background image

Rev. 0308

19

Refrigeration

Average

Disch. Air T~Stat

Fans

        Defrosts

       Elec. Load (Amps) @ ~115 VAC

Btu / Hr.

Temperatures (°F) Speed

Settings Coil

Size(in.)&

        per day

Evap      Airsweep

Case Case Defrost Std.

Length / Application (Ft.) (Total) Evap. Prod. Disch.

(FPM)

(°F)

Type

Pitch° (Qty.)

Min. Qty. Fans Fans Heater Warmer Lights Heater Outlet Drain

ASC-L / ASCS-L

-  

Electric Defrost Option

4' Frozen food

370 1,480

-20° -5° -10°

150

-10° Forced

Evap / 8” x 10° (1)

60

2

.60

0.36

1.04

.35

1.83

4.72

15

1.04

Ice Cream

450 1,800

-30 -10° -20°

150

-20°

Air Airsweep / 4

1

/

2

”Axial (2)

(208V)

6' Frozen food

370 2,200

-20° -5° -10°

150

-10° Forced

Evap / 8” x 10° (1)

60

2

.60

0.36

1.57

.52

1.83

5.10

15

1.57

Ice Cream

450 2,700

-30 -10° -20°

150

-20°

Air Airsweep / 4

1

/

2

”Axial (2)

(208V)

8' Frozen food

370 2,960

-20° -5° -10°

150

-10° Forced

Evap / 8” x 10° (1)

60

2

.60

0.36

2.09

.70

1.83

10.82

15

2.09

Ice Cream

450 3,600

-30 -10° -20°

150

-20°

Air Airsweep / 4

1

/

2

”Axial (2)

(208V)

10'Frozen food

370 3,700

-20° -5° -10°

150

-10° Forced

Evap / 8” x 10° (2)

60

2

1.20

0.54

3.48

.87

3.05

10.10

15

3.48

Ice Cream

450 4,500

-30 -10° -20°

150

-20°

Air Airsweep / 4

1

/

2

”Axial (3)

(208V)

12'Frozen food

370 4,400

-20° -5° -10°

150

-10° Forced

Evap / 8” x 10° (2)

60

2

1.20

0.54

3.13

1.04

3.05

10.10

15

3.13

Ice Cream

450 5,400

-30 -10° -20°

150

-20°

Air Airsweep / 4

1

/

2

”Axial (3)

(208V

ASC-L / ASCS-L

-  KOOL-GAS ™ 

Defrost Option

4' Frozen food

370 1,480

-20° -5° -10°

150

-10° Forced

Evap / 8” x 10° (1)

20

2

.60

0.36

1.04

.35

1.83

4.72

15

1.04

Ice Cream

450 1,800

-30 -10° -20°

150

-20°

Air Airsweep / 4

1

/

2

”Axial (2)

(208V)

6' Frozen food

370 2,200

-20° -5° -10°

150

-10° Forced

Evap / 8” x 10° (1)

20

2

.60

0.36

1.57

.52

1.83

5.10

15

1.57

Ice Cream

450 2,700

-30 -10° -20°

150

-20°

Air Airsweep / 4

1

/

2

”Axial (2)

(208V)

8' Frozen food

370 2,960

-20° -5° -10°

150

-10° Forced

Evap / 8” x 10° (1)

20

2

.60

0.36

2.09

.70

1.83

10.82

15

2.09

Ice Cream

450 3,600

-30 -10° -20°

150

-20°

Air Airsweep / 4

1

/

2

”Axial (2)

(208V)

10'Frozen food

370 3,700

-20° -5° -10°

150

-10° Forced

Evap / 8” x 10° (2)

20

2

1.20

0.54

3.48

.87

3.05

10.10

15

3.48

Ice Cream

450 4,500

-30 -10° -20°

150

-20°

Air Airsweep / 4

1

/

2

”Axial (3)

(208V)

12'Frozen food

370 4,400

-20° -5° -10°

150

-10° Forced

Evap / 8” x 10° (2)

20

2

1.20

0.54

3.13

1.04

3.05

10.10

15

3.13

Ice Cream

450 5,400

-30 -10° -20°

150

-20°

Air Airsweep / 4

1

/

2

”Axial (3)

(208V

Set (PSI)

Size

Voltage

Ampacity

Out

In

(HP)

(VAC)

ASC-L / ASCS-L Self Contained Data

-  

Electric Defrost Option

4'

20

50

1/2

115

11.1

6'

20

50

3/4

115

15.6

8'

20

50

3/4

208/230

8.5

10'

20

50

1

208/230

10.6

12'

20

50

1 1/4

208/230

11.0

ASC-L / ASCS-L Self Contained Data

-  

Not Available with Kool-Gas Defrost Option

Summary of Contents for ASC-L

Page 1: ...ASCS L SERVICE GELATO AND ICE CREAM REV 0308 Installation Operation Manual ASC L ASCS L Lift up Curved Glass Refrigerated Service Gelato and Ice Cream Case p n IGSF ASC L ASCS L 0308 INSTALLATION OPE...

Page 2: ...Hussmann Chino notify Hussmann Chino If such a shortage involves the carrier notify the carrier immediately and request an inspection Hussmann Chino will acknowledge shortages within ten days from re...

Page 3: ...nt position as possible Remove the top of the crate Detach the walls from each other and remove from the skid Unbolt the case from the skid The fixture can now be lifted off the crate skid Lift only a...

Page 4: ...gs over the highest part of the floor so that case is level Prevent damage case must be raised under leg or by use of 2x6 or 2x4 leg brace Remove side and back leg braces after case is set 3 Set secon...

Page 5: ...gerators or between a refrigerator and a wall provide means to prevent freezing The water seal should be insulated to prevent condensation Refrigeration GELATO SOFT ICE CREAM These display cases are d...

Page 6: ...Some supermarkets require a 4th sensor in the return air Case controllers will be located in the electrical race way or under the case THERMOSTATIC EXPANSION VALVE LOCATION This device is located on t...

Page 7: ...ay and duration up to 4 hours Four Relay Outputs Compressor defrost evaporator fan and alarm Adjustable Short Cycle Protection Extra protection for the equipment Non volatile memory The programmed par...

Page 8: ...mp down amount of time the compressor remains on after defrost initiates 0 to 59 min Drip time amount of time the compressor is locked out after defrost is terminated 0 to 59 min Defrost duration time...

Page 9: ...the upper right corner Fig 9 Sensor Connectors 3 Connecting the refrigeration defrost equipment Connect the wires from the compressor including the thermostat to the correspondent terminal on the bott...

Page 10: ...low these steps Step 1 SET Press and hold SET for 5 seconds The display will show CLoC Step 2 SET Press SET again to change the time of day Step 3 or Press UP or DOWN until the correct time of day is...

Page 11: ...nimum Compressor OnTime Con Minimum time that the compressor will remain turned on Range from 0 to 15 min Alarm Delay ALrd Time delay before the alarm goes off after the temperature fall off the two a...

Page 12: ...me Press UP or DOWN until the 11 59 PM appears on the display Press SET Press DOWN ten times to exit the programming level Error Codes Display Control Status Er 1 ERC Fault software or hardware failur...

Page 13: ...epower Rating hp 1 1 5 2 FLA LRA 16 96 12 72 12 72 Pilot Duty 470 470 470 DEFROST SPST NC 120VAC 208VAC 240VAC ResistiveAmps 16 16 16 Horsepower Rating hp 1 2 3 4 1 Pilot Duty VA 470 470 470 EVAPORATO...

Page 14: ...PERAGE Field Wiring must be sized for component amperes printed on the serial plate Actual ampere draw may be less than specified Field wiring from the refrigeration control panel to the merchandisers...

Page 15: ...applicable Refrigeration performance will be seriously affected if left open for a prolonged period of time 8 Avoid the use of supplemental flood or spot lighting Display light intensity has been des...

Page 16: ...CARE Improper cleaning not only accelerates the cleaning cycle but also degrades the quality of this surface Normal daily buffing motions can generated static cling attracting dust to the surface Inc...

Page 17: ...de edge of the glass panel 3 Remove or re adjust the glass panel servicing always replace fan with a fan of the same specifi cations COPPER COILS The copper coils used in Hussmann merchandisers may be...

Page 18: ...800 5 10 5 120 5 Forced 41 2 4 16 1 0 72 1 04 3 05 15 0 3 13 Air Axial 208V ASC L ASCS L Ice Cream Electric Defrost Option 4 450 1 800 30 10 20 150 20 Forced 41 2 1 30 2 0 18 0 35 1 83 15 65 15 0 1 04...

Page 19: ...1 20 0 54 3 13 1 04 3 05 10 10 15 3 13 Ice Cream 450 5 400 30 10 20 150 20 Air Airsweep 41 2 Axial 3 208V ASC L ASCS L KOOL GAS Defrost Option 4 Frozen food 370 1 480 20 5 10 150 10 Forced Evap 8 x 10...

Page 20: ...VAC 50 60 Hz M M CANOPY LIGHTING 2 F25T8 SPX30 ANTI SWEAT HEATER 1 180W 115 VAC 125 01 3032 ANTI SWEAT FANS COMAIR ROTRON MX2B1 E1 2 0 18A 115 VAC 125 01 2012 A EVAPORATOR FANS EBM PAPST MODEL 9906L 0...

Page 21: ...LEDGE LIGHTS 2 FP28T5 830 BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L CANOPY LIGHTS 4 F32T8 SPX30 NOSE LIGHTS 2 F32T8 SPX30 AiR SWEEP FANS 2 4 AXIAL MOTORS LIGHT SWITCH...

Page 22: ...of food into the refrigerator which includes such items as a Initial temperature performance Coils should be properly fed with a refrigerant according to Hussmann s recommendations b Observation of ou...

Page 23: ...direct sunlight 9 Are display signs blocking or diverting air flow 10 Are the coils of the refrigerator iced up 11 Is the store ambient over 75 F 55 RH as set forth in ASHRAE Standard 72 and ASHRAE St...

Page 24: ...age equipment doors should be kept closed during periods of inactivity f Minimize the transfer time of perishables from storage to display g Keepmeatunderrefrigerationinmeatcuttingand processing area...

Page 25: ...er this warranty shall be limited to a period not to exceed five years from date of factory shipment On Hussmann refrigeration systems an additional 4 year extended warranty for the motor compressor a...

Page 26: ...particular unit They can be found on a small metal plate on the unit Please note them below for future reference MODEL SERIAL NUMBER Chino Additional copies of thispublication may be obtained by cont...

Reviews: