8
Cap Tube -
.042 ID x .020 Wall Thick
x
83"
Min. Fuse Size -
15 amps
Refrig. Charge -
23 ounces R 404
652.05
grams
Operating Pressure 75F/24C
90F/32C
Head
215
235
Suction 10
10.5
TROUBLESHOOTING CHART
TROUBLE
POSSIBLE CAUSE
REMEDY
Compressor starts but
immediately cuts out on
overload.
1. Low voltage
1. Check voltage at cabinet.
Should be within 5% of serial
plate rating
2. Relay defective
2. Replace
Compressor will not start, no
hum.
1. Power disconnected
1. Reconnect power
2. Power switch off
2. Reposition switch to ON
3. Blown or tripped breaker
3. Reset breaker
4. Defective wiring
4. Repair or replace
5. Defective temp control
5. Replace
6. Defective overload
6. Replace
Compressor will not start, hums
but cycles on overload
1. Low Voltage
1. Check voltage at cabinet.
Should not be more than 5%
below serial plate rating.
2. Defective compressor
2. Replace
3. Defective relay
3. Replace
4. Restriction (pinched cap
tube)
4. Replace cap tube