
TESTING
1) Activate the call point.
LED indicator signals “Alarm activation”; the control panel receives the alarm message.
2) Deactivate the call point.
3) Reset the control panel.
BATTERY FAULTS AND BATTERY SUBSTITUTION PROCEDURE
When one or both batteries are low in charge, a specific fault message is routed to the
control panel. If such event occurs:
1) Remove the device block from the back box.
2) Extract both batteries.
3) Insert both new batteries into their holders, oriented as per polarity marks.
See
POWERING UP - DEVICE LINKED TO THE SYSTEM
.
4) Reinstall the device block.
TECHNICAL SPECIFICATIONS
*
* See TDS-TWCPX technical specification document for further technical data.
BATTERIES SPECIFICATIONS
* Batteries lifespan depends by environmental conditions, default monitor settings and link quality.
Local safety standards may require you
to test these devices on a regular basis.
When a low battery condition is indicat-
ed, both batteries must be changed
altogether.
Batteries must be brand new.
Do not touch the Link / program switch.
Ensure that the batteries are installed properly,
with their polarities matching the indications on
the device.
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to environmental
deterioration. However, after 10 years of continuous operation, it is advisable to replace the devices in order to
minimize the risk of reduced performance caused by external factors. Ensure that this device is only used with
compatible control panels.
Detection systems must be checked, serviced and maintained on a regular basis to confirm correct operation.
Smoke sensors may respond differently to various kinds of smoke particles, thus application advice should be
sought for special risks. Sensors cannot respond correctly if barriers exist between them and the fire location and
may be affected by special environmental conditions. Refer to and follow national codes of practice and other
internationally recognized fire engineering standards.
Appropriate risk assessment should be carried out initially to determine correct design criteria and updated periodi-
cally.
Use only in Taurus fire detection and alarm systems.
WARRANTY
All devices are supplied with the benefit of a limited 3 years warranty relating to faulty materials or manufacturing
defects, effective from the production date indicated on each product. This warranty is invalidated by mechanical or
electrical damage caused in the field by incorrect handling or usage. Product must be returned via your authorized
supplier for repair or replacement together with full information on any problem identified. Full details on our war-
ranty and product’s returns policy can be obtained upon request.
Hyfire Wireless Fire Solutions
Ltd - Unit B12a, Holly Farm
Business Park, Honiley,
Warwickshire, CV8 1NP -
United Kingdom
20
HF-20-023CPR
TAU-CP-R-01
EN 54-25:2008
EN 54-11:2001 + A1:2005
Type A (direct operation)
Indoor use only
0051
Specification
Value
Communication range with
TAU-TRM-01
,
TAU-CEM-01
or
TAU-
EXM-01
network devices
200 m (in open space)
Wireless frequency band
868 MHz
Number of wireless channels
66
Radiated power
14 dBm (25 mW)
Operating temperature range
-10 °C to 55 °C
Maximum humidity (non condensing)
95% RH
Environmental application
Indoors
Dimensions
88 mm x 87 mm x 61 mm
Weight
160 grams (without batteries)
Table 3
Specification
Value
Batteries type
CR123A (3 V, 1.25 Ah)
Batteries lifespan *
10 years
Low battery threshold value (nominal)
2.850 V
Table 2
L20-TWCPR1-1400 (vA.3)
4