The
OCPP
Configuration window allows for the following settings:
•
OCPP type
: select the OCPP mode for the gateway
o
BMS Central System:
Gateway and BMS act as an OCPP Central System
o
External Central System
: Gateway acts as a bridge between an external OCPP CS and OCPP
chargers
▪
IP:
The IP of the external OCPP CS
▪
Port:
The port of the external OCPP CS
▪
Check connection
. Press this button to stablish a test connection between the gateway and
the External Central System.
•
OCPP Scan.
Press this button to search for OCPP Chargers in your network. Scan function will generate a
list of all chargers that are trying to connect with the gateway.
– Note that chargers must be configured first
to connect to the gateway before they can be discovered with the Scan tool. For more information, please
review the
Intesis Configuration Guide
.
Fig 4.5
Scan OCPP network functionality
•
Chargers Configuration:
A list of all available chargers with its corresponding Charger Id and number of
connectors. Activating each Charger will change the Signals available in Signals tab. Keep in mind the
different capacities for each gateway model.
o
Heartbeat interval:
Changes the Heartbeat interval time for OCPP messages
•
TCP Configuration port:
Sets the TCP port for the OCPP communication with the OCPP Chargers
•
TCP Keep Alive:
Sets the time of inactivity to send a Keep Alive message (0-disabled)