Poseidon 2250 – Short Manual 

HW group 

 

 

 

www.HW-group.com 

 

 

1 / 54

 

 

 
 
 

Poseidon 2250 

 

Short Manual

 

 

 

  

 

 

 

Summary of Contents for Poseidon 2250

Page 1: ...Poseidon 2250 Short Manual HW group www HW group com 1 54 Poseidon 2250 Short Manual...

Page 2: ...following safety and maintenance instructions In particular the device must not be used under any of the following conditions The device is noticeably damaged The device does not function properly Unf...

Page 3: ...llowed DIP4 Off 1 4 Connect the unit to the Ethernet with a patch cable to a switch cross over cable to a PC 1 2 Plug the power adapter to a mains outlet 230 110V and connect it to the Poseidon 12V po...

Page 4: ...s for devices on your local network Individual Poseidon units are identified by their MAC addresses printed on the label at the bottom side of the unit Double click a MAC address to open a basic confi...

Page 5: ...ucture are in the manual Modbus TCP description of the structure is in the manual or in application examples Standard port 502 is open for reading by default Unique sensor ID serial number Overview of...

Page 6: ...ied CD Poseidon install_flash_player_7 msi or download the latest version from the Internet Flash Setup allows you to Set sensor names and corresponding alarm thresholds safe range Select units for di...

Page 7: ...wering up the Poseidon the connector must click in Sensors can be daisy chained Maximum distance is 30m Sensors can be also connected using a star topology with the T Box TBox2 hub In this case the ma...

Page 8: ...z or a number 65 122 The numbers correspond to the ASCII codes of the letters A 65 Z 90 a 97 z 122 For details about address configuration see the sensor manual If you change the sensor topology the s...

Page 9: ...s HTTP XML direct access to the unit E MAIL Pop3 download data from the email Poseidon unit have to send email first Note Search Devices find only local network devices You can add remote devices on p...

Page 10: ...ata to MS Excel click to Add Report check which sensors do you want to have in Excel and click to Save Preview It call your MS Excel Enable marcos and you get data to the first sheet Report Data can b...

Page 11: ...s as well as set an output high or low CapTemp CapTemp and MonTemp is a pair of utilities to monitor production processes The programs can supervise all sensors from HW group temperature and humidity...

Page 12: ...ritten over calibrator utility a menu invoked by a right click or by XML Programmers can use EX104 in the HWg SDK Calibration examples Calibration value 3 sensor measures 0 5 C Poseidon shows 3 5 C Ca...

Page 13: ...public online demo 999 9 can sometimes appear even though the sensor works properly This is due to limited computing performance of the unit Try to reduce the load Units are assigned to values automat...

Page 14: ...of 5 C the alarm raised at point 8 would end at point 9 With the hysteresis function the alarm continues until the temperature rises above the tolerance band point 10 that is 5 C 15 C 10 C Hysteresis...

Page 15: ...factory defaults Toggling DIP1 3x down and up right after powering up the unit erases all settings including passwords configuration can be backed up with UDP Config RS 232 Sensor configuration and in...

Page 16: ...ire special cable Rxd TxD and GND only Outputs 2 additional outputs 1 0 RTS 10V 10V DTR 10V 0V Port 4 Dry Contact Inputs Contact inputs 3 digital inputs accept NO NC dry contacts Input type One common...

Page 17: ...Poseidon 2250 Short Manual HW group www HW group com 17 54 Mechanical dimensions Wall mount L bracket...

Page 18: ...ifying the device It is printed on the label at the bottom side of the unit It consists of six hexadecimal number pairs the first three pairs are always 00 0A 59 With the MAC address you can distingui...

Page 19: ...o settings can be changed TCP Setup at port 99 by default is not available No parameters can be changed over SNMP LED indicators LEDs indicate the current mode power being supplied Ethernet activity a...

Page 20: ...ing the RTS and DTR outputs Port 3 complies with the RS 232 specification If needed the P1250 RC converter designed for connecting two 12VDC rated relays to Poseidon 1250 over RS 232 can be used to co...

Page 21: ...ct without external voltage Per input alarm settings Alarm activation and state 0 1 configured over WWW Poseidon Flash setup o Alarm inactive o Alarm when the contact is opened or closed o Alarm whene...

Page 22: ...umber of sensors on the bus Up to 10 sensors Power to sensors 5V 50mA available at the RJ12 jack Sensor power consumption Power supplied over the bus is sufficient for all connected sensors Communicat...

Page 23: ...Poseidon 2250 Short Manual HW group www HW group com 23 54 Examples of 1W bus connections...

Page 24: ...The Spider unit connects to the Poseidon over the Industrial bus RS 485 Up to four 1W bus sensors temperature humidity dry contacts can be connected to the Spider unit Each sensor is connected to a se...

Page 25: ...added to power more sensors Communication cable UTP in some cases 4 wire phone cable Alarm settings Checking the reading against its Safe Range configuration in Poseidon Flash setup Polling period 800...

Page 26: ...the current consumption of the sensors Note A disadvantage is that it is necessary to have a wiring topology with a single beginning and a single terminated end as opposed to the popular star topolog...

Page 27: ...in Sensors connected with this table must not terminate the RS 485 bus Sensor RJ45 LAST cable RS 485 cable 0 5m RJ45 4 pins Connects 4 terminals A B to a RJ45 modular jack 2 pairs only This cable is u...

