Page 26
7.3.2 Internal electrical eonnection w/
o HygroMatik control
Blow-down
For blowing-down the cylinder water, the
blow-down interval should be set in a way
that after 60 mins of steam production the
pump runs for 7 secs.
When running the kit with tap water, increas-
ing the number of blow-down cycles may
enlarge the specific maintainance interval.
If required, pls. contact your expert dealer or
HygroMatik for advice.
Control cylinder
The Steamkit-H kit is delivered with a control
cylinder that holds a floating switch array
consisting of reed switches for the stepped
monitoring of the water level. Three levels
are discriminated. The wire colours are
assigned as follows:
Red - max. level
Orange - refilling
Black - dry level
Brown - phase L1
Included in the delivery scope is a varistor
the usage of which is recommened for the
smooth operation of the kit.
The varistor smoothes the load peaks
impacting on the reed switches. The wiring
(across the solenoid valve connections) is
depicted in the interconnection diagram (s.
section 7.4.1).
7.3.3 Internal Electrical Connection
when the kit is delivered with a
HygroMatik control
Use of Control Standard
Part of the delivery scope of the control is a
level control for the continuous monitoring of
the water level in the steam cylinder. Connec-
tion diagrams for the electrical interconnec-
tion of the kit with the Control Standard can
be found in section 3.1.1 („Wiring diagrams“)
of the respective manual.
7.4 Connection diagrams
In case of a HygroMatik Control Basic or
Control Standard to be used with the kit, the
device-specific wiring diagrams are included
in the scope of delivery. Please use them for
the installation and keep them in a safe
place.
For all other types of application, the connec-
tion of the electrical components is the
responsibility of the customer.
Folllowing hereafter, pls. find 2 recommenda-
tions for setting up a simple control making
use of the control cylinder supplied with the
kits that are delivered without a HygroMatik
control.