Connecting the FAM
FAM 15-70 ATEX
en
Page 30 /
88
BEWA FAM-15-70 II 2G IIB+H2 T4 EX02 4510066 en-us 2020-01-24.docx
2020-01-24
Connecting the FAM
All hoses on the FAM must be sufficiently conductive to properly
discharge electrostatic charge buildup.
If hoses are used, the ohmic resistance between the fittings
—in
this case between the FAM and the tank
—may not exceed a limit
value depending on the respective hose type.
Identification of hose with the symbol
"M"
:
Limit value ≤10
2
Identification of hose with the symbol
"
"
:
Limit value ≤10
6
The hose connection must ensure a highly conductive transition
between the hose and FAM tube, as well as between the hose
and tank tube.
If this is not the case, all conducting parts (such as the metal
mouth piece at the end of the hose) are to be grounded
separately.
Connecting conductive hoses with fittings to hose tubes requires
marking and checking per DIN EN 12 115.
Connect the ground clamp of the FAM to a suitable grounding
source nearby. The grounding lead is 3 m long.