; “+∞” means bi-level control, the fixture is 100% on
when there is motion detected, and remains at the stand-by dimming level
when no presence after motion hold-time.
Press the button in zone “stand-by dimming level” to set the stand-by
dimming level at 10% / 20% / 30% / 50%.
1. Press buttons in this zone to select sensor technology.
HF+PIR: the light is on when both HF and PIR sensors are activated.
HF/PIR: the light is on when HF or PIR sensors are activated.
2. Learn / Erase, Transmit, RX100% and RX STBY% are disabled.
Detection Pattern
HF walking across 10m
PIR walking towards 8m
A rotary switch is built inside the sensor for scene
selection / fast programming. Total 16 channels
are available:
Rotary switch preset
Rotary Switch Preset
Note: settings can also be changed by remote control
HRC-11. The last action controls.
0
5s
100%
Disable
1
1min
100%
50Lux
2
5min
100%
50Lux
3
5min
100%
75Lux
4
5min
100%
100Lux
5
5min
100%
200Lux
6
10min
100%
50Lux
7
10min
100%
75Lux
8
10min
100%
100Lux
9
10min
100%
200Lux
A
20min
100%
100Lux
B
20min
100%
200Lux
C
30min
100%
100Lux
D
30min
100%
200Lux
E
30min
100%
400Lux
F
5s
100%
10%
10%
10%
10%
10%
30%
10%
10%
10%
30%
10%
30%
10%
30%
50%
10%
100Lux
10s
5min
10min
+∞
+∞
+∞
30min
+∞
+∞
+∞
1h
+∞
+∞
+∞
+∞
10s
Detection
range
Channel
Hold-time
Stand-by
time
Stand-by
dim level
Daylight
sensor