background image

3-2

 

s

tartup

 / o

pEratIon

P/N 3018126_E 

U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • www.hussmann.com

P/N 3018126_E 

3-3

HUSSMANN CORPORATION • BRIDGETON, MO  63044-2483  U.S.A.

SMG8B & SSG8B

XR 75 

Code XR 75 Parameter

XR 75 Function

XR 75 

Default

SSG

SMG

SEt

Temperature Setpoint

LS to US

-5

17

19

Hy

Differential

(0.1 to 25.5°C / 1 to 255°F)Intervention differential for setpoint. Compressor 

Cut IN is  se differential (Hy).Compressor Cut OUT is when the 

temperature reaches the setpoint.

2

9

6

LS

Minimum  setpoint

(-100°C to SEt/-148°F to SEt)Sets the minimum value for the setpoint.

-50

10

12

US

Maximum  setpoint

(SEt to 110°C/ SEt to 230°F)Set the maximum value for the setpoint.

110

33

26

ot

Thermostat probe calibration

(-12.0 to 12.0°C; -120 to 120°F)Allows to adjust possible offset of the 

thermostat probe.

0

0

0

P2P

Evaporator probe presence

n = not present: the defrost stops by time       y = present: the defrost stops 

by temperature

Y

n

n

oE

Evaporator probe calibration

(-12.0 to 12.0°C; -120 to 120°F)Allows to adjust possible offset of the 

evaporator probe.

0

0

0

P3P

Third probe presence (P3)

n = not present; the terminals 18-20 operate as digital input        y = present; 

the terminals 18-20 operate as third probe

n

n

n

o3

Third probe calibration (P3)

(-12.0 to 12.0°C; -120 to 120°F)    Allows to adjust possible offset of the third 

probe.

0

0

0

P4P

Fourth probe presence

(n = not present; y = present)

n

n

n

o4

Fourth probe calibration

(-12.0 to 12.0°C)   Allows to adjust possible offset of the fourth probe.

0

0

0

Ods

Outputs activation delay at startup

(0 to 255 min)  This function is enabled at the initial start up of the device 

and inhibits any output acti-vation for the period of time set in the 

parameter.

0

0

0

Ac

Anti-short cycle delay

(0 to 50 min)    Minimum interval between the compressor stop and the 

following restart.

1

2

2

rtr

Percentage of the second andfirst 

probe for regulation (0 to100; 100 

= P1, 0 = P2 )

Allows to set the regulation according to the percentage of the first and 

second probe,as for the following formula (rtr(P1-P2)/100 + P2).

100

100

100

CCt

Compressor ON time during 

continuous cycle

(0.0 to 24.0 hr; res. 10 min)Allows to set the length of the continuous cycle: 

compressor stays ON without interruption for the CCt time. Can be used, for 

instance, when the room is filled with new products.

0

0

0

CCS

Setpoint for continuous cycle

(-100 to 150°C)Sets the setpoint used during the continuous cycle.

-5

17

19

Con

Compressor ON time with faulty 

probe

(0 to 255 min)Time during which the compressor is active in case of faulty 

thermostat probe. WithCon = 0, compressor is always OFF.

15

6

6

CoF

Compressor OFF time with faulty 

probe

(0 to 255 min)Time during which the compressor is OFF in case of faulty 

thermostat probe. When CoF= 0, compressor is always active.

30

2

2

CF

Temperature measurement unit

°C = Celsius, °F = Fahrenheit, (CAUTION!  When the measurement unit is 

changed, the setpoint and the values of the parameters Hy, LS, US, ot, ALU 

and ALL have to be checked and modified if necessary).

C

F

F

rES

Resolution (for °C)

(in = 1°C; dE = 0.1°C) Allows decimal point display.

dE

dE

dE

Lod

Device display

(P1; P2, P3, P4, SEt, dtr) Selects which probe is displayed by the device: P1 = 

Thermostat probe P2 = Evaporator probe; P3 = Third probe (only for models 

with this option enabled),  P4 = Fourth probe, SEt= setpoint,   dtr = 

percentage of visualization

P1

P1

P1

Red

X- REP display (optional)

(P1; P2, P3, P4, SEt, dtr) Selects which probe is displayed by the device: P1 = 

Thermostat probe P2 = Evaporator probe; P3 = Third probe (only for models 

with this option enabled),  P4 = Fourth probe, SEt= setpoint,   dtr = 

percentage of visualization

P1

P1

P1

dLy

Display delay

(0 to 20.0 min; resul. 10 seconds)  When the temperature increases, the 

display is updated of 1°C/1°F after this time.

