Page 2 of 5
3940 Dr. Martin Luther King Drive
St. Louis, MO 63113
P/N 00912336 FORM NO. K1225 R09/16 ECO-7-023-16
This device cannot be used as a replacement for
VSQ series or other hazardous location devices.
VSQ & VWSQ covers are NOT interchangeable.
1. APPLICATIONS
•
VWSQ series dead front interlocked receptacle
with switch
• Designed for supplying power to fixed or
portable electrical equipment.
2. ELECTRICAL RATING
Maximum voltage – 600 VAC @ 50-400Hz.
Continuous Current – 30 Amperes.
Mounting Arrangement:
1. Receptacle assembly must be mounted
securely onto column, wall, or other structure
that is able to support the device and associated
conduit system. Structure is to be prepared for
use of four (4) 3/8” steel bolts (furnished by
others) using lugs in the enclosure spaced as
shown in Fig. 1. Device is equipped with factory
installed hinges. Device must be mounted with
the hinges on the bottom and the receptacle
mounted in downward direction.
Conduit Installation:
1. 1 ½” NPT conduit entries are provided on top
and bottom of the housing.
2. Make sure conduit entries are clean before
installing conduit/close-up plugs/reducers
etc. Killark “LUBG” thread lubricant is
recommended for this application.
Wiring
1. Develop and establish the wiring pattern
for your system. Locations having different
voltages and/or frequencies must not have
interchangeable attachment plugs. Always test
before energizing.
2. Make sure to pull sufficient length of supply
conductors to connect the enclosed terminals.
3. Strip the conductors to the length shown in
table.
WARNING: Use only copper cable or wire for the range
indicated in the table. 75
°
C rated conductors (minimum).
Wire Range
Strip Length
Torque
Switch
#10 - #8
0.750 inches
20 lb-in.
Ground
#16 - #6
0.500 inches
20 lb-in.
Fig. 1