Page 13
5.1.1 Dimensions and Mounting
Directions
Table of dimensions
Model
X [mm/inch] Y [mm/inch] Z [mm/inch] A [mm/inch] B [mm/inch]
FLE05-FLE10*
460/~21.3
535/~21
320/~12.6
310/~15.4
400/~15.7
FLE15-FLE25
540/~21.3
695/~27.4
320/~12.6
390/~15.4
560/~22
FLE30-FLE40
580/~22.8
750/~29.5
355/~14
425/~16.7
620/~24.4
FLE50-FLE65
640/~25
785/~30.9
420/~16.5
490/~19.3
650/~25.6
FLE80
1130/~43.1
750/~29.5
420/~16.5
870/~34,4
620/~24.4
FLE100-FLE130
1170/~46
785/~30.9
420/~16.5
1000/~39.4
660/~25.6
<
=
;
$
%
Detailed measurements under
https://www.hygromatik.com/files/pdf/hygromatik-flexline-dimensionsv13.pdf
.
3D models under
https://www.hygromatik.com/en/downloads
* Units with production date January 2022 and earlier: X:540 / A:390
Wall clearances
When mounting the steam
humidifier, the wall clearanc-
es shown in the fig. below
must be obeyed::
* distance to designated paths
A
5 cm / 2,0 inch
B
50 cm / 19,7 inch
C
20 cm / 7,8 inch
D
60 cm / 23,6 inch
E
30 cm / 11,8 inch
A
B
C
D
E
Y
X
Z
*