0

0

0

dtr

Percentage of the second and first 

probe for visualization when Lod = 

dtr (0 to 100; 100 = P1, 0 = P2 )

If Lod = dtr, it allows to set the visualization according to the percentage of 

the first and second probe, as for the following formula (dtr(P1-P2)/100 + P2).

50

100

100

EdF

Defrost mode (only for controller 

with RTC)

rtC = Real Time Clock mode. Defrost time follows Ld1 to Ld6 parameters on 

workdays and Sd1 to Sd6 on holidays. in = interval mode. The defrost starts 

when the time Idf is expired.

rtC

in

in

tdF

Defrost type

EL = electrical heater  in = hot gas

EL

EL

EL

dFP

Probe selection for defrost 

termination

nP = no probe  P1 = thermostat probe  P2 = evaporator probe  P3 = 

configurable probe  P4 = probe on Hot Key plug

P2

P1

P1

dtE

Defrost termination temperature

(-50 to 50°C/ -58 to 122°F) (Enabled only when EdF = Pb) Sets the temperature 

measured by the evaporator probe, which causes the end of defrost.

8

48

48

IdF

Interval between defrost cycles

(0 to 120 hr) Determines the time interval between the beginning of two 

defrost cycles.

6

24

24

MdF

(Maximum) length for defrost

(0 to 255 min)  When P2P = n, (not evaporator probe: timed defrost) it sets 

the defrost duration, when P2P = y (defrost end based on temperature) it sets 

the maximum length for defrost.

30

90

90

dSd

Start defrost delay

(0 to 99 min)  This is useful when different defrost start times are necessary 

to avoid overloading the plant.

0

0

0

dFd

Temperature displayed during 

defrost

(rt = real temperature; it = temperature at defrost start; SEt =  setpoint; dEF = 

dEF la-bel)

it

Def

Def

dAd

MAX display delay after de-frost

(0 to 255 min)Sets the maximum time between the end of defrost and the 

restarting of the real roomtemperature display.

30

30

30

Fdt

Drip time

(0 to 120 min)Time interval between reaching defrost termination 

temperature and the restoring of thecontrollers normal operation. This time 

allows the evaporator to eliminate water drops that might have formed due 

to defrost.

0

0

0

dPo

First defrost after start-up

(y = immediately; n = after the IdF time)

n

y

y

dAF

Defrost delay after continuouscycle

(0 to 23.5 hr)Time interval between the end of the fast freezing cycle and the 

following defrost relatedto it.

0

0

0

FnC

Fans operating mode

C-n = runs with the compressor, OFF during defrost    O-n = continuous mode, 

OFF during defrost      C-y = runs with the compressor, ON during defrost          

O-y = continuous mode, ON during defrost

O-n

O-y

O-y

Fnd

Fans delay after defrost

(0 to 255 min)  Interval between end of defrost and evaporator fans start

10

0

0

FCt

Temperature differential avoiding 

short cycles of fans

(0 to 59°C; FCt = 0 function disabled)  If the difference in temperature 

between the evaporator and the room probes is morethan the value of the 

FCt parameter, the fans are switched ON.

10

0

0

FSt

Fans stop temperature

(-50 to 50°C/ 122°F) Setting of temperature, detected by the evaporator 

probe, above which fans are always OFF.

2

2

2

Fon

Fan ON time

(0 to 15 min)  With Fnc=C_n or C_y, (fan activated in parallel with 

compressor). Sets the evaporator fan ON cycling time when the compressor is 

OFF. When Fon=0 and  FoF not equal to 0, the fans are always OFF, with 

Fon=0 and FoF=0, the fans are always OFF.

