Hydronix HD0476 User Manual Download Page 3

2.2.1

Installing using the Mounting Collar

Drill a 25mm diameter hole in the mounting surface and 
weld the Mounting Collar centrally over it. The Thermo-
Tuff is retained by tightening two bolts on to the long flat 
areas of the sensor. 

To remove the sensor, loosen the screws and withdraw 
from the Mounting Collar. A spanner can be used on the 
two flat areas of the sensor to ease extraction of the 
sensor from the Mounting Collar.

When flush mounted, it is important to adjust the position 
of the sensor periodically so that the sensing face 
remains flush with the mounting surface and does not 
become damaged by any moving parts within the system. 
This will also prevent the build up of material around the 
sensor.

2.2.2

Installing using the Extension Mounting Sleeve and Collar

When mounting in a bin or hopper, the Extension 
Mounting Collar is welded into a 43mm diameter 
hole. The sensor should be installed into the 
Extension Mounting Sleeve so that it is flush with 
the end of the sleeve. It is retained with two grub 
screws. The Sleeve is then fitted in the Mounting 
Collar and the retaining bolts used to secure the 
assembly.

3

Electrical Installation

3.1

Power

The Thermo-Tuff is designed to be powered by the 4-20mA current loop. It does not have connections for an 
external power supply.

3.2

Analogue Output

The Thermo-Tuff outputs a continuous 4-20mA signal and this is scaled to read between 0 and 80°C as shown:

Temperature in °C = (I

o

 - 4) x 5

 

Where I

o

 is the output current in mA.

Current Output

Temperature

4mA

0 °C

32 °F

20mA

80 °C

176 °F

Mounting

Surface

Ø25mm

Hole

Weld

2x

retaining

bolts at

90°

Flats to

ease

removal

3-40mm

Ø43mm

Hole

50mm

220mm

Extension Mounting

Collar

Extension Mounting Sleeve

150mm

Max

Holes for inserting an extension

bar to ease removal

Weld

2x Retaining

Bolts @ 90°

0

10

20

30

40

50

60

70

80

90

0

5

10

15

20

Current Output (m A)

T

em

p

er

at

u

re (

°C

)

SUNSTAR传感与控制 http://www.sensor-ic.com/ TEL:0755-83376549 FAX:0755-83376182 E-MAIL:[email protected]

SUNSTAR自动化 http://www.sensor-ic.com/ TEL: 0755-83376489 FAX:0755-83376182 E-MAIL:[email protected]

Summary of Contents for HD0476

Page 1: ...on 1 0 1 Revision Date January 2011 Thermo Tuff User Guide SUNSTAR传感与控制 http www sensor ic com TEL 0755 83376549 FAX 0755 83376182 E MAIL szss20 163 com SUNSTAR自动化 http www sensor ic com TEL 0755 83376489 FAX 0755 83376182 E MAIL szss20 163 com ...

Page 2: ...ement Range 0 80 C Storage Temperature 10 80 C Voltage Range 10 28v DC Reverse Polarity Protected IP Rating IP68 Weight 600g including 4m cable Installed T90 56s 2 Mechanical Installation 2 1 Dimensions 2 2 Installation Options The sensor can be mounted vertically or horizontally The sensing surface must touch the material being measured The Thermo Tuff is designed to be maintenance free and does ...

Page 3: ...n Mounting Sleeve so that it is flush with the end of the sleeve It is retained with two grub screws The Sleeve is then fitted in the Mounting Collar and the retaining bolts used to secure the assembly 3 Electrical Installation 3 1 Power The Thermo Tuff is designed to be powered by the 4 20mA current loop It does not have connections for an external power supply 3 2 Analogue Output The Thermo Tuff...

Page 4: ...put scaling Check the voltage across the TT01 Noisy Signal Check total resistance in the loop No Current Check polarity Output clamps at less than 20mA Check the resistance of the cable and the control system input Check the voltage across TT01 5 Declaration of conformity Wire Colour Description Red Current Loop Positive Blue Current Loop Negative Screen Earth This device complies with part 18 of ...