HC7000v2 Utility Pump Switch
with Automatic Turn On/Off, Hi-Lo Dual Sensors and Built-in Alarms
Overview:
The HydroCheck
HC7000v2 Electronic Utility Pump Switch with Automatic Turn On/Off, Hi-Lo Dual Sensors and Built-in Alarms
automat-
ically controls the on/off function of any utility pump and only runs the pump when water is present. To ensure maximum water removal, an addi-
tional run time can be programmed using the Smart Button that begins once the water has dropped below the Lo-Sensor. See the Troubleshoot-
ing section for Smart Button, LED and Alarm specifications. Not rated for outdoor use.
READ PRIOR TO INSTALLATION (How It Works):
The HC7000v2 is designed with an
Additional Run Time
feature that can be programmed using the Smart Button. This feature helps to ensure
that the utility pump has pumped to its lowest possible depth by allowing it to run for a designated amount of time after the water has dropped
below the lo-sensor. The complete operation works as follows:
1.
When both the Hi-Sensor and the Lo-Sensor are detecting water, the HC7000v2 turns on the pump and operates in Hi-Lo Mode where
the sensor positions determine how long the pump runs for.
2.
When the water level drops below the Lo-Sensor, the HC7000v2 switches to Timed Mode, where the pump is run for an Additional Run
Time as programmed using the Smart Button.
3.
When the Additional Run Time expires, the HC7000v2 turns the pump off, and waits for the next cycle to begin.
Step-by-Step Installation
Additional Run Time Adjustment
Step 1:
Plug the
control module
(A) into a 3-prong 120 VAC outlet.
NOTE:
The output will turn on briefly and the LED will illuminate red.
Step 2:
Plug the
utility
pump power cord
(B) into the
control module
(A).
NOTE:
The HC7000v2’s output is rated for a maximum of 1 HP and/or
15 Amps at 120 VAC.
Step 3:
Using a provided
tie wrap
(C), secure
either
one of the s
ensors
direct-
ly to the
utility pump
(D) where the pump is intended to turn on. This
is the
Hi-Sensor
(E).
Step 4:
Using the other provided
tie wrap
(C), secure the second s
ensor
di-
rectly to the
utility pump
(D) so that the tip of the sensor is positioned
just above the pump’s lowest pumping capability*. This is the
Lo-Sen-
sor
(F).
*
Refer to the pump’s manual for the exact minimum water level specifi-
cations.
Step 5:
Adjust the
Additional Run Time
by following the
Run Time Adjust-
ment
steps on Page 2.
NOTE:
This product defaults to a 5 second Additional Run Time and
can be reprogrammed at anytime. See
Read Prior to Installation (How
It Works)
above for more information about this feature.
Step 6:
TEST YOUR INSTALLATION BEFORE LEAVING IT FOR UNAT-
TENDED USE.
NOTE:
This product will not work if tested in a cup of water. See the
Product FAQ page on our website for more information.
Step 1
Mute any active alarms. There should be no audible alarms when pro-
gramming the
Run Time Adjustment
. (See “Alarm Operation” below
for more information about muting alarms).
Step 2
Press and hold the
Smart Button
for approximately 5 seconds, or until
the output turns on and the light starts to flash green. The output turn-
ing on marks the start of the
Additional Run Time
.
NOTE:
If the pump is in the middle of a cycle, first cancel the cycle by
pressing and releasing the Smart Button.
1
Rev-A
www.hydrocheckproducts.com | [email protected] | 1(877)-225-2124
A. Control Module
D. Utility Pump
B. Pump Power Cord
E. Hi-Sensor
C. Tie Wrap
F. Lo-Sensor
Installation Key
Product Specifications
Product Dimensions
2.8 x 2.5 x 3.5 in
Weight
14.4 oz
Output Rating
120 VAC, 15 Amp, 1 HP
Alarm Rating
80 dB
Power
120 VAC, 60 Hz
Sensor Cable Length 12 ft
Anti-Airlock Cycle
2 Attempts