0

0

0

FoF

Fan OFF time

(0 to 15 min)With Fnc=C_n or C_y, (fan activated in parallel with compressor). 

Sets the evaporator fan OFF cycling time when the compressor is OFF. When 

Fon=0 and FoF not equal to 0, the fans are always OFF, when Fon=0 and 

FoF=0, the fans are always OFF.

0

0

0

FAP

Probe selection for fan 

management

nP = no probe    P1 = thermostat probe     P2 = evaporator probe      P3 = 

configurable probe      P4 = probe on Hot Key plug

P2

nP

nP

ACH

Kind of regulation for auxiliary 

relay

Ht = heating    CL = cooling

CL

CL

CL

SAA

Setpoint for auxiliary relay

(-100 to 150.0°C; -148 to 302°F)   Defines the room temperature  setpoint to 

switch auxiliary relay.

0

0

0

SHy

Differential for auxiliary output

(0.1 to 25.5°C/ 1 to 255°F)Intervention differential for auxiliary output 

setpoint.     When ACH = CL,  AUX Cut in is SAA + SHy; AUX Cut out is SAA        

When ACH = Ht ,  AUX Cut in is SAA - SHy; AUX Cut out is SAA

2

2

2

ArP

Probe selection for auxiliary

nP = no probe, the auxiliary relay is switched only by the digital input      P1 = 

Probe 1 (thermostat probe)        P2 = Probe 2 (evaporator probe)        P3 = 

Probe 3 (display probe)       P4 = Probe 4

nP

nP

nP

Sdd

Auxiliary relay OFF during defrost

n = the auxiliary relay operates during defrost      y = the auxiliary relay is 

switched OFF during defrost

n

n

n

ALP

Probe selection for alarm

nP = no probe, the temperature alarms are disabled    P1 = Probe 1 

(thermostat probe)    P2 = Probe 2 (evaporator probe)    P3 = Probe 3 (display 

probe)    P4 = Fourth probe

P1

P1

P1

ALC

Temperature alarms configuration

(Ab; rE)  Ab = absolute temperature: alarm temperature is given by the ALL or 

ALU values.   rE= temperature alarms are referred to the setpoint.   

Temperature alarm is enabled whenthe temperature exceeds the SEt + ALU or 

SEt - ALL values.

Ab

Ab

Ab

ALU

Maximum temperature alarm

(SEt to 150°C; SEt to 302°F)When this temperature is reached, the alarm is 

enabled, after the ALd delay time.

110

56

56

ALL

Minimum temperature alarm

(-100 to SEt; -148°C to 230°F)When this temperature is reached, the alarm is 

enabled, after the ALd delay time.

-50

10

10

AFH

Differential for temperature alarm 

recovery

(0.1 to 25.5°C; 1 to 45°F)    Intervention differential for recovery of 

temperature alarm. It is also used for the restartof the fan when the FSt 

temperature is reached.

2

4

4

ALd

Temperature alarm delay

(0 to 255 min)  Time interval between the detection of an alarm condition 

and alarm signaling.

15

30

30

dAo

Exclusion of temperature alarmat 

start-up

(from 0.0 min to 23.5 hr)Time interval between the detection of the 

temperature alarm condition after devicepower ON and alarm signaling.

1.3

2

2

AP2

Probe selection for temperature 

alarm of condenser

nP = no probe   P1 = thermostat probe    P2 = evaporator probe    P3 = 

configurable probe    P4 = probe on Hot Key plug

P4

nP

nP

AL2

Low temperature alarm of 

condenser

(-100 to 150°C)  When this temperature is reached, the LA2 alarm is signaled, 

possibly after the Ad2 delay.

-40

-40

-40

AU2

High temperature alarm of 

condenser

(-100 to 150°C)When this temperature is reached, the HA2 alarm is signaled, 

possibly after the Ad2 delay.

110

110

110

AH2

Differential for temperature 

condenser alarm recovery

(0.1 to 25.5°C; 1 to 45°F)

5

52

52

Ad2

Condenser temperature alarm 

delay

(0 to 255 min)Time interval between the detection of the condenser alarm 

condition and alarm signaling.

