98
MX3636-01 Rev. D
HydraSwing Programming & Operations
© 2018
e
LectricaL
i
SSueS
A general set of troubleshooting procedures are provided in the following paragraphs. Use a voltmeter to take
the measurements described in the steps. If at any point in the process, a result different than what’s expected
occurs, stop and identify the problem.
AC-Powered Gate Operators
PROBLEM 1:
Pushed the OPEN and CLOSE button, but the motor is not running.
1.
Verify the incoming voltage and phase at the incoming power terminals matches the voltage and phase on the
nameplate of the motor. They must match!
2.
Verify the 24VAC transformer has the proper connection to the incoming power (the black wire is always
connected); White – 115VAC*, Red = 208VAC, Orange = 230VAC, Blue = 480VAC.
3.
Verify the primary tap wires match line voltage connected to operator. Measure the line voltage carefully to
distinguish between 208V and 230V branch circuits or between 390V and 460V branch circuits. A label on top
of the transformer identifies the various voltage taps. This connection must match the voltage on the operator
nameplate.
NOTE:
Primary taps do not exist on battery operators.
4.
Verify the 24VAC is present at the Red and Green wires from the control transformer to the Power Supply Board
by measuring the bottom of the power supply board at the -ACC+ connectors.
5.
Verify that the main power wires are at least the minimum wire size specified in
on
page 17. Be certain that the branch circuit wire size versus the distance of the run from the main panel is large
enough to avoid excess voltage drop.
6.
Verify 24VDC power is present on the Power Supply Board between the +24VDC terminals above the terminal
strip and any screw connection on the terminal strip.
7.
Be sure a 20A circuit (protected with a 20A inverse time breaker) is provided.
8.
Check and make sure the operator is electrically grounded per NEC Article 250 and local codes.
9.
Verify the 24VDC is present at the +24VDC and common terminals located along the lower edge of the Smart
Touch Controller board. (RADIO OPTIONS, etc.)
10.
Verify that the “Heart Beat” LED is blinking green.
11. Verify the display is operational on the LCD and VFD display.
12. With the knowledge that the power is correct and the electric motor runs, check the STC display. If an error, alert
or fault code appears, refer to
Table 8: Troubleshooting Codes
on page 92 to determine possible resolutions.
Summary of Contents for HSG80F
Page 2: ...www SecureOpeners com 800 878 7829 Sales SecureOpeners com...
Page 14: ...Page intentionally left blank xiv MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 36: ...Page intentionally left blank 22 MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 124: ...110 MX3636 01 Rev D HydraSwing Programming Operations 2018 Page intentionally left blank...
Page 136: ...122 MX3636 01 Rev D HydraSwing Programming Operations 2018...