8
ETS
300
Status: 29.01.2014
HYDAC ELECTRONIC GMBH
Part No.: 669651 E
7.2
ANALOGUE OUTPUT
Depending on the model, the ETS 300 has one analogue output with a 4 .. 20 mA signal.
7.3
SETTING THE SWITCHING POINTS, HYSTERESES AND/OR SWITCHING VALUES
FOR THE WINDOW FUNCTION
•
Press "
mode
" key
•
"
S.P.1
" or "
hi.1
" is displayed
•
Keep pressing the "mode" key until the required parameter is displayed (depending on the
basic setting: "
S.P.1
", "
h.Y.1
", "
S.P.2
", "
h.Y.2
", "
hi.1
", "
Lo.1
", "
hi.2
" or "
Lo.2
").
•
After 2 seconds the actual setting flashes.
•
Use the
▼
or
▲
the keys to alter the setting.
•
Use the "
mode
" key to call up other parameters, if required, and alter the setting
•
using the
▼
and the
▲
keys.
•
If no keys are pressed for 3 seconds, the display changes back and the settings are saved.
NOTE
:
•
If
"
LOC
" appears in the display when trying to alter the settings, programming is
disabled.
Action
: set programming enable to "
ON
"
(see point 9 "Programming enable")
•
If the or the key is held down during alteration, the value automatically advances.
•
If a setting has been altered, "
PRG
" appears briefly in the display when the display is
switched over. The new setting is then saved in the unit.