15

15

15

dA2

Condenser temperature alarm 

exclusion at start up

(from 0.0 min to 23.5 hr, res. 10 min)

1.3

1.3

1.3

bLL

Compressor OFF with low 

temperature alarm of condenser

n = no: compressor keeps on working   Y = yes, compressor is switched OFF 

until the alarm is present, in any case regulation restarts after Ac time at 

minimum.

n

n

n

AC2

Compressor OFF with high 

temperature alarm of condenser

n = no: compressor keeps on working   Y = yes, compressor is switched OFF 

until the alarm is present, in any case regulation restarts after Ac time at 

minimum.

n

n

n

tbA

Alarm relay silencing (with 

oA3=ALr)

n= silencing disabled: alarm relay stays ON until alarm condition lasts    y 

=silencing enabled: alarm relay is switched OFF by pressing a key during an 

alarm

y

y

y

oA3

Fourth relay configuration (1-4)

dEF, FAn: do not select it!    ALr: alarm; Lig: light; AUS: Auxiliary relay; onF: 

alwaysON with device ON; db= neutral zone; cP2 = do not select it!;   dEF2: do 

not select it!; HES: night blind

Lig

Alr

Alr

AOP

Alarm relay polarity

Set if the alarm relay is open or closed when an alarm happens.  CL= 

terminals 1-4 closed during an alarm   oP = terminals 1-4 open during an 

alarm

CL

CL

CL

i1P

Digital input polarity (18-20)

oP = the digital input is activated by opening the contact     CL = the digital 

input is activated by closing the contact

CL

CL

CL

i1F

Digital input configuration (18-20) dor = door switch functiondEF = activation of a defrost cycle

dor

dor

dor

i2P

2nd digital input polarity (18-19)

oP = the digital input is activated by opening the contact   CL = the digital 

input is activated by closing the contact

CL

CL

CL

i2F

2nd digital input configuration(18-

19)

EAL= external alarm: "EA" message is displayed   bAL= serious alarm "CA" 

message is displayed   PAL= pressure switch alarm, "CA" message is displayed   

dor = door switch function   dEF= activation of a defrost cycle   ES = energy 

saving   AUS = auxiliary relay activation with oA3 = AUS   Htr = kind of action 

inversion (cooling - heating)   FAn = fan   HdF = Holiday defrost (enable only 

with RTC)   onF = to switch the controller OFF

EAL

EAL

EAL

did

(0 to 255 min) with i2F= EAL or i2F 

= bAL digital input alarm delay (18-

20)

Delay between the detection of the external alarm condition and its signaling. 

When i2F= PAL: time for pressure switch function: time interval to calculate 

the number of the pressure switch activation.

15

15

15

doA

Door open signaling delay

(0 to 255 min)

15

15

15

nPS

Pressure switch number

(0 to 15)  Number of activation of the pressure switch, during the did interval, 

before signaling the alarm event (i2F = PAL). If the nPS activation in the did 

time is reached, switch OFF and ON the device to restart normal regulation.

15

15

15

Odc

Compressor status when open 

door

no = normal   Fan = fan OFF   CPr = compressor OFF   F_C = compressor and 

fan OFF

F-C

F-C

F-C

rrd

Outputs restart after doA alarm

no = outputs not affected by the doA alarm   yES = outputs restart with the 

doA alarm

y

y

y

HES

Temperature increase during the 

Energy Saving cycle

(-30.0°C to 30.0°C) Sets the increasing value of the setpoint during the Energy 

Saving cycle.

0

0

0

Adr

Serial address (1 to 244)

Identifies the device address when connected to a MODBUS compatible 

monitoring system.

