Problem: Combination Softener unit appear to be causing a high pressure drop in home water system. 

1.  Pressure drop may be due other factors. 

• 

Confirm pressure loss is due to the unit, and 
not the result of distribution or well pump problem. 

• 

Confirm pressure loss is due to unit by 
checking flow while in BYPASS mode. 

• 

Check that flow demand is not exceeding rated 
flow rate of Combination Softener unit. These units 
are supplied with a SERVICE LINE FLOW 
CONTROL to ensure maximum effectiveness is 
maintained. Attempting to exceed this flow control 
rating will result in a pressure drop. Combination 
Softener unit should be increased in size to 
compensate for larger demand. 

NOTE: Do not remove this FLOW CONTROL 
from valve outlet. It will likely result in a 
decrease in Combination Softener unit 
performance. 

2.  Pressure loss may be due to fouling from 

Organics, Iron or Calcium Carbonate. 

• 

See troubleshooting notes above on dealing with 
fouling problems. 

3.  Pressure loss may be due to Resin Media being 

plugged with Silt and Turbidity. 

• 

Try manually regenerating the unit and extending 
the backwash by unplugging unit during the first 
cycle that begins to send water to the drain. 
Monitor water to the drain and watch for dirt and 
silt. If present, continue this backwash cycle until 
water runs clear then plug unit and allow valve 
to finish regeneration normally. 

• 

Install multi-media filter or 5 micron cartridge filter 
ahead of the unit to remove Silt and Turbidity. 

Problem: Combination softener unit appears to be removing most of the colour in the water, but some still 
passes through. 

1.  Raw water may be partially slipping past Combination 

Softener unit or the Organics (Tannins) not being 
removed may be impervious to the resin media in the 
Combination Softener unit. 

• 

Check to see that  SERVICE LINE FLOW 
CONTROL is in place on the valve outlet. 
Flowrates higher than recommended through the 
unit may be causing some leakage of colour. 

• 

Check to see that BYPASS valve is not partially 
open and bleeding some raw water to distribution 
lines. 

• 

Check that pipelines after the unit are not lined 
with organics that are slowly being stripped away. 
Lines may require flushing. 

• 

If all equipment and distribution sources of problem 
have been eliminated, consult your water treatment 
dealer, who may try to “polish” the remaining colour 
after the the  unit with an ACTIVATED CARBON 
filter or cartridges or other treatment method. 

Summary of Contents for 5600 Calendar Clock Valve

Page 1: ...5600 Calendar Clock Valve Combination Organic Color Removal Softener Operation Manual Read all instructions carefully before operation 51426 Rev 12 08...

Page 2: ......

Page 3: ...for this application total removable of all colour contaminants may occasionally not be attained due to a Multiple types of tannins in the source water Unit media may only be successful at removing so...

Page 4: ...mately two inches from the fitting on the main water line Install an elbow on the end of the pipe nearest the outside faucet and a cap on the end connected to the existing water line Install piping fr...

Page 5: ...the valve to the brine and rinse position Allow the water to run at the drain for a further 2 to 3 minutes Using the same procedure turn the knob to rapid rinse position and allow to run for a few min...

Page 6: ...nd return to service Be sure there is adequate salt and salt brine in the brine tank for a satisfactory regeneration Setting the Regeneration Frequency Figure 5 The unit s control features a skipper w...

Page 7: ...softener is designed to operate under normal water pressures from 20 psi 1 4 atm to 120 psi 8 2 atm New Sounds You may notice new sounds as your water softener operates The regeneration cycle lasts ap...

Page 8: ...er To retain the attractive appearance of your new water softener clean occasionally with mild soap solution Do not use abrasive cleaners ammonia or solvents Never subject your softener to freezing or...

Page 9: ...ier into service run OR Problem Combination Softener unit was removing colour from water but no longer seems to be effective 1 Regeneration is not being performed adequately Check to see if salt is in...

Page 10: ...led with Iron Check visually to confirm Iron should typically be removed prior to the unit Install an iron filter upstream of the unit Clean iron from resin media bed with a reducing agent such as sod...

Page 11: ...unit during the first cycle that begins to send water to the drain Monitor water to the drain and watch for dirt and silt If present continue this backwash cycle until water runs clear then plug unit...

Page 12: ...RINE TANKS HYDROTECH will provide a replacement mineral or brine tank to any original equipment purchaser in possession of a tank that fails within 120 months provided that the water conditioner is at...

Reviews: