Audible Alarm
Push the alarm enable/disable button to enable or disable the alarm (see
Figure 16). If the green alarm LED is lit the alarm is enabled. If the green alarm
LED is not lit the alarm is disabled.
Surge Counter
The surge counter displays the number of transient voltage surges since the
counter was last reset. The counter is battery powered to retain memory in the
event of a power loss to the HBL module. To reset the surge counter, remove all
power and press the small switch located inside the unit on the underside of the
diagnostic circuit board near the RJ45 connectors (also refer to Figure 17). This
will reset the counter to zero.
Figure
15:
Three-Phase Diagnostic Display Panel with Surge Counter
www.hubbell-wiring.com
Made in USA
8232-0031A
Push-to- Test:
= O K
= Replace Module
Surge
Counter
Audible
Alarm
AØ
BØ
CØ
Alarm
enable/disable
push button
Phase LEDs
On-Line diagnostics
push buttons
Surge counter
Surge counter
reset switch
(on diagnostic
circuit board)
Description of
phase LEDs
Alarm LED
Enable alarm
Disable alarm
Note:
Phase B is not presented on single phase applications.
Figure
16:
Rear of Diagnostic Circuit Board
Dry contacts
Diagnostic display
connectors
Surge counter
reset switch
(white)
Dry contacts
Diagnostic display
connectors
Surge counter
reset switch
(white)
SpikeShield
®
Modular Panel Surge Protective Device (SPD)
OPERATION