1

1

1

pbC

Type of probe

Allows to set the kind of probe used by the device:  Pt1 = Pt1000 probe    ntc 

= NTC probe

ntc

ctc

ctc

onF

ON/OFF key enabling

not used = disabled   oFF = enabled      ES = not set it

dP1

Thermostat probe display

dP2

Evaporator probe display

dP3

Third probe display - optional

dP4

Fourth probe display

rSE

Real setpoint

Shows the setpoint used during the energy saving cycle or during the 

continuous cycle.

rEL

Software release

For internal use only

Ptb

Parameter table code

Read-only

OTHER PARAMETERS

ALARMS

CONDENSER TEMPERATURE ALARM

AUXILIARY RELAY

DIGITAL INPUTS

Dixell XR75

REGULATION

DEFROST

FANS

AUXILIARY THERMOSTAT CONFIGURATION (terms. 1-4) - oA3 = AUS

Controller Parameters

Summary of Contents for SSG8B

Page 1: ...SMG8B SSG8B Medium Temperature Self Contained Installation Operation Manual P N 3018126_E AUGUST 2018 IMPORTANT Keep in store for future reference MANUAL I O SMG8B SSG8B Diamond tread bumper shown...

Page 2: ...ORTANT KEEP IN STORE FOR FUTURE REFERENCE Quality that sets industry standards 12999 St Charles Rock Road Bridgeton MO 63044 2483 U S Canada 1 800 922 1919 Mexico 1 800 890 2900 www hussmann com 2018...

Page 3: ...Operation 3 1 Controller Parameters 3 3 Dixell Control Sensor Location 3 6 Controls and Adjustments 3 7 TEV Adjustment 3 8 Self Contained Location 3 8 Load Limits 3 9 Stocking 3 9 MAINTENANCE Care an...

Page 4: ...ANSI Z535 5 DEFINITIONS DANGER Indicate s a hazardous situation which if not avoided will result in death or serious injury WARNING Indicate s a hazardous situation which if not avoided could result...

Page 5: ...he cor rect parts SHIPPING DAMAGE All equipment should be thoroughly examined for shipping damage before and during unloading This equipment has been carefully inspected at our factory Any claim for l...

Page 6: ...ance and may damage the refrig eration system Do NOT remove shipping crate until the merchandiser is positioned for installation Maintain minimum 4 inch air clearance at rear of case Air Intake Air Ex...

Page 7: ...eavy objects on the merchandiser SHIPPING SKID Each merchandiser is shipped on a skid to protect the merchandiser s base and to make positioning the case easier Unscrew the case from the skid The fixt...

Page 8: ...traight upward to clear lower brackets and then down to remove The panel is installed by reversing the above procedure Ensure all panels are installed to prevent air circulation problems The case is s...

Page 9: ...re it can be re positioned as follows A Remove the glass and clamp hardware from the merchandiser by opening the glass and loosening set screws in hinge Metric 3 millimeter set screws B Slide the glas...

Page 10: ...ent After all glass has been adjusted as defined in Step 4 the flexible portion of one gasket at a joint may be trimmed with a razor knife Be sure that the remaining wiper gasket seals the gap Verify...

Page 11: ...of the door frame These must be removed 7 Remove stainless steel top liner by grabbing the rear flange and pulling back Note It is possible to access the adjusting bolt by using a small swivel socket...

Page 12: ...the adjusting bolt clockwise will raise the front glass Turning the adjusting bolt counter clockwise will lower the front glass Once the glass position is set tighten the set screw positive stop 10 O...

Page 13: ...SMG8B SSG8B OPTIONAL DISPLAY PAN WIRE RACK AND DIVIDER KIT The wire shelf with divider fits in the case The divider slides from one end to the other sepa rating meat and seafood products Wire Shelf D...

Page 14: ...extension cord 6 Ensure that the proper electrical requirements for the equipment are supplied 7 Verify field electrical connections are tight 8 Verify all electrical wiring is secured and clear of a...

Page 15: ...dedicated circuit with the amperage stated on the unit Plug into an outlet designed for the plug Do not overload the circuit Do not use long or thin extension cords Never use adapters If in doubt cal...

Page 16: ...e Refrigerant must be recovered before attempting any connection or repair Product will be degraded and may spoil if allowed to sit in a non refrigerated area LOCK OUT TAG OUT To avoid serious injury...

Page 17: ...to browse the parameter codes in programming mode or to decrease the cur rently displayed temperature value Table 4 1 XR75CX Front Panel Keys and Functions onF oFF Switches the light ON and OFF if oA...

Page 18: ...Alarms P1 Discharge temperature probe failure P2 Defrost termination probe failure HA Max temperature alarm LA Min temperature alarm How to set defrost start time Defrost occurs 24 hours after startup...

Page 19: ...lows decimal point display dE dE dE Lod Device display P1 P2 P3 P4 SEt dtr Selects which probe is displayed by the device P1 Thermostat probe P2 Evaporator probe P3 Third probe only for models with th...

Page 20: ...N 10 0 0 FSt Fans stop temperature 50 to 50 C 122 F Setting of temperature detected by the evaporator probe above which fans are always OFF 2 2 2 Fon Fan ON time 0 to 15 min With Fnc C_n or C_y fan ac...

Page 21: ...cP2 do not select it dEF2 do not select it HES night blind Lig Alr Alr AOP Alarm relay polarity Set if the alarm relay is open or closed when an alarm happens CL terminals 1 4 closed during an alarm...

Page 22: ...exico 1 800 890 2900 www hussmann com Safe NET Location on Rear of Case Rear Panel Removed Dixell Control Sensor Location Sensor is located under the gravity coil for SMG8B Sensor is located under the...

Page 23: ...models defrost is time initiated and temperature terminated START UP Follow the Dixell XR75 start up procedures as detailed on Page 3 1 of this manual Each self contained merchandiser has its own eva...

Page 24: ...ence between the two tem peratures is 3 F to 5 F Make adjustments of no more than 1 2 turn of the valve stem at a time and wait for at least 15 minutes before rechecking the probe tem perature and mak...

Page 25: ...rchandiser 24 hours to operate before loading product Proper rotation of product during stocking is necessary to prevent product loss Always bring the oldest product to the top and set the newest to t...

Page 26: ...3 10 Startup Operation P N 3018126_E U S Canada 1 800 922 1919 Mexico 1 800 890 2900 www hussmann com NOTES...

Page 27: ...ar the finish Coarse paper towels on coated glass Ammonia based cleaners on acrylic parts Solvent oil or acidic based cleaners on any interior surfaces Do not use high pressure water hoses Do Remove t...

Page 28: ...d be cleaned every six months Dirty louvers will cause mer chandisers to perform poorly The louvers may be cleaned with a vacuum cleaner Soap and water may be used if all water is removed from the lou...

Page 29: ...CLEANING COILS Condenser coils should be cleaned at least once per month Additional cleaning may be needed depending on the operational environ ment A dirty condenser blocks normal airflow through th...

Page 30: ...educe the pan s capacity This may cause the drain pan waste water to overflow and spill onto the floor Remove accumulated debris from the drain pan A garden hose can be hooked up to the drain pan to d...

Page 31: ...at and air registers fans and doors etc x Check for water leaks x Clean evaporator coil s and fan blade s Do not use an acid base cleaner Rinse off any cleaner residue x Clean discharge air honeycombs...

Page 32: ...4 6 Maintenance P N 3018126_E U S Canada 1 800 922 1919 Mexico 1 800 890 2900 www hussmann com NOTES...

Page 33: ...n motor and blade 7 Lower fan plenum 8 Reconnect fan to wiring harness 9 Turn on power 10 Verify that motor is working and blade is turning in the correct direction 11 Close air gaps under fan plenum...

Page 34: ...l will lubricate the rod and seals Failure to lubricate will severely shorten cylinder life Removing a Cylinder Cylinders are a wear item They are designed to support the glass when fully open to allo...

Page 35: ...mly held in place by the glass clamps Set Screw Locations Apply a drop of Loctite 242 or equivalent threading locking fluid onto each set screw of the glass clamp assembly Tighten all screws with a TO...

Page 36: ...tight fit HINGE HARDWARE Type Two cylinders and one fastening point P N 0401884 Used on 8 ft and 12 ft 2438 mm and 3658 mm parent cases and as a joining bracket Type Two cylinders and three fastening...

Page 37: ...information or other support contact your Hussmann representative Please include the model and serial number of the product Hussmann Corporation Corporate Headquarters Bridgeton Missouri U S A 63044 2...

Page 38: ...Hussmann Corporation 12999 St Charles Rock Road Bridgeton MO 63044 2483 www hussmann com...

Reviews: