30
Problem
Probable Cause(s)
Corrective Action
• Low water
temperature
• Chemical capacity exceeded
• Improper wiring/failed heater.
Fouling of heater surface
• Improper wiring/failed temperature
controller
• Solenoid is stuck open allowing cold
water
• Water circulation pump clogged or
failed
• Lower feed capacity
• Check wiring/replace or clean heater
• Check wiring/replace PID controller
• Close/replace solenoid. If low water
level exists, allow for the water level
to reach set point before making any
changes
• Inspect, clean, replace circulation
pump and piping
• Low water level alarm
• Low water alarm
• Pump shut down and
heater is shut off
• Water level is below operating set
point
• Solenoid failed closed
• Check solenoid for correct operation
• Check level probes for correct
operation
• Check for water leaks
• Overfi ll alarm
• Water overfl owing
through drain
• Water level is above operating set
point
• Solenoid failed open
• Solenoid is stuck open. Clean or
replace
• Replace water level control circuitry
• Electronic PRV is
closed while trying to
chlorinate
• No power to the actuator
• Alarm condition exists
• Actuator failed
• Restore power to unit
• Check operating parameter and adjust
improper conditions
• Inspect and replace actuator
• No cathodic
protection
• Insuffi cient conductivity in water
• Anodes are consumed
• Circuitry improperly connected
• Add ¼ lb. (113 g) sodium sulphate to
water
• Replace anodes
• Check circuitry
• Low superheat
• Design capacity exceeded
• Fouling inside/outside of pressure
chamber
• Low water temperature
• Low water level
• Lower feed rate
• Clean chlorine pressure chamber
• Follow corrective action for low water
temperature and/or low water level
• Corrosion of chlorine
pressure chamber
• Poor cathodic protection
• Moisture in manifold piping
• Check anodes and cathodic protection
system
• Replace chlorine pressure chamber
if weight is more than 10 lb (4.5 g)
lighter than factory weight or if
corrosion anywhere exceeds
1
⁄
8
"
(0.3 cm).
Summary of Contents for VPH-10000-1 Series
Page 1: ...1 Series VPH 10000 1 Vaporizer Instruction and Operation Manual VPH 10000 1 Rev 9 11 19 ...
Page 13: ...13 FIGURE 4A Relay Connections Box ...
Page 14: ...14 FIGURE 4B Signal Connections Box ...
Page 34: ...34 FIGURE 9 Chlorine Vapor Pressure Curve Vapor Pressure ...
Page 35: ...35 FIGURE 10 Sulfur Dioxide Vapor Pressure Curve Vapor Pressure Min Superheat ...
Page 36: ...36 FIGURE 11 Ammonia Vapor Pressure Curve Vapor Pressure Min Superheat ...