Page 28: ...o connect four 1W bus 1 Wire sensors to the Industrial bus RS 485 Each 1W bus sensor connects to a separate connector to enable a greater distance up to 1000 meters as defined by the Industrial bus sp...

Page 29: ...akes it possible to connect sensors in a star topology sensors must be connected using TP cables Simpler and faster connection of sensors Makes expanding an installation easier Simplifies supplying po...

Page 30: ...sed to connect three Temp 1Wire 10m temperature sensors and one door contact the contact is connected to the blue pair of the RJ45 Temp 485 and HTemp 485 sensors are connected to S Hub connectors 1 th...

Page 31: ...ary communication interface that invokes other links and the Flash setup Flash setup Detailed user interface for configuring all features of the device Telnet setup Configuration of special features t...

Page 32: ...ess and communication port is displayed after a device is found Compatible with all HW group products Poseidon Damocles PortBox PortStore I O Controller IP relay and other product lines Windows and Li...

Page 33: ...www HW group com 33 54 WEB interface The Web interface shows an overview of the device status Configuration takes place in Flash Setup The main page with the overview of sensor and input readings aut...

Page 34: ...n alarm Red Input is in alarm Sensors The Sensors table displays information valid at the time of the last refresh about detected and activated sensors including their states Name Textual name of the...

Page 35: ...L definition file for values xml right click the link and select Save Target as to save the file to disk Text and link For more information try www HW group com Customizable link to the supplier or se...

Page 36: ...to be installed on your PC If the PC is connected to the Internet the plug in is downloaded automatically Alternatively you can install the plug in from the supplied CD Poseidon install_flash_player_...

Page 37: ...Poseidon 2250 Short Manual HW group www HW group com 37 54 Flash menu General Setup Device name Important for sending e mail and synchronizing time...

Page 38: ...Poseidon 2250 Short Manual HW group www HW group com 38 54 Flash menu SNMP...

Page 39: ...Short Manual HW group www HW group com 39 54 Flash menu Email SMS Test whether your e mail setup works String inserted to the subject of every e mail Log file with values is sent every few hours to t...

Page 40: ...anual HW group www HW group com 40 54 Flash menu Log Time Interval for logging sensor readings Log file with values is e mailed every X hours Periodical email every XX minutes Remind alarm status by e...

Page 41: ...cording to location and function Every e mail contains this name Unique sensor ID Enables sending e mail or SMS or SNMP Trap because of this sensor When out of this range e mail or SMS is sent Automat...

Page 42: ...Poseidon 2250 Short Manual HW group www HW group com 42 54 Flash Menu Inputs Outputs...

Page 43: ...on timeout With Communication Monitor you can send email when central monitoring system stop polling the device Communication Monitor can help you indicate by output when network connectivity failure...

Page 44: ...irmware over the Web Upload the firmware in a hwg file over http to http x x x x upload Connection problems etc must be avoided during file transfer If the update fails upload the firmware over RS 232...

Page 45: ...group www HW group com 45 54 T Box2 600 280 T Box RJ11 600 356 B Cable 600 044 Poseidon S Hub 600 041 T Box2 600 280 GSM Modemcom G10 600 312 Spider 600 273 12V power adapter 3pin ATX 600 079 Sensors...

Page 46: ...steel silicon cable Temp 1Wire Rack19 600 329 19 Rack Cabinet HTemp 1Wire Box2 600 344 Indoor Temp 1Wire Flat 3m 600 337 Fridge probe IP67 stainless steel flat cable HTemp 1Wire Rack19 600 330 19 Rack...

Page 47: ...external PT100 sensor Temp 485 Pt100 Box 600 113 Outdoor IP67 Temp 485 Pt100 Cable2 600150 Boxed converter for an external PT100 sensor HWg HTemp 485 T3411 600 368 Indoor HWg HTemp 485 T3419 600 369...

Page 48: ...eidon Use a T Box T Box2 hub Daisy chain the sensors if they have two RJ11 jacks Maximum total wiring length is 10 30m Industrial bus RS 485 RJ45 Several sensors with a single Poseidon Use an S Hub Da...

Page 49: ...onverter or use an S Hub unit Maximum wiring length is 1000m An address must be assigned to each sensor if the factory preset addresses are in conflict For details see the TCP Setup chapter section Co...

Page 50: ...See the sensor documentation for details Special accessories 2x L profile A size 600 023 2x sidewise L brackets for wall mounting See the Poseidon housing drawing for mechanical dimensions DB9 Prolong...

Page 51: ...a Set Ready 7 RTS Request to Send 8 CTS Clear to Send 9 Not used Port 1 RJ12 1 5V Power 2 Not used 3 Data Transmit Data 4 GND Ground 5 5V Power 6 Not used Port 1 RJ45 1 Not used 2 Not used 3 485 B bac...

Page 52: ...properties diameter When connecting a Pt100 using two wires only connect the third terminal locally Addresses of Temp 485 sensors with Pt100 elements When shipped the configured sensor address is in...

Page 53: ...X X X O X B X O O X O M O O X X X X X X X O O C X O O O X N O O X X O Y X X O X X D X O O O O O O O X O X Z X X O X O E O X X X X P O O X O O Adr by SETUP X X O O X F O X X X O Q O O O X X Adr by SET...

Page 54: ...oup www HW group com 54 54 Connecting supplied accessories Connecting the optical smoke detector The relay output connects to the dry contact inputs Power can be supplied with any polarity Power can b...