ElectroVap RTH
Changing Unit Configuration
Menu
Software Assistant
MENU: CHANGING UNIT
CONFIGURATION
To gain entry, dial access code 2.3.4 :
Press the key and the first digit will
flash
Using the keys enter the first digit
of the access code and then press
the key to confirm. The next digit will
start to flash. Repeat for a second and
third digit of the access code.
DIAL ACCESS CODE
: XXX
SELECTED CONTROL
SIGNAL : ………..
STEAM CAPACITY
LIMIT : .…%.
SET POINT
ADJUSTEMENT…..%HR
Limits steam output from 100%
down to 50% of units maximum.
MAINTENANCE
FREQUENCY …..KG/ST
Allows adjustment of the estimated
number of kg of steam to be
produced before next maintenance.
Allows selectio
n of the control signal
you wish to use.
OR
If on-off humidistat or external
proportional sensor/controller are
used, set point & propl band are not
set on the humidifier display, but on
the humidistat or external control.
PROPORTIONAL BAND
ADJUSTMENT …..%
22
CYCLIC DRAINING TIME
.…..
DRAINING IF LONG STOP
YES / NO
This allows adjustment of the short
duration drains after a succession of
water intakes.
Automatic inactivity (end of season)
drain when there is no steam
production for 72 hours. Adjustable 1
MAINTENANCE INTERVAL
…..H
Sets the hours of operation until the
next tank maintenance message
appears on the display screen.
Maintains the water tank temperature
at 150°F while the humidifier is not
producing steam. For freeze protect-
ion and / or faster steam production
for closer humidity control.
TANK COOLING
YES / NO
This enables a cooling cycle of the
water tank before its maintenance
WATER TEMP.
MAINTAINED AT …….°C
Adjusts the temperature maintained
inside the tank when the humidifier is
stopped
WATER TEMP. AT 65°C
YES / NO