Service/maintenance
OPERATION MANUAL
Chapter 7
Unichiller® eo Desktop
V2.2.0en/09.08.21//17.12
74
Cooling*
Description
Maintenance
interval
Comment
Person re-
sponsible
A/W
Exchange safety-
relevant electric
and electrome-
chanical compo-
nents
20 years
Have the exchange only carried
out by certified personnel (such as
Huber service engineers). Please
contact Customer Support.
→
Page
Operating
company
*A = Air cooling; W = Water cooling; U = Applicable only for Unistats
7.3.2
Replacing temperature control or coolant hoses
Replace defective temperature control and/or coolant hoses
before
turning on the temperature
control unit.
7.3.2.1
Replacing temperature control hoses
PROCEDURE
Drain the temperature control unit.
→
»Draining externally open applications«
Replace defective temperature control hoses. Follow the instructions for the proper disposal.
→
»Proper disposal of resources and consumables«
Reconnect your external application.
→
»Connecting an externally open application«
Fill the temperature control unit with thermal fluid.
→
Vent the temperature control unit.
→
»Filling and venting externally open
Restart the temperature control unit in normal mode.
7.3.2.2
Replacing coolant hoses
PROCEDURE
Drain the cooling water.
→
Replace the defective coolant hoses. Follow the instructions for the proper disposal.
→
Page 15,
section
»Proper disposal of resources and consumables«
Reconnect the temperature control unit to the building’s cooling water supply.
→
Page 28, sec-
tion
»Temperature control units with water cooling«
Restart the temperature control unit in normal mode.
7.3.3
Clean liquefier fins (air-cooled temperature control unit)
Manual cleaning
RISK OF BEING CUT ON THE LIQUEFIER FINS
Wear suitable cut-resistant gloves for cleaning work.
Depending on the ambient conditions, use cleaning equipment such as vacuum cleaners and/or
a hand brush/brush. Follow the local regulations when cleaning. Do not clean the liquefier fins
in a clean room with items like a brush and do not use a vacuum cleaner without an extra-fine
particle filter.
Cleaning using pointed or sharp-edged tools
DAMAGE TO THE LIQUEFIER FINS
Clean the liquefier fins using suitable cleaning appliances.
Make sure there is adequate ventilation (removal of waste heat, fresh air supply) for the tempera-
ture control unit, in case of
air cooling, maintain wall clearance
.
→
Page 20, section
illustrations of the cooling variants«
and
→
The liquefier fins must be cleaned (dust) from time to time as only then will the temperature con-
trol unit perform at its maximum cooling capacity.