POWERING UP 

-

 FIRST TIME USE 

-

 WITHOUT INSULATING TAB

 

 

Use this procedure the first time you power up a 

TAU

-

TH

-

01

; the detector has not been supplied with the insulating tab.

 

1)

 

Make sure the Link / program switch is set on 

ON

”.

 

2)

 

Insert the two supplied batteries into their device

s lodgments.

 

 

POWERING UP 

-

 DEVICE LINKED TO THE SYSTEM

 

 

Use this procedure when a 

TAU

-

TH

-

01

-

BL

is successfully linked to its Taurus system and you have to extract one or both batteries (e.g. 

batteries substitution).

 

1)

 

Reinsert the battery or both batteries into their lodgments.

 

If performing a batteries substitution, use two brand new batteries and substitute both of them.

 

Do not touch the Link / program switch.

 

 

POWERING UP 

-

 RECOVERY

 

 

Use this procedure when you fail to link successfully a 

TAU

-

TH

-

01

-

BL

or you want to link it again.

 

1)

 

Move alternatively the Link / program switch 5 times.

 

2)

 

Set the Link / program switch on 

ON

”.

 

3)

 

Insert the two supplied batteries into their device

s lodgments.

 

 

LINKING 

-

 WAKE

-

UP 

-

 WITHOUT INSULATING TAB

 

 

Wake

-

up

” 

linking consists in associating one or more child devices to the Taurus system altogether in a single operation.

 

Wake

-

up is performed either through the 

TauREX

 software or the 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

 keyboard

-

screen interface; it CANNOT be 

done through 

TAU

-

EXM

-

01

 devices.

 

1)

 

Create the 

virtual model

” 

of the 

TAU

-

TH

-

01

-

BL

either on 

TauREX

 or on the 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

.

 

2)

 

Power

-

up the detector (either 

first time use

” 

or 

recovery

”).

 

3)

 

Set the Link / program switch OPPOSITE to 

ON

”.

 

4)

 

Trigger the wake

-

up procedure either from 

TauREX

 or from the 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

.

 

5)

 

Wait the end of the 

wake

-

up

” 

linking procedure.

 

6)

 

Check on 

TauREX

 or from 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

 for linking success. Consult their user manual.

 

 

LINKING 

-

 ONE

-

BY

-

ONE 

-

 WITHOUT INSULATING TAB

 

 

One

-

by

-

one

” 

linking consists in associating one child device at a time to the Taurus system.

 

This operation is performed either through the 

TauREX

 software or the 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

 keyboard

-

screen interface; it CANNOT 

be done through 

TAU

-

EXM

-

01

 devices.

 

1)

 

Create the 

virtual model

” 

of the child device either on 

TauREX

 or on the 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

.

 

2)

 

Trigger the linking procedure either from 

TauREX

 or from the 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

.

 

3)

 

Power

-

up the child device (either 

first time use

” 

or 

recovery

”).

 

4)

 

Set the child device

s Link / program switch OPPOSITE to 

ON

”.

 

5)

 

Wait the end of the 

one

-

by

-

one

” 

linking procedure.

 

6)

 

Check on 

TauREX

 or from 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

 for linking success. Consult their user manual.

 

 

TESTING

 

 

Magnet test

 

1)

 

Activate test mode.

 

2)

 

Apply again the magnet in correspondence of the 

magnet test activation area

.

 

3)

 

LED indicators signal 

Alarm activation

”.

 

 

Heat test

 

1)

 

Activate test mode.

 

2)

 

Apply the heat test device to the detector.

 

3)

 

Wait a few seconds.

 

4)

 

LED indicators signal 

Alarm activation

”.

 

 

BATTERY FAULTS AND BATTERY SUBSTITUTION PROCEDURE

 

 

When one or both batteries are low in charge, a specific fault message is routed to the 

control panel. If such event occurs:

 

1)

 

Remove the safety screw.

 

2)

 

Remove the detector from its base.

 

3)

 

Remove the batteries cover.

 

4)

 

Extract both batteries.

 

5)

 

Insert both new batteries into their holders, oriented as per polarity marks.

 

 

See 

POWERING UP 

-

 DEVICE LINKED TO THE SYSTEM

.

 

6)

 

Reinstall the batteries cover.

 

7)

 

Reinstall the detector.

 

8)

 

Reinstall the safety screw.

 

Local  safety  standards  may  require  you 

to test these devices on a regular basis.

 

 

Use  only  suitable  heat  test devices  supplied by 

approved  manufacturers.  Follow  their  specific 

use instructions.

 

Before  testing  every  TAU

-

TH

-

01,  always 

activate  test  mode.  This  is  done  by 

holding  a  suitable  magnet  in  the 

magnet  test  activation  area

”. 

When  activated, 

LED indicators signal 

Test mode active

”.

