HUW1
Series Intelligent Universal Circuit Breaker
5
5.2
Power consumption
Shell frame
current (A)
Rated current
(A)
Power consumption (W)
3P, drawer mode
4P, drawer mode
3P, fixed mode
4P, fixed mode
1,000
200
8
11
4
6
400
35
47
18
24
630
81
104
45
60
800
96
128
48
64
1,000
144
192
85
114
2,000
630
42
56
24
32
800
67
90
38
51
1,000
75
100
45
60
1,250
117
156
70
94
1,600
192
256
115
154
2,000
276
368
156
208
3,200
2,000
276
368
156
208
2,500
375
500
188
250
2,900
454
606
252
336
3,200
553
737
307
410
4,000
2,500
400
550
268
350
2,900
510
680
275
380
3,200
598
790
300
400
4,000
660
880
332
450
6,300
4,000
576
768
-
-
5,000
900
1,200
-
-
6,300
1,429
1,905
-
-
Note: The power consumption of the circuit breaker refers to the power consumption of the main circuit measured by the
rated current of the circuit breaker at normal temperature, excluding the power of other accessories with the power
consumption of the circuit breaker. The data in this table is for users' selection reference only, and cannot be seen as the
circuit breaker’s actual power consumption when in use.
5.3
Altitude and derating factor
Altitude (m)
2,000
3,000
4,000
5,000
Derating
factor
of related
items
Working current I
e
1
0.93
0.88
0.82
Short-circuit breaking capacity I
cu
, I
cs
1
0.83
0.71
0.63
Short-circuit withstand capacity I
cw
1
0.83
0.71
0.63
Rated impulse withstand voltage U
imp
1
0.9
0.71
0.63
Power frequency withstand voltage
1
0.9
0.71
0.63
Rated insulation voltage U
i
1
0.83
0.71
0.63