13
4. Turn power supply on
Turn power supply on, the indicator light above it will glow, “kV” voltage
meter display 0.00kV.
5. Test start
Press the "high voltage control" button, and the high voltage will be output
from the + terminal. The "kV" meter will display the voltage value b -.
Press the "timing switch" and the "timing" meter will start timing.
6. Test power adjustment
Adjust the "high voltage adjustment" knob to smoothly adjust the voltage
to the specified value
7. Resistance range selection
Adjust the range switch to select the desired range. If the meter
continuously give an alarm indicating the measured resistance is too low,
please adjust to low range for measuring.
8. Reading resistance value
Read the resistance value through the "MΩ / GΩ" meter. After the
resistance value is stable, press the "timing switch" stopwatch to report the
time in 15 seconds, 60 seconds and every 60 seconds after the high-voltage
output for the convenience of the operator to record.The formula of
absorptance and polarization index as follows:
absorptance = R60S/R15S-- resistance reading of the 60
th
seconds ÷
resistance reading of the 15
th
seconds.
Polarization Index = R10min/R1min-- resistance reading of the 10
th
minutes ÷ resistance readings of the 1
st
second.
9. Exit test power
Press “push to test” to exit test power, at this time “KV” display will slowly
return to zero and the stopwatch will display exit.
10. End
When the “kV” display screen shows 0.00kV, then the measured target
has completed discharge via the manual discharging rod, you can turn power