Hydreon RG-11 Application Notes Download Page 3

Specifications

Parameter

Value

Input Voltage

9 – 30VDC or
9 – 26 VAC
50V surge
Reverse polarity protected to 50V

Current Drain

15 mA nominal.  (No outputs on, not 
raining, no heater)
about 1.5 mA in micro-power sleep 
mode.
50 mA with output on.
55 mA - With heater on, 24V dc 
input.

Output

Relay closure, Normally Open and 
Normally Closed contacts.  
Max load 1A, 24 VDC.

Operating 
Temperature range

-40 C to +60C

DIP Switches

Set the DIP switches for the application according to the 
table below.  DIP Switch settings below correspond to 
software part number: 45-005-006  (SW 006)

OUT LED--

 The LED in the center of the circuit board turns 

on when NO is on, as an aid to debugging.

Condensation-- 

Generally, the RG-11 will sense 

condensation as if it were rainfall, but this seldom amounts 
to a significant accumulation of water.

Ambient Light Interference--  

The RG-11 is almost 

completely  immune to the effects of ambient light, and may 
freely be mounted in direct sunlight.

Heater Notes--

 A built-in low power (0.25W) heater extends 

operation of the device to freezing (32 F or 0C).  Note that 
this is a very modest amount of power; it will tend to drive 
off a modest amount of frost, but will not melt ice.

Mode 4: Irrigation Control

Rain Gage output on means inhibit watering. 

Switch

Behavior

7 6 5 4 3 2 1

1 0 X X 0 0 0 Typical Water Control.  Inhibit watering for 

up to 5 days.

0 0 1 Water More

0 1 0 Water a lot more

1 0 0 Water Less

1 0 1 Water a lot less

0 X X X Inhibit irrigation during a storm

1

Allow irrigation during a storm

0 X X X X Inhibit irrigation during freeze

1

Allow irrigation during freeze

In the table above, 1 = Switch on, 0 = Switch off, X = 
switch in either position.

The RG-11 may be set to provide precise control of an 
irrigation system.   Typically, the installation will connect to 
the COM and NC relay contacts to interrupt the valves when 
watering should be inhibited.  Note that the RG-11 also 
requires 24 VAC (or other suitable supply.)

 The nominal irrigation profile is set so that the ground 
receives an inch of water per week.  It will  inhibit watering 
upon the accumulation of 0.2 inches of water, and re-enable 
the system after that water has evaporated.  This can be as 
short as less than a day, or as long as six days, depending 
on rainfall.  Additional DIP switch settings are provided for 
allowing more or less watering, as shown in the table.

Nominally (Switch 4 off), the RG-11 will inhibit watering 
during a storm, even if not much water has accumulated. 
The reasoning is that if it is raining hard now, the rainfall is 
likely to deliver enough accumulation to justify inhibiting at 
least the current cycle of watering.  This prevents the “it's 
pouring, but my sprinklers are still running” objection from 
the customer, and the accompanying excessive runoff and 
muddy ground.  The feature may be defeated by turning 
switch 4 on.

Normally, the RG-11 will inhibit irrigation if the temperature 
drops below freezing, or nominally about 34 degrees.   If 
SW 5 is on, the RG-11 will allow irrigation below 34 
degrees.  Micro-power mode is disabled in irrigation control.

Reviews: