17
If the results need to be printed out, you need to press "ENT".
It is shown in Figure 10.
⑦
In the boot screen, pressing the "ESC" then 40 sets of
historical data could be checked.
VI. Connection
Proper connection method should be selected in accordance
with the grounding of tested equipment.
1. P(Positive connection)
If the low-voltage measuring terminal or secondary port of
equipment under test is ground insulated, positive connection
should be adopted.
The red special high-voltage cable should be led out from the
HVx which is on the back of the instrument; the high-voltage
shielded cable should be connected with the high-voltage terminal
of equipment under test.
The black special low-voltage cable should be led out from Cx
which is on the panel of instrument; the low-voltage core should be
connected to the low-voltage terminal L of equipment under test
(see Figure 11). The low-voltage shielded cable should be
connected to the shielding terminal E of equipment under test. (If
shielding terminal is unavailable, then it could be vacant)