Programmable
Water Feeder for
Steam Boilers

120 VAC Operating Voltage

U.S. Patent No. 6,688,329

INSTALLATION

Model VXT-120

WARNING

– To

prevent electrical
shock or equipment
damage, power
must be off during
installation or ser-
vicing of the con-
trol. To prevent

serious burns, the boiler should be thoroughly cooled
before installing or servicing control. Only qualified
personnel may install or service the control in accor-
dance with local codes and ordinances. Read instruc-
tions completely before proceeding.

Feeder must be installed with a manual by-pass. Use isolation valves and
unions to allow easy removal for service or replacement. Remove and
clean the feed valve strainer after the first feed cycle to remove any conta-
minents introduced during installation.

Note: 

Arrow on VXT valve indicates direction of water flow.

LIMITED MANUFACTURER’S WARRANTY

We warrant products manufactured by Hydrolevel Company to
be free from defects in material and workmanship for a period
of  two  years  from  the  date  of  manufacture  or  one  year  from
the date of installation, whichever occurs first. In the event of
any claim under this warranty or otherwise with respect to our
products  which  is  made  within  such  period,  we  will,  at  our
option, repair or replace such products or refund the purchase
price  paid  to  us  by  you  for  such  products.  In  no  event  shall

Hydrolevel  Company  be  liable  for  any  other  loss  or  damage,
whether direct, indirect, incidental or consequential. This war-
ranty  is  your  EXCLUSIVE  remedy  and  shall  be  IN  PLACE  OF
any  other  warranty  or  guarantee,  express  or  implied,  includ-
ing, without limitation, any warranty of MERCHANTABILITY or
fitness  for  a  particular  purpose.  This  warranty  may  not  be
assigned  or  transferred  and  any  unauthorized  transfer  or
assignment thereof shall be void and of no force or effect.

SPECIFICATIONS

MAXIMUM FLUID 
TEMPERATURE:

150°F

AMBIENT TEMPERATURE:

100°F

FLOW RATE:

1 GPM

MAXIMUM FEED:

10 Gallons (2 Cycles)

ELECTRICAL:

120 VAC, 60 HZ

126 Bailey Road • North  Haven, CT 06473 • Phone: (203) 776-0473 • FAX: (203) 764-1711 • 

www.hydrolevel.com

• 

UNIVERSAL COMPATIBILITY:

The VXT feeder can be used with virtually

any probe or float-type low water cut-off.

• 

FEED COUNTER: 

Brightly illuminated feed cycle counter displays the

amount of water added to the boiler – essential in diagnosing water loss
problems that can severely shorten the life of a steam boiler. Built-in mem-
ory prevents power interruptions from clearing the counter.

• 

PROGRAMMABLE FEED DELAY SETTINGS: 

Helps prevent flooded boilers.

Allows time for condensate to return to the boiler before starting feed
cycle – ensuring that additional water is needed.

• 

PROGRAMMABLE FEED AMOUNT SETTINGS: 

Six settings provide two

ways to feed: 1-5 gallon settings feed 

above 

the Low Water Cut-Off to

restore boiler’s normal operating level. Or, select LWCO setting to end the
feed cycle when the Low Water Cut-Off re-energizes the burner.

• 

UNDERFEED PROTECTION: 

If one feed cycle is not sufficient to restore

boiler operation, the VXT will delay and feed one additional cycle.

• 

LOCKOUT FLOOD PROTECTION: 

The VXT locks-out to prevent steam sys-

tem flooding and costly water damage if burner operation does not
resume after two consecutive feed cycles.

Step 1  

Warning

Step 2  

Plumbing