hyfire HFW-TRI-05 Quick Start Manual Download Page 5

 

MAINTENANCE 

-

 CLEANING

 

 

1)

 

Remove the detector from its base.

 

 

2)

 

Smoke  entry  areas  and  thermistor  area:  use  a  small, 

soft  bristle  brush  to  dislodge  any  obvious  contaminants 

such as insects, spider webs, hairs, etc.

 

 

3)

 

Smoke  entry  areas  and  thermistor  area:  use  a  small 

vacuum tube or dry, clean, compressed air to suck up or 

blow any remaining small particles away.

 

 

4)

 

Wipe the exterior housing of the detector with a clean, 

damp,  lint

-

free  cloth  to remove  any  surface  film  that  can 

later attract airborne contaminants.

 

 

5)

 

Install the detector onto its base again.

 

 

6)

 

Test the detector.

 

 

 

 

MAINTENANCE 

-

 BATTERY REPLACEMENT

 

 

When a low battery condition is indicated, 

 

both batteries must be changed altogether.

 

 

During this procedure the linking switch must NOT 

 

be touched at all !

 

 

 

1)

 

Detach the detector from its base.

 

 

2)

 

Extract the batteries cover.

 

 

3)

 

Extract the batteries.

 

 

4)

 

Insert the new batteries into their holders, 

 

 

oriented as per polarity marks.

 

 

5)

 

Reinstall the batteries cover.

 

 

6)

 

Reinstall the detector onto its base.

 

 

7)

 

Test the detector.

 

 

Table 4

 

TECHNICAL SPECIFICATIONS **

 

Communication range with the 

translator or expander

 

200 m

 

Open space

 

Operating frequency

 

868 MHz

 

 

Operating frequency channels

 

7

 

 

Radiated power

 

≤ 14 

dBm (25 mW)

 

 

Batteries type*

 

Type CR123A (3 Vdc)

 

 

Primary battery lifespan

 

 

7.2 years life

 

Secondary battery lifespan

 

 

43 days life (after 

primary battery low 

fault)

 

Approved battery voltage range

 

2.85 

-

 3.2V

 

 

Parent expander

s check

-

up period

 

60 seconds (default setting)

 

 

Alarm threshold temperature.

 

Class A1R ROR

 

58 °C

 

 

Alarm threshold temperature.

 

Class B 

-

 high temperature 

 

78 °C

 

 

Dimensions

 

110 mm x 65 mm

 

 

Weight

 

200 g

 

Base and batteries 

included

 

IP rating 

 

40

 

 

Max tolerated humidity

 

(no condensing)

 

95% RH

 

 

Operating temperature range

 

From –

10 

°C to +55 °C

 

 

WARNINGS AND LIMITATIONS

 

 

Our  devices  use  high  quality  electronic  components  and  plastic  materials  that  are  highly  resistant  to 

environmental deterioration. However, after 10 years of continuous operation, it is advisable to replace 

the  devices in order  to  minimize  the  risk  of reduced performance  caused by  external  factors.  Ensure 

that  this  device  is  only  used  with  compatible  control  panels.  Detection  systems  must  be  checked, 

serviced and maintained on a regular basis to confirm correct operation. Smoke detectors may respond 

differently  to  various  kinds  of  smoke  particles,  thus  application  advice  should  be  sought  for  special 

risks. Detectors cannot respond correctly if barriers exist between them and the fire location and may 

be  affected  by  special  environmental  conditions.  Refer  to  and  follow  national  codes  of  practice  and 

other  internationally  recognized  fire  engineering  standards.  Appropriate  risk  assessment  should  be 

carried out initially to determine correct design criteria and updated periodically.

 

 

WARRANTY

 

 

All  devices  are  supplied  with  the  benefit  of  a  limited  5  years  warranty  relating  to  faulty  materials  or 

manufacturing defects, effective from the production date indicated on each product. This warranty is 

invalidated  by  mechanical  or  electrical  damage  caused  in  the  field  by  incorrect  handling  or  usage. 

Product  must  be  returned  via  your  authorized  supplier  for  repair  or  replacement  together  with  full 

information on any problem identified. Full details on our warranty and product

s returns policy can be 

obtained upon request.

 

 

Hyfire Wireless Fire Solutions Limited 

-

 Unit 

B12a, Holly Farm Business Park, Honiley, 

 

Warwickshire, CV8 1NP 

-

 United Kingdom

 

 

 

EN 54

-

25:2008  

 

EN 54

-

5:2000

 

Class A1R & BS

 

 

EN 54

-

7:2000+A1:2002+A2:2006

 

EN 54

-

31:2014+A1:2016

 

Programmable MT/NT category

 

 

HFW

-

TRI

-

05

 

 

For use in compatible fire detection and 

alarm system

 

NOTE OF THE DOCUMENT:

 

Argus Security Srl  hereby declares that this detector is in compliance with the essential requirements 
and other relevant  provisions of Directive 1999/5/EC. A copy of the original Declaration of Conformity 
(Document: DoC LI01) is made available to the user on website: www.argussecurity.it

 

* When a low battery condition is indicated, both batteries must be changed for new cells.

 

   Lifespan of batteries indicated is subject to standard environmental conditions default 

 

   monitor settings and excellent link quality.

 

**  Check  latest  version  of  document  TDS

-

LDMCO  for  further  data,  obtainable  from  your 

supplier.

 