Programmable
Water Feeder for
Steam Boilers
120 VAC Operating Voltage
U.S. Patent No. 6,688,329
INSTALLATION
Model VXT-120
WARNING
– To
prevent electrical
shock or equipment
damage, power
must be off during
installation or ser-
vicing of the con-
trol. To prevent
serious burns, the boiler should be thoroughly cooled
before installing or servicing control. Only qualified
personnel may install or service the control in accor-
dance with local codes and ordinances. Read instruc-
tions completely before proceeding.
Feeder must be installed with a manual by-pass. Use isolation valves and
unions to allow easy removal for service or replacement. Remove and
clean the feed valve strainer after the first feed cycle to remove any conta-
minents introduced during installation.
Note:
Arrow on VXT valve indicates direction of water flow.
LIMITED MANUFACTURER’S WARRANTY
We warrant products manufactured by Hydrolevel Company to
be free from defects in material and workmanship for a period
of two years from the date of manufacture or one year from
the date of installation, whichever occurs first. In the event of
any claim under this warranty or otherwise with respect to our
products which is made within such period, we will, at our
option, repair or replace such products or refund the purchase
price paid to us by you for such products. In no event shall
Hydrolevel Company be liable for any other loss or damage,
whether direct, indirect, incidental or consequential. This war-
ranty is your EXCLUSIVE remedy and shall be IN PLACE OF
any other warranty or guarantee, express or implied, includ-
ing, without limitation, any warranty of MERCHANTABILITY or
fitness for a particular purpose. This warranty may not be
assigned or transferred and any unauthorized transfer or
assignment thereof shall be void and of no force or effect.
SPECIFICATIONS
MAXIMUM FLUID
TEMPERATURE:
150°F
AMBIENT TEMPERATURE:
100°F
FLOW RATE:
1 GPM
MAXIMUM FEED:
10 Gallons (2 Cycles)
ELECTRICAL:
120 VAC, 60 HZ
126 Bailey Road • North Haven, CT 06473 • Phone: (203) 776-0473 • FAX: (203) 764-1711 •
www.hydrolevel.com
•
UNIVERSAL COMPATIBILITY:
The VXT feeder can be used with virtually
any probe or float-type low water cut-off.
•
FEED COUNTER:
Brightly illuminated feed cycle counter displays the
amount of water added to the boiler – essential in diagnosing water loss
problems that can severely shorten the life of a steam boiler. Built-in mem-
ory prevents power interruptions from clearing the counter.
•
PROGRAMMABLE FEED DELAY SETTINGS:
Helps prevent flooded boilers.
Allows time for condensate to return to the boiler before starting feed
cycle – ensuring that additional water is needed.
•
PROGRAMMABLE FEED AMOUNT SETTINGS:
Six settings provide two
ways to feed: 1-5 gallon settings feed
above
the Low Water Cut-Off to
restore boiler’s normal operating level. Or, select LWCO setting to end the
feed cycle when the Low Water Cut-Off re-energizes the burner.
•
UNDERFEED PROTECTION:
If one feed cycle is not sufficient to restore
boiler operation, the VXT will delay and feed one additional cycle.
•
LOCKOUT FLOOD PROTECTION:
The VXT locks-out to prevent steam sys-
tem flooding and costly water damage if burner operation does not
resume after two consecutive feed cycles.
Step 1
Warning
Step 2
Plumbing