background image

SWIMMING POOL HEAT PUMP UNIT

Installation & Instruction Manual

Summary of Contents for PV 13

Page 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual ...

Page 2: ......

Page 3: ... Heat Pumps Electrical Wiring 3 6 Initial start up of the Unit 4 4 1 4 2 4 3 4 4 5 Maintenance and Inspection 6 Appendix Installation illustration Swimming Pool Heat Pumps Location Interface display Key and icon function instruction Startup shutdown Mode switch Caution Warning Operation and use 14 4 5 Temperature setting 15 4 6 Clock setting 17 4 7 Silent setting 18 4 8 Keyboard lock 18 4 9 Fault ...

Page 4: ...type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics 1 Durable The heat exchanger is made of PVC Titanium tube which can withstand prolonged exposure to swimming pool water 2 Installation flexibility The unit can be installed outdoors 3 Quiet operation The unit comprises an efficient rotary scroll compressor and a low ...

Page 5: ...pliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Appliance shall be installed operated and stored in a room with a floor area larger than 30 m2 Be aware that refrigerants may not contain an odour The installation of pipe work shall be kept to a minimum 30 m2 Spa...

Page 6: ...separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs This product is compliant with directive 2002 95 EC RoHs concerning restrictions for the use of harmful substances in electric and electronic devices 7 The unit CANNOT be installed near the flammable ...

Page 7: ...OP Power Supply Compressor Quantity Compressor Fan Number Fan Power Input Fan Rotate Speed Fan Direction Noise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Ship Dimensions L W H Net Weight Shipping Weight kW Btu h kW kW Btu h kW W RPM dB A mm 3 m h kPa mm mm kg kg PV 17 3 600 16 50 12240 56100 0 2600 2 740 13 8 6 02 1 940 12 30 6596 41820 0 3000 2 680 6...

Page 8: ...Power Supply Compressor Quantity Compressor Fan Number Fan Power Input Fan Rotate Speed Fan Direction Noise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Ship Dimensions L W H Net Weight Shipping Weight kW Btu h kW kW Btu h kW W RPM dB A mm 3 m h kPa mm mm kg kg PV 24 PV 21 6 100 20 70 6 730 23 600 20740 70380 22882 80240 0 4800 3 160 0 4500 3 620 12 7 6...

Page 9: ...ming Pool Heat Pump Unit 2 SPECIFICATIONS Mod Model PV 21 PV 24 el PV 13 PV 17 unit mm unit mm 6 1090 690 690 470 740 5 water o tlet u 0 465 0 wa 5 ter inlet 97 5 925 600 600 385 650 5 water o tlet u 0 430 0 wa 5 ter inlet 107 5 ...

Page 10: ...provided by users or the installer Attention Please follow these steps when using for the first time 1 Open valve and charge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary that the water in pipe is higher than the pool surface Chlorinator cell Water outlet Pool Valve Water supply Water inlet Water pump San...

Page 11: ...s source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 2 Swimming Pool Heat Pumps Location Normally the pool heat pump is installed within 7 5 metres of the pool The longer the distance from the pool the greater the heat loss from the piping For the most part the piping is buried Therefore the heat loss is minimal for runs of up to15 meters 15 meters to and from...

Page 12: ... the basepan and drain out through the barbed plastic condensation drain fitting on the side of the basepan This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand and run to a suitable drain It is easy to mistake the condensation for a water leak inside the unit NB Aquick way to verify that the water is condensation is to shut off the unit and keep the pool pump ...

Page 13: ...s your pool pump is running when the pool temperature drops more than 0 2 below set temperature Time Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect control circuit components and to eliminate restart cycling and contactor chatter This time delay will automatically restart the unit approximately 3 minutes after each control circuit interruption Eve...

Page 14: ... used to enter or exit the silent mode with one click 4 2 Key and icon function instruction Key symbols It is used to switch the unit mode temperature setting and parameter setting It is used to carry out startup shutdown cancel current operation and return to the last level of operation It is used to page up and increase variable value It is used to page down and decrease variable value It is use...

Page 15: ... unit It will display when compressor is started It will display when water pump is started It will display when fan is started When the timing silent function is started it keeps bright for a long time It will flash when work on silent state else it is off It will display after the user sets the timing and multiple timing intervals can be set When the axillary display area displays the water outl...

Page 16: ...own the wire controller will display as follows Operations are the same as under ON OFF main interface 4 4 Mode switch Under the main interface Short press to switch the unit among heating cooling and automatic mode When there is no operation within 1 minute it will display with half screen off Notes Startup shutdown operation can only be conducted in the main interface When it displays with half ...