 

When  a  low  battery  condition  is  indicat-

ed,  both  batteries  must  be  changed 

altogether.

 

 

Batteries must be brand new.

 

 

Do not touch the Link / program switch.

 

 

Ensure  that  the  batteries  are  installed  properly, 

with their polarities matching the indications on 

the device.

 

Always  ensure  that  the  batteries  are 

installed  properly,  with  their  polarities 

matching the indications on the device.

 

Hyfire Wireless Fire Solutions Ltd 

-

 Unit B12a, Holly Farm Business Park, Honiley, 

 

Warwickshire, CV8 1NP 

-

 United Kingdom

 

www.hyfirewireless.com

 

 

3

 

MAINTENANCE 

-

 CLEANING

 

 

1)

 

Remove the safety screw.

 

2)

 

Remove the detector from its base.

 

3)

 

Thermistor area: use a small, soft bristle brush to dislodge any obvious contaminants such as insects, spider webs, hairs, etc.

 

4)

 

Thermistor area: use a small vacuum tube or dry, clean, compressed air to suck up or blow any remaining small particles away.

 

5)

 

Wipe the exterior housing of the detector with a clean, damp, lint

-

free cloth to remove any surface film that can later attract airborne 

 

 

contaminants.

 

6)

 

Install the detector onto its base again.

 

7)

 

Test the detector.

 

8)

 

Reinstall the safety screw.

 

 

TECHNICAL SPECIFICATIONS

 *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

 

See TDS

-

TWDTX technical specification document for further technical data.

 

**

 

Detector

s rate of rise (A1R) / high temperature (BS) modes can be set through 

TauREX

.

 

 

BATTERIES SPECIFICATIONS

 

 

 

 

 

 

 

 

 

 

*

 

Batteries lifespan depends by environmental conditions, default monitor settings and link quality.

 

 

 

 

 

 

Specification

 

Value

 

Communication range with 

TAU

-

TRM

-

01

TAU

-

CEM

-

01

 or 

 

TAU

-

EXM

-

01

 network devices

 

200 m (in open space)

 

Wireless frequency band

 

868 MHz

 

Number of wireless channels

 

66

 

Radiated power

 

14 dBm (25 mW)

 

Temperature alarm threshold (A1R rate of rise setting) ** 

 

58 °C

 

Temperature alarm threshold (BS high temperature setting) ** 

 

78 °C

 

Operating temperature range

 

-

10 °C to 55 °C

 

Maximum humidity (non condensing)

 

95% RH

 

IP rating

 

40

 

Specification

 

Value

 

Batteries type

 

CR123A (3 V, 1.25 Ah)

 

Batteries lifespan *

 

10 years

 

Low battery threshold value (nominal)

 

2.850 V

 

Table 2

 

Table 3

 

 

WARNINGS AND LIMITATIONS

 

 

Our devices use high quality electronic components and plastic materials that are highly resistant 

to environmental deterioration. However, after 10 years of continuous operation, it is advisable to 

replace  the  devices  in  order  to  minimize  the  risk  of  reduced  performance  caused  by  external 

factors.  Ensure  that  this  device  is  only  used  with  compatible  control  panels.  Detection  systems 

must be checked, serviced and maintained on a regular basis to confirm correct operation. Smoke 

detectors  may  respond  differently  to  various  kinds  of  smoke  particles,  thus  application  advice 

should  be  sought  for  special  risks.  Detectors  cannot  respond  correctly  if  barriers  exist  between 

them and the fire location and may be affected by special environmental conditions. Refer to and 

follow  national  codes  of  practice  and  other  internationally  recognized  fire  engineering  standards. 

Appropriate risk assessment should be carried out initially to determine correct design criteria and 

updated periodically.

 

 

Use only in Taurus fire detection and alarm systems.

 

 

 

WARRANTY

 

 

All devices are supplied with the benefit of a limited 5 years warranty relating to faulty materials or 

manufacturing defects, effective from the production date indicated on each product. This warranty 

is  invalidated  by  mechanical  or  electrical  damage  caused  in  the  field  by  incorrect  handling  or 

usage.  Product  must  be  returned  via  your  authorized  supplier  for  repair  or  replacement  together 

with  full information  on any  problem  identified.  Full details  on  our  warranty and  product

s  returns 

policy can be obtained upon request.

 

Hyfire Wireless Fire Solutions Ltd 

-

 Unit B12a, 

Holly Farm Business Park, Honiley, Warwickshi-

re, CV8 1NP 

-

 United Kingdom

 

TAU

-

TH

-

01

-

BL

 

 

EN 54

-

25:2008

 

 

EN 54

-

5:2017+A1:2018

 

Class P (A1R / BS)

 

[email protected]

 

L20

-

TWDT1

-

1400 (vA.1)

 

 

4

 

0051

 

22

 

HF

-

20

-

041CPR

 