Connect network connection (Ethernet)
FAM 5
en-US
Page 85 / 148
BEWA FAM5 4166129a en-us 2019-03-04.docx
2019-03-04
Modifying the network settings
NOTICE
Error while modifying the network address
Function faults in unit
►
Adhere to the specified sequence of the input without fail.
►
Note the entered IP addresses.
The PLC components
-LOGO! SPS (A1), Factory setting: IP192.168.0.30
-Control panel LOGO! TDE (A3), Factory setting: IP 192.168.0.31
have an individual IP address for internal communication. These IP
addresses must be freely available in the network or approved.
The network settings may only be modified for standard FAM units
with a maximum of two SPS components with LAN interface.
Consult the HYDAC service in case of any doubt.
The menu structure is displayed in chapter "Menu structure of the LOGO!
control panel TDE" on page 48.
Proceed as follows for modifying the network settings:
1.
Press the arrow key ▼ in FAM Home – Start menu. The display switches
to the start menu of the control panel.
2. Press the "ESC" key. The display switches to LOGO! TDE main menu.
3. Change the access level to the status Administrator:
LOGO! Settings ->
Settings -> Switch to ADMIN -> ADMIN Password : LOGO
4. Switch to the PLC operating state STOP:
LOGO! Settings -> STOP ->
YES
5. Modify the network settings of LOGO! PLC:
LOGO! Settings -> Network
a. Factory settings gateway 192.168.01
b. Factory settings subnet mask 255.255.255.0
c. Factory setting IP address 192.168.0.30
6. Change the IP address of the control panel (TDE):
TDE Settings -> TDE
Network
a. Factory settings gateway 192.168.01
b. Factory settings subnet mask 255.255.255.0