Page 17: ...e unit is under the defrosting state the defrosting symbol is on with the display interface as follows Notes 1 After completing the defrosting the unit will be automatically switched to the heating automatic mode keeping consistent with the mode before defrosting During the defrosting mode switch is available And when switching the mode the unit won t work under a new mode until defrosting is comp...

Page 18: ...eturn to the main interface Under the clock setting interface Long press for 2 s to enter into the system times setting interface Short press Press or to adjust hour digit Flashing Stort press to enter into the timer setting interface Short press or to circularly display among timer ON1 OFF1 ON2 and OFF2 4 6 2 2 Select or timer setting interface 2Q 2 2 2Q Timer setting interface Flashing Press to ...

Page 19: ...e the change and return to the main interface While enter into the set the Timer ON OFF as below or timer setting interface 2 2 21 21 Take for example ON1 1 Select cancel the Timer ON OFF as below or timer setting interface refers to 6 2 1 2 2 2 1 2 1 Take for example ON1 Note Under the Timer ON OFF setting interface if the timing symbol and entire time digits flash at the same time click to retur...

Page 20: ...ong press of for 2 s Short press or Short press for entering the hour digit setting of timing on silent Short press or Short press for confirming the timing on silent and turn to the setting of timing off silent Short press for entering the hour digit setting of timing off silent Short press or Short press for confirming timing off silent saving the changes and returning to the main interface Shor...

Page 21: ... screen will be lighten after other operations conducted 2 Under the OFF interface locking operation is available and the operation method is the same as locking screen under the ON interface 2 Two or more faults 1 Single fault Short press or Fault code Fault serial number Quantity of fault Short press For example Notes 1 When the silent icon is lighten The timing mute has been set but it s not un...

Page 22: ...ck the pressure switch and cold circuit Check or change the temp Sensor Check the pressure switch and cold circuit check and replace this temp sensor Check whether fan motor is broken or locked or not Inlet Temp Sensor Fault PP Pressure sensor Fault The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is br...

Page 23: ... communication connection Recovery after the 150s Check the measuring voltage check requency conversion board hardware Check whether current return wires connected motor Check and adjust the current measurement Check the input voltage measurement Check the input voltage measurement Check the input voltage measurement Check the input voltage measurement Check and adjust the current measurement Chec...

Page 24: ...ing V R T A B G 12V power No use No use 485A 485B GND power 4 23 5 7 21 1 86 AC L OUT1 OUT2 CN2 CN8 CN13 OUT3 AC N OUT4 OUT5 PC1004 CN9 GND GND GND GND GND GND GND GND GND GND GND GND AI DI12 AI DI11 AI DI10 AI DI09 AI DI08 AI DI07 AI DI06 AI DI05 AI DI04 AI DI03 AI DI02 AI DI01 12V 0 10V_OUT PWM_OUT PWM_IN GND GND GND GND 5V AI DI13 GND GND RS485_B_2 RS485_A_2 12V GND RS485_B_3 RS485_A_3 12V GND ...

Page 25: ...22 Main board of the input and output interface instructions below 4 OPERATION AND USE Sign Meaning Number ...

Page 26: ...23 4 OPERATION AND USE ...

Page 27: ...MOTE CN42 MODE CN30 IT CN30 OT CN30 CT CN30 SUT CN30 AT CN30 ET P00 GND P13 L P14 L R485 RS485 2 CC CN15 Compressor output 220 230VAC Water pump output 220 230VAC 4 way valve output 220 230VAC DC Fan Live wire input 220 230VAC Neutral wire input 220 230VAC Pressure sensor High pressure switch input Low pressure switch input Wat ow switch input Remote switch input Rerserve Water input temperature i...

Page 28: ...operation pressure of the refrigerant system should only be serviced by a certified technician Discharge all water in the water pump and water system so that freezing of the water in the pump or water system does not occur You should discharge the water at the bottom of water pump if the unit will not be used for an extended period of time You should check the unit thoroughly and fill the system w...

Page 29: ...02 95 EC RoHs This product is compliant with directive 2002 95 EC RoHs concerning restrictions for the use of harmful substances in electric and electronic devices 7 The unit CANNOT be installed near the flammable gas Once there is any leakage of the gas fire can be occur 8 Make sure that there is circuit breaker for the unit lack of circuit breaker can lead to electrical shock or fire 9 The heat ...

Page 30: ...ine MCB Creepage protector Signal line 2 h n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm 2 mm 25 2 mm 25 2 35mm 2 50mm 2 70mm 2 95mm 2 Three phase unit 2 3h1 5mm 2 3h2 5mm 2 3h4mm 2 3h6mm 2 3h10mm 2 h16mm 3 2 h25mm 3 2 3h25mm 2 3h35mm 2 3h50mm 2 3h70mm 2 3h95mm 30mA less than 0 1 sec 30m...

Page 31: ...Note ...

Page 32: ...Code ...

Reviews: